{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6B0C35T4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6B0C35T4","canonicalUrl":"https://aoctrl.com/schneider/ATV6B0C35T4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6B0C35T4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600 series, ATV6B0C35T4 modular AC drive, 480 V, 550 HP normal duty / 450 HP heavy duty, 443 kVA, cabinet mount, integrated EMC filter C3, STO SIL 3.","salesMarkdown":"## Motor sizing: the ND vs HD split decides your real load The ATV6B0C35T4 carries two distinct ratings: 550 HP at 480 V in normal duty and 450 HP at 480 V in heavy duty, with corresponding apparent power of 443 kVA ND and 362 kVA HD. Heavy duty typically applies to constant-torque loads like conveyors or extruders; normal duty suits variable-torque fans and pumps where the headroom isn't needed. Line current at 480 V is 533 A for normal duty and 436 A for heavy duty. The switching frequency is adjustable from 2 to 8 kHz, but above 2.5 kHz a derating factor applies — if you need quieter motor operation at higher carrier frequencies, the output current ceiling drops proportionally. Prospective line short-circuit current (SCCR) is 50 kA. That is high enough for most industrial mains, but the upstream breaker must be coordinated to keep the drive protected — check the selective coordination tables in the installation manual. ## Fieldbus and control: what ships on the base unit The drive includes a Modbus serial port (2-wire RS-485, RTU frame, 1-247 addresses) and a Modbus TCP/Ethernet port (10/100 Mbit/s, half/full duplex, auto-negotiation). Slot A accepts optional communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (daisy chain RJ45, SUB-D 9, or screw terminals). The data format on Modbus serial is 8 bits with configurable odd, even, or no parity. For Ethernet/IP, the transmission rate is 10/100 Mbit/s — no speed negotiation issues with modern switches. ## Safety and protection: STO SIL 3 and the protection map That means the drive can be used in safety circuits up to SIL 3 without external contactors for the torque removal function — the drive's own power stage is the isolating element. The protection suite covers both motor and drive sides: thermal protection, motor phase break, overcurrent between output phases and earth, short-circuit protection, overvoltage on the DC bus, line supply over/undervoltage, line phase loss, and overspeed. For the motor, it also includes thermal protection and phase break detection. ## Environmental limits and installation constraints Operating altitude is 1000 to 4800 m with current derating above 1000 m — at 2000 m expect roughly a 10% output current reduction. The drive is cabinet mount only (UL Type 1 or Type 12 per UL 61800-5-1 when integrated into an enclosure). Vibration resistance is 1.5 mm peak-to-peak from 2 to 13 Hz and 0.5 gn from 13 to 200 Hz per IEC 60068-2-6. Shock resistance is 4 gn for 11 ms per IEC 60068-2-27. Relative humidity range is 5 to 95% without condensation per IEC 60068-2-3. The integrated EMC filter covers 300 m of motor cable per IEC 61800-3 category C3 — that is the second environment (industrial mains). For first-environment (residential) installations, an external filter may be needed. ## Lifecycle and sourcing: active, modular, quoted to order The kit composition includes: 1 control unit, mechanical mounting kits, power connection set, set of fuses, 1 power module (160 kW), and 1 front cover. Marking is CE, confirming conformity with EU directives. Standards compliance includes IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonic limits), IEC 60721-3 (environmental conditions), IEC 61508 and IEC 13849-1 (functional safety).","metaTitle":"Schneider ATV6B0C35T4 AC Drive 480V, 550 HP ND, 450 HP HD","metaDescription":"Schneider Electric ATV6B0C35T4 Altivar Process ATV600 AC drive, 480V, 550 HP normal duty / 450 HP heavy duty, 443 kVA, integrated EMC filter C3, STO SIL 3.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"ATV6B0C35T4","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"75 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"variable speed drive APM, ATV600, Low Harmonic drive, 480 V, 550 hp","Line current":"533.0 A 480 V normal duty) 436.0 A 480 V heavy duty)","Maximum THDI":"<5 % full load IEEE 519","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"443 kVA at 480 V normal duty 362 kVA at 480 V heavy duty","Motor power hp":"550.0 hp at 480 V normal duty 450.0 hp at 480 V heavy duty","Motor power kW":"355.0 kW at 480 V normal duty 280.0 kW at 480 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 3.0 power module 160 kW 2.0 front cover","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6B0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"1000...4800 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2.5...8 kHz with derating factor 2...8 kHz adjustable","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 15780 W 2.5 kHz normal duty) Forced convection 12660 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Network number of phases":"3 phases","Continuous output current":"660.0 A at 2.5 kHz normal duty 520.0 A at 2.5 kHz heavy duty","Maximum transient current":"726 A 60 s normal duty) 780 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"480 V - 10...10 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/th/en/product/download-pdf/ATV6B0C35T4?filename=Schneider+Electric_Altivar-Process-ATV600_ATV6B0C35T4.pdf', 'path_name': '71b4d39f10f4c64d91dc62d9f8ddb5d4.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/71b4d39f10f4c64d91dc62d9f8ddb5d4.pdf', 'status': 1}","sourceUrl":"https://www.se.com/th/en/product/ATV6B0C35T4/variable-speed-drive-apm-atv600-low-harmonic-drive-480-v-550-hp/"},"ai":{"faq":[{"question":"What is the difference between normal duty and heavy duty ratings on ATV6B0C35T4?","answer":"Normal duty is 550 HP at 480 V with 533 A line current and 443 kVA apparent power; heavy duty is 450 HP at 480 V with 436 A line current and 362 kVA. Heavy duty applies to constant-torque loads where the drive must deliver full torque at low speed; normal duty suits variable-torque loads like pumps and fans."},{"question":"What fieldbus options are available for ATV6B0C35T4?","answer":"The base unit includes Modbus serial (RS-485, RTU) and Modbus TCP/Ethernet. Slot A accepts optional modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (three connector variants). Slots A and B also accept digital/analog I/O extension and output relay modules."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6B0C35T4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6B0C35T4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}