{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6B0C40Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6B0C40Q6","canonicalUrl":"https://aoctrl.com/schneider/ATV6B0C40Q6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6B0C40Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600 modular drive, ATV6B0C40Q6, 400 kW at 690 V normal duty, integrated C3 EMC filter, STO SIL3, Modbus/Profibus/Ethernet.","salesMarkdown":"The ATV6B0C40Q6: Motor power: 400 kW normal duty at 690 V, 315 kW heavy duty – the heavy-duty figure governs continuous high-torque loads like conveyors and crushers; the normal-duty number applies to centrifugal pumps and fans with quadratic torque. Line current at 690 V: 363 A normal duty, 287 A heavy duty – this is the current the drive draws from the supply, not the motor full-load current. Size upstream protection and cables accordingly. Integrated EMC filter meets IEC 61800-3 category C3, meaning it is suitable for second-environment (industrial) installations with cable lengths up to 300 m. No external filter needed for typical plant-floor runs. Safe Torque Off (STO) SIL 3 – a hardware safety function that removes torque without a separate safety contactor. If your machine safety requirement calls for SIL 3, this drive already has it. ## Communications and modularity Slot A on the ATV6B0C40Q6 accepts fieldbus option cards: Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (RJ45 or Sub-D or screw terminals). Slot A/B also accepts digital/analog I/O or relay extension modules. The base unit carries Modbus serial (RS-485, 2-wire, RTU) and Modbus TCP Ethernet (10/100 Mbit/s) as standard. Switching frequency adjustable 2–4.9 kHz; derate current for higher frequencies above 2 kHz. For motor-friendly operation at long cable runs, stay at 2 kHz. ## Mechanical and environmental Cabinet-mounted, forced-convection cooled. Pollution degree 2, vibration 1.5 mm peak-to-peak at 2–13 Hz (0.5 g at 13–200 Hz), shock 4 g for 11 ms. Relative humidity 5–95% non-condensing.","metaTitle":"Schneider ATV6B0C40Q6 ATV600 Drive, 400kW, 690V, C3 EMC","metaDescription":"Schneider Electric ATV6B0C40Q6 modular ATV600 drive, 400 kW normal duty at 690 V, integrated C3 EMC filter, STO SIL3, fieldbus options. Current production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV6B0C40Q6","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"73 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"Variable speed drive, Altivar Process ATV600, APM, Low Harmonic 690 V, 400 kW","Line current":"363.0 A 690 V normal duty) 287.0 A 690 V heavy duty)","Maximum THDI":"<5 % full load IEEE 519","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"434 kVA at 690 V normal duty 343 kVA at 690 V heavy duty","Motor power kW":"400.0 kW at 690 V normal duty 315.0 kW at 690 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 2.0 power module 200 kW 1 front cover","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6B0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"< 2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 14910 W 2.5 kHz normal duty) Forced convection 11760 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Number Of Preset Speeds":"16 preset speeds","Network number of phases":"3 phases","Continuous output current":"425.0 A at 2.5 kHz normal duty 340.0 A at 2.5 kHz heavy duty","Maximum transient current":"467.5 A 60 s normal duty) 510 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"690 V - 10...10 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/ATV6B0C40Q6/variable-speed-drive-altivar-process-atv600-apm-low-harmonic-690-v-400-kw/"},"ai":{"faq":[{"question":"What are the key motor power ratings of this drive?","answer":"The drive is rated 400 kW normal duty and 315 kW heavy duty at 690 V supply. Normal duty applies to variable-torque loads like pumps and fans; heavy duty for constant-torque loads like conveyors."},{"question":"What communication protocols does the ATV6B0C40Q6 support?","answer":"It includes built-in Modbus serial (RS-485, RTU) and Modbus TCP Ethernet. For Profibus, PROFINET, DeviceNet, CANopen, or EtherNet/IP, install an option card in Slot A."},{"question":"Does this drive have an internal EMC filter?","answer":"Yes, it has an integrated EMC filter compliant with IEC 61800-3 category C3, suitable for industrial environments with cable lengths up to 300 m."},{"question":"What safety functions does the ATV6B0C40Q6 include?","answer":"It includes Safe Torque Off (STO) certified SIL 3, which can replace a safety contactor in many machine safety architectures."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6B0C40Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6B0C40Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}