{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6B0C20Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6B0C20Q6","canonicalUrl":"https://aoctrl.com/schneider/ATV6B0C20Q6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6B0C20Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600, modular version, ATV6B0C20Q6, 200 kW normal duty at 690 V, integrated EMC filter category C3, STO SIL3.","salesMarkdown":"## Drive brief The ATV6B0C20Q6 is a modular Altivar Process ATV600 drive sized for 200 kW at 690 V three-phase normal duty — it runs a 200 kW asynchronous or synchronous motor under constant torque, with headroom to 160 kW for heavy-duty (high overload) applications. Line current pulls 183 A at 690 V normal duty; feeder and upstream protection must accommodate that, with a prospective short-circuit current rating of 50 kA. The integrated EMC filter meets IEC 61800-3 category C3, supporting up to 300 m of motor cable in industrial environments — external filter is not needed for typical panel installations. Safe Torque Off (STO) is built-in to SIL 3, allowing the drive to be wired directly into a safety circuit without an external safety relay, simplifying the safety chain. Communication options via slot A modules include Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, and CANopen; the base unit includes Modbus TCP slave. ## Integration notes Cabinet mount, forced convection cooled. Pollution degree 2. Vibration resistance per IEC 60068-2-6: 1.5 mm peak-to-peak at 2–13 Hz, 0.5 gn at 13–200 Hz. Allow clearance for the 200 kW power module and its included mounting kit, power connection set, and fuses. Switching frequency adjustable from 2 to 4.9 kHz with derating; braking via DC injection. Control wiring via removable screw terminals, line and motor connections via M10 bars.","metaTitle":"Schneider ATV6B0C20Q6 Altivar Process ATV600 Drive, 200 kW","metaDescription":"Current-production ATV6B0C20Q6 drive, 200 kW at 690 V, integrated C3 EMC filter, STO SIL3. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV6B0C20Q6","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"70 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"Variable speed drive, Altivar Process ATV600, APM, Low Harmonic 690 V, 200 kW","Line current":"183.0 A 690 V normal duty) 148.0 A 690 V heavy duty)","Maximum THDI":"<5 % full load IEEE 519","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"219 kVA at 690 V normal duty 177 kVA at 690 V heavy duty","Motor power kW":"200.0 kW at 690 V normal duty 160.0 kW at 690 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 1.0 power module 200 kW","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6B0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"< 2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 7560 W 2.5 kHz normal duty) Forced convection 6080 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Number Of Preset Speeds":"16 preset speeds","Network number of phases":"3 phases","Continuous output current":"215.0 A at 2.5 kHz normal duty 175.0 A at 2.5 kHz heavy duty","Maximum transient current":"236.5 A 60 s normal duty) 262.5 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"690 V - 10...10 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/th/en/product/download-pdf/ATV6B0C20Q6?filename=Schneider+Electric_Altivar-Process-ATV600_ATV6B0C20Q6.pdf', 'path_name': '87d1d9f46afac8dc4da60fcb9ed027bf.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/87d1d9f46afac8dc4da60fcb9ed027bf.pdf', 'status': 1}","sourceUrl":"https://www.se.com/in/en/product/ATV6B0C20Q6/variable-speed-drive-altivar-process-atv600-apm-low-harmonic-690-v-200-kw/"},"ai":{"faq":[{"question":"What are the key ratings of this drive?","answer":"Rated at 200 kW normal duty at 690 V, with an integrated C3 EMC filter supporting 300 m motor cable, and Safe Torque Off to SIL 3."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6B0C20Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6B0C20Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}