{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6B0C11Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6B0C11Q6","canonicalUrl":"https://aoctrl.com/schneider/ATV6B0C11Q6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6B0C11Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600, modular VFD, ATV6B0C11Q6, 110 kW ND / 90 kW HD at 690 V, integrated C3 EMC filter, STO SIL 3.","salesMarkdown":"The ATV6B0C11Q6: The 110 kW at 690 V normal duty and 90 kW at 690 V heavy duty ratings are what you size the drive against. Normal duty covers constant-torque loads like conveyors; heavy duty handles the higher peak demands of crushers or extruders. The line current at 690 V is 102 A normal duty, 85 A heavy duty — these are the numbers for sizing input fusing and cabling. The integrated EMC filter is rated for 984.3 ft (300 m) of motor cable under IEC 61800-3 category C3. That means you can run cable lengths up to 300 m without an external filter in a typical industrial environment — saves panel space and installation time. That's a functional safety requirement for many machine safety circuits — it lets you remove torque without a power disconnect, which is useful for clearing jams or during setup. Prospective line short-circuit current rating is 50 kA. That's the fault current the drive can withstand on its input — important for coordination with upstream protection in high-capacity panels. The drive has a Slot A for communication modules — you can fit Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (with RJ45, SUB-D 9, or screw terminal options). Slot A and Slot B also accept digital/analog I/O extension modules and output relay extension modules. That means you can field-fit the exact fieldbus and I/O count without swapping the whole drive. Built-in Modbus serial at 4.8, 9.6, 19.2, 38.4 kbit/s and Ethernet IP/Modbus TCP at 10/100 Mbit/s. The Ethernet port supports half/full duplex and autonegotiation. For Modbus RTU, the physical interface is 2-wire RS-485, configurable 8-bit data with odd, even, or no parity. Cabinet mount, with UL Type 1 and Type 12 enclosure ratings for cabinet integration. That covers indoor use where you need some protection from falling dirt and dripping water (Type 1) or from dust and non-corrosive liquids (Type 12). Forced convection cooling — keep the airflow paths clear in the panel. Operating altitude is below 2000 m with current derating above 1000 m. If this drive is going into a high-altitude site, factor that into the sizing. Pollution degree 2 per IEC 61800-5-1 — typical for a clean industrial control room. Vibration resistance: 1.5 mm peak-to-peak at 2–13 Hz, 0.5 gn at 13–200 Hz per IEC 60068-2-6. Shock resistance: 4 gn for 11 ms per IEC 60068-2-27. It'll handle normal industrial floor vibration, but if it's going on a crusher or near a press, check the mounting isolation. ## Protection and safety functions The drive packs a full suite of protections: thermal protection for both motor and drive, safe torque off, motor phase break, overcurrent between output phases and earth, overload of output voltage, short-circuit protection, overvoltages on the DC bus, line supply over/undervoltage, line supply phase loss, and overspeed. That's a lot of coverage — you won't need many external relays for basic motor protection. Braking to standstill is by DC injection — no external braking resistor needed for stopping, though for vertical loads or rapid decel you'd still want the resistor option.","metaTitle":"Schneider ATV6B0C11Q6 Altivar Process ATV600 Drive, 110 kW N","metaDescription":"Schneider ATV6B0C11Q6 Altivar Process ATV600 drive. 110 kW normal duty / 90 kW heavy duty at 690 V. Integrated C3 EMC filter for 300 m cable. STO SIL 3. Active production. RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Current":"102.0 A 690 V normal duty) 85.0 A 690 V heavy duty)","Frequency":"50...60 Hz - 5...5 %","Product Status":"Active","Pollution Degree":"Pollution degree 2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.1 °C","Temperature Storage":"-40...158 °F (-40...70 °C)","Main Product Or Component Type":"Variable speed drive"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/ATV6B0C11Q6/variable-speed-drive-altivar-process-atv600-apm-low-harmonic-690-v-110-kw/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV6B0C11Q6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6B0C11Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6B0C11Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}