{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6B0C11Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6B0C11Q6","canonicalUrl":"https://aoctrl.com/schneider/ATV6B0C11Q6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6B0C11Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600, modular VFD, ATV6B0C11Q6, 110 kW ND / 90 kW HD at 690 V, integrated C3 EMC filter, STO SIL 3.","salesMarkdown":"The ATV6B0C11Q6: The 110 kW at 690 V normal duty and 90 kW at 690 V heavy duty ratings are what you size the drive against. Normal duty covers constant-torque loads like conveyors; heavy duty handles the higher peak demands of crushers or extruders. The line current at 690 V is 102 A normal duty, 85 A heavy duty — these are the numbers for sizing input fusing and cabling. The integrated EMC filter is rated for 984.3 ft (300 m) of motor cable under IEC 61800-3 category C3. That means you can run cable lengths up to 300 m without an external filter in a typical industrial environment — saves panel space and installation time. That's a functional safety requirement for many machine safety circuits — it lets you remove torque without a power disconnect, which is useful for clearing jams or during setup. Prospective line short-circuit current rating is 50 kA. That's the fault current the drive can withstand on its input — important for coordination with upstream protection in high-capacity panels. The drive has a Slot A for communication modules — you can fit Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (with RJ45, SUB-D 9, or screw terminal options). Slot A and Slot B also accept digital/analog I/O extension modules and output relay extension modules. That means you can field-fit the exact fieldbus and I/O count without swapping the whole drive. Built-in Modbus serial at 4.8, 9.6, 19.2, 38.4 kbit/s and Ethernet IP/Modbus TCP at 10/100 Mbit/s. The Ethernet port supports half/full duplex and autonegotiation. For Modbus RTU, the physical interface is 2-wire RS-485, configurable 8-bit data with odd, even, or no parity. Cabinet mount, with UL Type 1 and Type 12 enclosure ratings for cabinet integration. That covers indoor use where you need some protection from falling dirt and dripping water (Type 1) or from dust and non-corrosive liquids (Type 12). Forced convection cooling — keep the airflow paths clear in the panel. Operating altitude is below 2000 m with current derating above 1000 m. If this drive is going into a high-altitude site, factor that into the sizing. Pollution degree 2 per IEC 61800-5-1 — typical for a clean industrial control room. Vibration resistance: 1.5 mm peak-to-peak at 2–13 Hz, 0.5 gn at 13–200 Hz per IEC 60068-2-6. Shock resistance: 4 gn for 11 ms per IEC 60068-2-27. It'll handle normal industrial floor vibration, but if it's going on a crusher or near a press, check the mounting isolation. ## Protection and safety functions The drive packs a full suite of protections: thermal protection for both motor and drive, safe torque off, motor phase break, overcurrent between output phases and earth, overload of output voltage, short-circuit protection, overvoltages on the DC bus, line supply over/undervoltage, line supply phase loss, and overspeed. That's a lot of coverage — you won't need many external relays for basic motor protection. Braking to standstill is by DC injection — no external braking resistor needed for stopping, though for vertical loads or rapid decel you'd still want the resistor option.","metaTitle":"Schneider ATV6B0C11Q6 Altivar Process ATV600 Drive, 110 kW N","metaDescription":"Schneider ATV6B0C11Q6 Altivar Process ATV600 drive. 110 kW normal duty / 90 kW heavy duty at 690 V. Integrated C3 EMC filter for 300 m cable. STO SIL 3. Active production. RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV6B0C11Q6","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"70 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"Variable speed drive, Altivar Process ATV600, APM, Low Harmonic 690 V, 110 kW","Line current":"102.0 A 690 V normal duty) 85.0 A 690 V heavy duty)","Maximum THDI":"<5 % full load IEEE 519","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"122 kVA at 690 V normal duty 101 kVA at 690 V heavy duty","Motor power kW":"110.0 kW at 690 V normal duty 90.0 kW at 690 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 1.0 power module 200 kW","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6B0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"< 2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 4290 W 2.5 kHz normal duty) Forced convection 2900 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Number Of Preset Speeds":"16 preset speeds","Network number of phases":"3 phases","Continuous output current":"125.0 A at 2.5 kHz normal duty 105.0 A at 2.5 kHz heavy duty","Maximum transient current":"137.5 A 60 s normal duty) 157.5 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"690 V - 10...10 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/ATV6B0C11Q6/variable-speed-drive-altivar-process-atv600-apm-low-harmonic-690-v-110-kw/"},"ai":{"faq":[{"question":"What are the key power ratings for this drive?","answer":"The ATV6B0C11Q6 is rated for 110 kW at 690 V normal duty and 90 kW at 690 V heavy duty. Line current is 102 A normal duty and 85 A heavy duty at 690 V."},{"question":"What safety functions does the ATV6B0C11Q6 include?","answer":"It includes STO (safe torque off) rated SIL 3 per IEC 61508 and IEC 13849-1, plus comprehensive protections for both motor and drive including thermal, overcurrent, short-circuit, and line supply monitoring."},{"question":"What communication options are available?","answer":"Built-in Modbus serial (RS-485, RTU) at up to 38.4 kbit/s and Ethernet IP/Modbus TCP at 10/100 Mbit/s. Slot A accepts optional modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen."},{"question":"What is the EMC filter rating?","answer":"The integrated EMC filter is rated for 984.3 ft (300 m) of motor cable under IEC 61800-3 category C3, suitable for typical industrial environments without an external filter."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6B0C11Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6B0C11Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}