{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6B0C25Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6B0C25Q6","canonicalUrl":"https://aoctrl.com/schneider/ATV6B0C25Q6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6B0C25Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600 ATV6B0C25Q6 modular drive, 250 kW normal duty / 200 kW heavy duty at 690 V, with integrated EMC filter and STO SIL3.","salesMarkdown":"The Schneider ATV6B0C25Q6 is a modular variable speed drive from the Altivar Process ATV600 range, rated for 250 kW normal duty at 690 V and 200 kW heavy duty, with a corresponding line current of 228 A normal / 183 A heavy. It carries an integrated EMC filter compliant with IEC 61800-3 category C3, covering up to 300 m of motor cable, and offers Safe Torque Off (STO) to SIL 3. The integrated EMC filter (category C3) is sized for industrial environments where the drive is installed in a cabinet with a protective earth. It suppresses both conducted and radiated emissions on the line and motor sides, which saves you an external filter in most second-environment applications. That means the drive can serve in safety-related control loops without a separate safety relay, as long as your control system handles the dual-channel request. Forced-convection cooling means fan noise is present — 73 dB per the EEC directive — so plan the cabinet ventilation accordingly if noise is a constraint in the machine cell. ## Fieldbus and I/O options Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, and CANopen (with three connector variants). Slot A/B also takes digital/analog I/O extensions or a relay output module. The drive ships with a Modbus serial port (2-wire RS-485, RTU, 4.8–38.4 kbit/s) and a Modbus TCP port (10/100 Mbit/s half/full duplex) as standard. This gives you a flexible fieldbus interface without opening the box for an optional card in many cases. Cabinet mount only (UL type 1 or 12 when integrated); pollution degree 2; operating altitude ≤2000 m with derating above 1000 m; shock 4 gn/11 ms; vibration 1.5 mm peak-peak at 2–13 Hz and 0.5 gn at 13–200 Hz. Forced convection requires clearance for airflow.","metaTitle":"Schneider ATV6B0C25Q6 Altivar Process Drive, 250 kW","metaDescription":"CE-marked modular drive for 250 kW (normal duty) at 690 V. Integrated EMC filter C3, STO SIL3, Modbus serial/Ethernet. Sourced to order. RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV6B0C25Q6","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"73 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"Variable speed drive, Altivar Process ATV600, APM, Low Harmonic 690 V, 250 kW","Line current":"228.0 A 690 V normal duty) 183.0 A 690 V heavy duty)","Maximum THDI":"<5 % full load IEEE 519","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"273 kVA at 690 V normal duty 219 kVA at 690 V heavy duty","Motor power kW":"250.0 kW at 690 V normal duty 200.0 kW at 690 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 2.0 power module 200 kW 1 front cover","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6B0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"< 2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 9440 W 2.5 kHz normal duty) Forced convection 7560 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Number Of Preset Speeds":"16 preset speeds","Network number of phases":"3 phases","Continuous output current":"275.0 A at 2.5 kHz normal duty 215.0 A at 2.5 kHz heavy duty","Maximum transient current":"302.5 A 60 s normal duty) 322.5 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"690 V - 10...10 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/th/en/product/download-pdf/ATV6B0C25Q6?filename=Schneider+Electric_Altivar-Process-ATV600_ATV6B0C25Q6.pdf', 'path_name': 'c0f8e3fc2c14e52ed3161d454fe1d21a.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/c0f8e3fc2c14e52ed3161d454fe1d21a.pdf', 'status': 1}","sourceUrl":"https://www.se.com/in/en/product/ATV6B0C25Q6/variable-speed-drive-altivar-process-atv600-apm-low-harmonic-690-v-250-kw/"},"ai":{"faq":[{"question":"Is the ATV6B0C25Q6 CE marked?","answer":"Yes, Marking CE is listed on the product."},{"question":"What motor types does this drive support?","answer":"It is designed for synchronous and asynchronous motors."},{"question":"What safety functions are integrated?","answer":"Safe Torque Off (STO) to SIL 3 per IEC 61508 and IEC 13849-1 is standard."},{"question":"Does it come with an integrated EMC filter?","answer":"Yes, an integrated EMC filter compliant with IEC 61800-3 category C3, rated for 300 m of motor cable."},{"question":"What communication ports are standard?","answer":"Standard ports include a 2-wire RS-485 Modbus serial (RTU, 4.8–38.4 kbit/s) and a Modbus TCP port (10/100 Mbit/s)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6B0C25Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6B0C25Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}