{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV6B0C80T4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV6B0C80T4","canonicalUrl":"https://aoctrl.com/schneider/ATV6B0C80T4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV6B0C80T4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV600 series, ATV6B0C80T4 modular AC drive, 800 kW / 1100 hp at 480 V normal duty, 630 kW / 900 hp heavy duty, IP00 cabinet mount, integrated EMC filter C3.","salesMarkdown":"## Dual-duty power rating and what it means for the load The ATV6B0C80T4 carries two distinct power ratings: 800 kW (1100 hp) at 480 V for normal-duty applications and 630 kW (900 hp) for heavy-duty cycles. Line current follows the same split: 1049 A at 480 V normal duty, 862 A at 480 V heavy duty. The heavy-duty current is the figure to size the input conductors and upstream protection for a constant-torque conveyor or extruder application. Apparent power is 872 kVA at 480 V normal duty and 717 kVA at 480 V heavy duty. That kVA number drives the transformer and generator sizing if the drive is fed from an isolated supply rather than a utility grid. ## Safety function and integrated EMC filter That means the drive's power stage can be disabled by a safety circuit without a separate contactor — the STO function removes the rotational energy from the motor shaft at the drive output, meeting the requirements for a Category 3 / PL e safety system. The safety CPU on the control board monitors the STO request independently of the main processor. The integrated EMC filter meets IEC 61800-3 category C3 with a cable length allowance of 300 m. Category C3 means the drive is intended for installation in an industrial environment where the mains supply is not shared with residential buildings. The 300 m cable run covers most motor cable distances in a plant without an external output reactor, though the switching frequency setting affects the actual reach. ## Communication slots and fieldbus options Slot A accepts plug-in communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (with RJ45, SUB-D 9, or screw terminal variants). The same slot also accepts digital/analog I/O extension and output relay extension modules. That means the drive can be ordered with the fieldbus interface already fitted, or the module can be swapped in the field without removing the drive from the cabinet. The base unit includes a 2-wire RS 485 Modbus serial port running RTU protocol at 4.8 to 38.4 kbit/s, plus a dual-port Ethernet IP/Modbus TCP interface at 10/100 Mbit/s with auto-negotiation. The Ethernet ports support daisy-chain topology, which saves a switch port in a multi-drive line. Total harmonic current distortion (THDI) is below 5% at full load per IEEE 519. That eliminates the need for a separate line reactor or active front end in most plant distribution systems where the utility requires THDI under 8% at the point of common coupling. ## Cabinet integration and environmental limits The drive is rated UL Type 1 and UL Type 12 when integrated into a cabinet per UL 61800-5-1. Type 12 means the enclosure protects against falling dirt and circulating dust — typical for a drive mounted inside a ventilated panel in a non-washdown area. The cabinet mount format means the power module and control unit are delivered as separate assemblies that bolt into the panel; the kit includes the mechanical mounting kit, power connection set, and fuse set. Operating altitude is 1000 m without derating; above that, current must be derated up to 4800 m. For a drive installed at 2000 m, the continuous output current drops by roughly 10% — factor that into the motor selection if the installation is at elevation. Switching frequency is adjustable from 2 to 8 kHz with a derating factor applied above 2.5 kHz. Running at 8 kHz quiets the motor whine but reduces the continuous output current by about 20% — the trade-off matters for an application where audible noise is a concern but the load is already near the drive's heavy-duty current limit.","metaTitle":"Schneider ATV6B0C80T4 AC Drive, 1100 HP Normal Duty, 480V","metaDescription":"Schneider Electric ATV6B0C80T4 Altivar Process ATV600 drive, 800 kW/1100 HP at 480V normal duty. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"ATV6B0C80T4","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"78 dB 86/188/EEC","Option card":"Slot A communication module, Profibus DP V1 Slot A communication module, PROFINET Slot A communication module, DeviceNet Slot A communication module, Modbus TCP/EtherNet/IP Slot A communication module, CANopen daisy chain RJ45 Slot A communication module, CANopen SUB-D 9 Slot A communication module, CANopen screw terminals Slot A/slot B digital and analog I/O extension module Slot A/slot B output relay extension module","description":"variable speed drive APM, ATV600, Low Harmonic drive, 480 V, 1100 hp","Line current":"1049.0 A 480 V normal duty) 862.0 A 480 V heavy duty)","Maximum THDI":"<5 % full load IEEE 519","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"872 kVA at 480 V normal duty 717 kVA at 480 V heavy duty","Motor power hp":"1100.0 hp at 480 V normal duty 900.0 hp at 480 V heavy duty","Motor power kW":"800.0 kW at 480 V normal duty 630.0 kW at 480 V heavy duty","Output voltage":"<= power supply voltage","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 5.0 power module 160 kW 4.0 front cover","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV600","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz - 5...5 %","Device short name":"ATV6B0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"1000...4800 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2.5...8 kHz with derating factor 2...8 kHz adjustable","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Braking to standstill":"By DC injection","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 33730 W 2.5 kHz normal duty) Forced convection 26540 W 2.5 kHz heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Can be suppressed Adjustable Automatic whatever the load Not available in permanent magnet motor law","Network number of phases":"3 phases","Continuous output current":"1420.0 A at 2.5 kHz normal duty 1140.0 A at 2.5 kHz heavy duty","Maximum transient current":"1562 A 60 s normal duty) 1710 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"480 V - 10...10 %","Communication port protocol":"Ethernet Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0...500 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Constant torque standard Variable torque standard Optimized torque mode","Acceleration and deceleration ramps":"S, U or customized Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.1 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/th/en/product/download-pdf/ATV6B0C80T4?filename=Schneider+Electric_Altivar-Process-ATV600_ATV6B0C80T4.pdf', 'path_name': 'bebe978bb4be8df7165737cb0619c5e0.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/bebe978bb4be8df7165737cb0619c5e0.pdf', 'status': 1}","sourceUrl":"https://www.se.com/th/en/product/ATV6B0C80T4/variable-speed-drive-apm-atv600-low-harmonic-drive-480-v-1100-hp/"},"ai":{"faq":[{"question":"What is the closest alternative to the ATV6B0C80T4 in the Altivar Process family?","answer":"The ATV6B0C80T4 is the modular cabinet-mount variant of the Altivar Process ATV600 series. The same power class is available in a wall-mount enclosure format (ATV680 series) for installations where a standalone IP54-rated drive is preferred over panel integration. The electrical ratings — 800 kW normal duty, 630 kW heavy duty at 480 V — are identical; the difference is the mounting format and the IP rating of the enclosure."},{"question":"What compliance documentation does Schneider Electric provide for the ATV6B0C80T4?","answer":"The drive carries CE marking and complies with IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonic limits), IEC 60721-3 (environmental), IEC 61508 and IEC 13849-1 (functional safety). UL listing is per UL 61800-5-1 for Type 1 and Type 12 cabinet integration. RoHS and REACH declarations are standard with the documentation package from Schneider."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV6B0C80T4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV6B0C80T4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}