{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV930U55N4ZU","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV930U55N4ZU","canonicalUrl":"https://aoctrl.com/schneider/ATV930U55N4ZU","factsUrl":"https://aoctrl.com/api/mcp/products/ATV930U55N4ZU","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900 series, variable speed drive ATV930U55N4ZU, 380-480 V 3-phase, 5.5 kW normal duty / 4.0 kW heavy duty, 12.7 A, IP21, with braking chopper.","salesMarkdown":"## Supply rails and what they split The drive uses three separate supply domains: an external 24 V DC (19-30 V) for digital inputs, an internal 10.5 V DC for a reference potentiometer, and another internal 24 V DC (21-27 V) for the digital inputs and STO safety circuit. The STO rail is isolated from the control logic supply — that matters for SIL-rated installations where you want the safety loop independent of any control-side fault. Wire the external supply accordingly; the split keeps the nameplate clean. Control terminals are screw-type, 0.5 to 1.5 mm² (AWG 20 to 16). Line and motor terminals are screw, 2.5 to 6 mm² (AWG 14 to 10) for line side and 4 to 6 mm² (AWG 12 to 10) for motor. DC bus terminals also 2.5 to 6 mm² torque the same way. Keep the strip length standard and the torque driver set, and you won't fight terminations. ## Network integration: what's on board, what's in the slot EtherNet/IP and Modbus TCP on the integrated Ethernet port; Modbus serial configurable for 9600, 19200, or 4.8 kbps with odd/even/no parity, up to 247 addresses. Slot A accepts optional modules for Profibus, PROFINET, DeviceNet, EtherCAT, or CANopen. Compliance documentation covers UL 508C, IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. The CE marking is on the nameplate. For a quality doc control packet, the standards list is what you need to satisfy plant-level certification review. Cabinet mount only, vertical within ±10°, with the heat sink oriented for free airflow. The drive pulls 38 m³/h (10038.7 gal/hr) of cooling air — account for that in the enclosure ventilation design. IP21 and UL type 12 protection means it's spill-resistant but not a washdown device. Operating altitude derates 1% per 100 m above 1000 m; for installations above 4800 m, you're outside the rated range. Shock resistance is 15 gn for 11 ms (IEC 60068-2-27); vibration tolerance is 1.5 mm pk-pk from 2-13 Hz and 1 gn from 13-200 Hz (IEC 60068-2-6). That's enough for most machine-mounted applications unless you're on a punch press or a compressor skid — then consider isolating the enclosure.","metaTitle":"ATV930U55N4ZU Altivar Process ATV900, 5.5 kW Normal Duty","metaDescription":"ATV930U55N4ZU is a current-production Altivar Process ATV900 drive for 5.5 kW normal duty asynchronous motors, 380-480 V 3-phase, with integrated EMC filter and braking chopper.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Phase":"3 phase","Supply":"External supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm 500 V DC for 1 minute to earth","Marking":"CE","Variant":"Standard version With braking chopper","Category":"US1CP4E22276","Standards":"UL 508C IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated With EMC plate option","Data format":"8 bits, configurable odd, even or no parity","Noise level":"54.5 dB","Maximum THDI":"<48 % full load IEC 61000-3-12","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP","Mounting Mode":"Cabinet mount","Option Module":"Slot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module EtherCAT Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A/slot B/slot C digital and analog I/O extension module Slot A/slot B/slot C output relay extension module Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module communication module Ethernet Powerlink","Assembly style":"With heat sink","Motor power kW":"5.5 kW normal duty 4.0 kW heavy duty","Regulation loop":"Adjustable PID regulator","lifecycle_stage":"current","Pollution degree":"2","Range of Product":"Altivar Process ATV900","Shock resistance":"15 gn 11 ms IEC 60068-2-27","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission Rate":"10, 100 Mbits 4.8 kbps 9600 bit/s 19200 bit/s","Device Application":"Industrial Application","Operating altitude":"1000...4800 m with current derating 1 % per 100 m","Operating position":"Vertical +/- 10 degree","Number of addresses":"1...247","Product destination":"Asynchronous motors Synchronous motors","Degree of protection":"UL type 12","Overvoltage category":"III","Type of polarization":"No impedance","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Electrical connection":"Control screw terminal 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal 2.5...6 mm² AWG 14...AWG 10 DC bus screw terminal 2.5...6 mm² AWG 14...AWG 10 Motor screw terminal 4...6 mm² AWG 12...AWG 10","Nbr. of units in pkg.":"1","Volume of cooling air":"10038.7 Gal/hr(US) (38 m3/h)","Nominal Output Current":"12.7 A","IP degree of protection":"IP21","Continuous output current":"12.7 A 4 kHz normal duty 9.3 A 4 kHz heavy duty","Product or Component Type":"Variable speed drive","[Us] rated supply voltage":"380...480 V","Communication Port Protocol":"EtherNet/IP Modbus TCP Modbus serial","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3","Product Specific Application":"Process for industrial","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Ambient air transport temperature":"-40...158 °F (-40...70 °C)","Ambient Air Temperature for Storage":"-40...158 °F (-40...70 °C)","Ambient air temperature for operation":"5...122 °F (-15...50 °C) (without derating) 122...140 °F (50...60 °C) (with derating factor)","Environmental class (during operation)":"Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3","Relative symmetric mains voltage tolerance":"10 %","Permitted relative humidity (during operation)":"Class 3K5 according to EN 60721-3","Relative symmetric network frequency tolerance":"5 %","Maximum acceleration under shock impact (during operation)":"150 m/s² at 11 ms","Maximum deflection under vibratory load (during operation)":"1.5 mm at 2...13 Hz","Maximum acceleration under vibrational stress (during operation)":"10 m/s² at 13...200 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,715.00 – $2,219.24","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c48cf12f3c9521480f983584fe8cd32a.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV930U55N4ZU/alternatives.json"},"ai":{"faq":[{"question":"What communication protocols are available out of the box?","answer":"EtherNet/IP and Modbus TCP via the integrated Ethernet port, plus a Modbus serial link. For other networks (Profinet, DeviceNet, EtherCAT, CANopen, Profibus DP V1), slot A accepts an optional communication module."},{"question":"What compliance standards does the ATV930U55N4ZU meet?","answer":"It complies with UL 508C, IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonics), IEC 60721-3 (environmental), IEC 61508 and IEC 13849-1 (functional safety). CE marked."},{"question":"Does the drive include a braking chopper?","answer":"Yes, the standard variant includes an integrated braking chopper, so you can handle dynamic braking without an external module for most profiles."},{"question":"What is the motor power rating for normal vs heavy duty?","answer":"Normal duty is 5.5 kW (12.7 A continuous at 4 kHz) and heavy duty is 4.0 kW (9.3 A continuous at 4 kHz). Heavy duty provides more torque margin for constant-torque loads."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV930U55N4ZU","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV930U55N4ZU when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}