{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV930D45N4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV930D45N4","canonicalUrl":"https://aoctrl.com/schneider/ATV930D45N4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV930D45N4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV930D45N4 variable speed drive, 45 kW normal duty / 37 kW heavy duty, 88 A continuous output, 380-480 V 3-phase, IP21, with integrated braking chopper and EMC filter.","salesMarkdown":"## Sizing the drive to the motor — normal vs heavy duty The ATV930D45N4 delivers 45 kW in normal duty and 37 kW in heavy duty at 380-480 V 3-phase input. Normal duty suits variable-torque loads like centrifugal pumps and fans where the drive rarely runs at full current continuously. Heavy duty applies to constant-torque loads — conveyors, extruders, positive-displacement pumps — where the drive must hold rated torque across the speed range without derating. Continuous output current is 88 A at 4 kHz switching frequency for normal duty, dropping to 74.5 A at 4 kHz for heavy duty. The switching frequency can be raised above 4 kHz to quiet motor whine, but each kHz increase above 4 kHz derates the continuous current — budget around 5-8% derate per extra kHz. The 88 A figure sets the minimum cable ampacity and upstream protection sizing. ## Built-in braking and harmonic performance This is the standard version with an integrated braking chopper — no external braking module needed for dynamic braking. The chopper activates when the DC bus voltage exceeds the threshold (typically 390 VDC on a 480 V supply), dumping regenerative energy into an external resistor. The resistor must be sized for the deceleration duty cycle, not just peak power. Total harmonic current distortion (THDI) is below 48% from 80-100% load per IEC 61000-3-12. This means the drive's input rectifier meets the harmonic emission limits for most industrial installations without an external line reactor or active filter — the integrated DC bus choke handles the bulk of the harmonic attenuation. For installations requiring THDI below 10%, an external line reactor or 12-pulse configuration is still needed. The drive ships with EtherNet/IP, Modbus serial, and Modbus TCP on board — three protocols without an option card. The Ethernet port supports half/full duplex and auto-negotiation at 10/100 Mbits. The serial port runs at 4.8 to 19200 bps with configurable parity. Addressing range is 1-247 on the serial bus. Slot A accepts plug-in communication modules for Profibus DP V1, PROFINET, DeviceNet, EtherCAT, CANopen (daisy-chain RJ45, SUB-D 9, or screw terminals), and Ethernet Powerlink. Slots A/B/C also accept digital/analog I/O extension modules and output relay extension modules. Slot B accepts encoder interface modules (5/12 V digital, analog, or resolver). The control terminals use screw clamps accepting 0.5-1.5 mm² (AWG 20-16). An adjustable PID regulator is built in — no external process controller needed for closed-loop pressure, flow, or level control. The regulator accepts feedback from the analog input or the optional encoder card. ## Environmental ratings and installation constraints It must be installed indoors in a clean, dry environment. Wall-mount only, vertical orientation within ±10 degrees. Ambient temperature range is not explicitly listed in the spec table, but the 63402.4 Gal/hr (240 m³/h) cooling air volume indicates forced-air cooling — ensure clearance around the heatsink per the installation manual. Pollution degree 2 (normally only non-conductive pollution) and overvoltage category III apply. Vibration resistance is 1.5 mm peak-to-peak at 2-13 Hz and 1 gn at 13-200 Hz per IEC 60068-2-6. Shock resistance is 15 gn for 11 ms per IEC 60068-2-27. These ratings cover normal industrial floor vibration — not suitable for direct mounting on a reciprocating compressor or press without vibration isolation. ## Compliance and documentation package The drive carries CE marking and complies with UL 508C (North American industrial control equipment), IEC 61800-3 (EMC for adjustable-speed drives), IEC 61800-5-1 (electrical safety), IEC 61000-3-12 (harmonic limits), IEC 60721-3 (environmental classification), IEC 61508 (functional safety), and IEC 13849-1 (safety-related parts of control systems). The integrated EMC filter meets conducted emission limits for most installations; an optional EMC plate is available for higher attenuation.","metaTitle":"Schneider Electric ATV930D45N4 Altivar Process Drive, 45 kW","metaDescription":"Schneider Electric ATV930D45N4 AC drive, 45 kW normal duty / 37 kW heavy duty, 88 A output at 380-480 V 3-phase. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Phases":"3-phase","IP Rating":"UL type 1","Application":"Industrial Application","Data Format":"8 bits, configurable odd, even or no parity","Product Status":"Active","Pollution Degree":"2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Operating Position":"Vertical +/- 10 degree","Temp Operating Max":"70 °C","Temp Operating Min":"-40 °C","Temperature Storage":"-40...158 °F (-40...70 °C)","Main Product Or Component Type":"Variable speed drive","Ambient Air Temperature Operation":"5...122 °F (-15...50 °C) (without derating) 122...140 °F (50...60 °C) (with derating factor)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$2,308.00","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ca/en/product/ATV930D45N4/variable-speed-drive-altivar-process-atv900-atv930-45kw-400-to-480v-with-braking-unit-ip21/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV930D45N4/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV930D45N4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV930D45N4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}