{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6B0C11N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6B0C11N6","canonicalUrl":"https://aoctrl.com/schneider/ATV6B0C11N6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6B0C11N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600 series, ATV6B0C11N6 modular AC drive, 75 kW at 500 V normal duty, 55 kW heavy duty, STO SIL 3, integrated EMC filter Category C3, cabinet mount.","salesMarkdown":"## 75 kW at 500 V — normal duty vs heavy duty selection The ATV6B0C11N6 is the 75 kW normal duty / 55 kW heavy duty frame in the Altivar Process ATV600 family, rated at 500 V supply. Normal duty delivers 98 A line current and 85 kVA apparent power; heavy duty drops to 72 A and 62 kVA. This split matters: if your load is a variable-torque pump or fan, normal duty covers the full 75 kW. For constant-torque loads like a conveyor or extruder, use the heavy-duty column — the drive has more thermal headroom for sustained torque at low speed. The drive handles both synchronous and asynchronous motors, so it works with permanent-magnet motors or standard induction machines. Braking is by DC injection — no built-in braking chopper, so if you need dynamic braking for overhauling loads, budget an external braking resistor and the corresponding option. ## STO SIL 3 and integrated protections That means the drive can be used in safety circuits up to SIL 3 without external safety contactors — the drive itself removes torque from the motor when the STO input is de-energized. This is the same functional safety level you'd spec for a press, robot cell, or any guarded machine where unexpected startup would be a hazard. The protection list covers both motor and drive sides: thermal protection, motor phase break, output earth fault, short circuit, DC bus overvoltage, line supply undervoltage, phase loss, and overspeed. That's a complete set — you don't need to add separate motor protection relays for most applications. The drive monitors its own health and the motor's health through the same firmware. ## Modular build and fieldbus options This is the modular version — the drive ships as separate power module, control unit, mounting kit, power connection set, and fuses. That means the power section and control section can be replaced independently. If a control board fails, you swap just the control unit without pulling the power wiring. The kit includes fuses sized for the drive, so you don't have to calculate the fuse rating from scratch. Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (with three connector variants). The base drive already has dual Ethernet at 10/100 Mbit/s running Modbus TCP and a 2-wire RS-485 Modbus serial port. For a new line, PROFINET or EtherNet/IP are the usual choices; for a legacy plant, Profibus or CANopen keeps the drive on the existing bus. ## EMC, harmonics, and SCCR The integrated EMC filter is rated for 300 m motor cable and meets IEC 61800-3 Category C3 — that's the second environment (industrial), so it's suitable for most factory floors without an external filter. Total harmonic current distortion is under 5% at full load per IEEE 519, which means the drive won't cause nuisance tripping of upstream breakers or overheat distribution transformers in most installations. Prospective line short-circuit current is 50 kA — that's the SCCR the drive can withstand at its input terminals. Your upstream protective device must be rated to interrupt at least that level. The pollution degree is 2 (IEC 61800-5-1), meaning the drive expects a clean, non-conductive environment inside the cabinet — no condensation, no conductive dust. Sourced through independent distribution channels — quoted to order against your BOM quantity. No stock-holding claim; the supply posture is per-RFQ confirmation.","metaTitle":"Schneider ATV6B0C11N6 Altivar Process Drive, 75 kW, 500 V","metaDescription":"Schneider Electric ATV6B0C11N6 Altivar Process ATV600 AC drive, 75 kW normal duty at 500 V, modular version, STO SIL 3, integrated EMC filter C3.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drives (VFD)"],"specifications":{"title":"ATV6B0C11N6","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"70 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"Variable speed drive, Altivar Process ATV600, APM, Low Harmonic 500 V, 75 kW","Line current":"98.0 A 500 V normal duty) 72.0 A 500 V heavy duty)","Maximum THDI":"<5 % full load IEEE 519","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"85 kVA at 500 V normal duty 62 kVA at 500 V heavy duty","Motor power kW":"75.0 kW at 500 V normal duty 55.0 kW at 500 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 1.0 power module 200 kW","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6B0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"< 2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 3890 W 2.5 kHz normal duty) Forced convection 3465 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Number Of Preset Speeds":"16 preset speeds","Network number of phases":"3 phases","Continuous output current":"125.0 A at 2.5 kHz normal duty 105.0 A at 2.5 kHz heavy duty","Maximum transient current":"137.5 A 60 s normal duty) 157.5 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"500 V - 10...15 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/nl/en/product/ATV6B0C11N6/variable-speed-drive-altivar-process-atv600-apm-low-harmonic-500-v-75-kw/"},"ai":{"faq":[{"question":"Where can I buy ATV6B0C11N6 and how do I get a price?","answer":"The ATV6B0C11N6 is sourced to order through independent distribution."},{"question":"What is the closest alternative to ATV6B0C11N6 in the Altivar Process family?","answer":"The ATV600 series includes other power ratings — the 75 kW normal duty frame is specific to this order code. For a different power level, consult the Altivar Process ATV600 catalog for the corresponding frame size."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6B0C11N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6B0C11N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}