{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6B0C63T6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6B0C63T6","canonicalUrl":"https://aoctrl.com/schneider/ATV6B0C63T6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6B0C63T6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600 ATV6B0C63T6 AC Drive (VFD) 600V, 650 hp normal duty, 511 A line current, 531 kVA, cabinet mount, modular version.","salesMarkdown":"## 650 hp at 600 V — normal vs heavy duty The ATV6B0C63T6 is a 650 hp normal-duty drive at 600 V, delivering 511 A line current and 531 kVA apparent power. In heavy-duty service the numbers drop to 550 hp, 434 A, and 451 kVA — that's the margin for constant-torque loads like conveyors or extruders that need full torque at low speed. ## STO SIL 3 and the safety circuit Safe Torque Off rated SIL 3 per IEC 61508 means the drive removes motor torque without a main contactor — the safety function lives in the control board, not an external relay. For a commissioning engineer, that translates to fewer interposing safety relays in the panel and a faster certification walk-through on a machine guarding loop. ## EMC filter and cable length — 300 m Integrated EMC filter rated for 300 m of motor cable, Category C3 per IEC 61800-3. That covers most plant-floor runs without an external output choke — the filter handles conducted emissions up to the second environment (industrial). The 50 kA prospective short-circuit current rating at the line side means the drive coordinates with a 50 kA SCCR panel without an upstream current-limiting fuse. ## Fieldbus slot architecture Slot A accepts Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen — the same hardware carrier, different communication module. The drive also carries a native Modbus serial port (RS-485, 2-wire, 4.8 to 38.4 kbit/s) and a dual-port Ethernet/IP + Modbus TCP interface at 10/100 Mbit/s. For a controls integrator, the slot approach means the fieldbus decision can wait until the panel build phase, not the drive order date. ## Harmonics and THDI <5 % Total harmonic current distortion below 5 % at full load, meeting IEEE 519. That's the built-in active front-end or multi-pulse rectifier doing its work — no external line reactor or active filter needed for most utility compliance checks. At partial load the THDI stays low enough to avoid nuisance transformer heating in shared-bus installations. ## Cabinet mount and UL type 1/12 Cabinet-mount design with UL Type 1 (finger-safe) and Type 12 (dust-tight) ratings when integrated into an enclosure. The forced-convection cooling (2 to 4.9 kHz switching frequency, derated above 4 kHz) needs clearance above and below the heatsink — plan for 150 mm minimum free air path. The line-side screw terminals and M10 motor bus bars take up to 500 MCM cable. The ATV6B0C63T6 is a standard catalog part in the Altivar Process ATV600 family, so spares availability is stable for the foreseeable future. Quoted to order against your BOM; lead time and volume pricing confirmed at RFQ through authorized distribution.","metaTitle":"Schneider ATV6B0C63T6 Altivar Process 600 V VFD, 650 hp","metaDescription":"Schneider Electric ATV6B0C63T6 Altivar Process ATV600 AC drive, 650 hp normal duty at 600 V, 511 A line current, STO SIL 3, integrated EMC filter C3.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Current":"511.0 A 600 V normal duty) 434.0 A 600 V heavy duty)","Frequency":"50...60 Hz - 5...5 %","Horsepower":"650.0 hp at 600 V normal duty 550.0 hp at 600 V heavy duty","Data Format":"8 bits, configurable odd, even or no parity Modbus serial","Product Status":"Active","Pollution Degree":"Pollution degree 2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.1 °C","Temperature Storage":"-40...158 °F (-40...70 °C)","Main Product Or Component Type":"Variable speed drive","Ambient Air Temperature Operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV6B0C63T6/variable-speed-drive-altivar-process-atv600-apm-low-harmonic-600-v-650-hp/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV6B0C63T6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6B0C63T6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6B0C63T6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}