{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9A0C11Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9A0C11Q6","canonicalUrl":"https://aoctrl.com/schneider/ATV9A0C11Q6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9A0C11Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, ATV9A0C11Q6, modular variant, 110 kW at 690 V normal duty, integrated C3 EMC filter, STO SIL3.","salesMarkdown":"## Supply rails — three distinct feeds The ATV9A0C11Q6: Control power is split three ways: digital inputs need a 24 V DC external supply (19–30 V), the reference pot gets its own 10.5 V DC ±5 % from the drive, and the STO circuit runs on a separate 24 V DC rail (21–27 V). That means your panel layout needs three branches — don't daisy-chain the STO feed off the digital input supply. Insulation resistance is 1 MΩ at 500 V DC for 1 min; keep that in mind for megger testing after installation. Cabinet-mount only. Forced convection cooling. IP00 as shipped, but it's built for IP21 or IP54 cabinet integration. Vibration: 1.5 mm peak-to-peak at 2–13 Hz, 0.5 gn at 13–200 Hz. Shock 4 gn, 11 ms. Pollution degree 2 per IEC 61800-5-1. Operating altitude to 2000 m with derating above 1000 m. Relative humidity 5–95 % without condensation. Noise level 69 dB — plan ear protection if you're benching it open. ## Communication and options Three slot architecture for option cards: Slot A takes Profibus DP V1, PROFINET, DeviceNet, EtherCAT, or CANopen (RJ45, SUB-D 9, or screw). Slots A/B/C accept digital/analog I/O expansion or output relay extension. Slot B can also take a 5/12 V digital encoder interface, analog encoder interface, or resolver interface. Built-in Modbus serial (2-wire RS-485, RTU, 1–247 addresses) and Ethernet IP/Modbus TCP (10/100 Mbit/s, half/full duplex). Data format 8 bits, parity configurable.","metaTitle":"Schneider ATV9A0C11Q6 ATV900, 110 kW/690 V","metaDescription":"Modular ATV900 drive rated 110 kW at 690 V normal duty, integrated C3 EMC filter, STO SIL3, current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV9A0C11Q6","Supply":"External supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm at 500 V DC, 1 min","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"69 dB 86/188/EEC","Option card":"Slot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module EtherCAT Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A/slot B/slot C digital and analog I/O extension module Slot A/slot B/slot C output relay extension module Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module","description":"Variable speed drive, Altivar Process ATV900, APM, single 690 V, 110 kW","Line current":"118.0 A 690 V normal duty) 100.0 A 690 V heavy duty)","Maximum THDI":"<48 % from 80...100 % of load","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"141.0 kVA at 690 V normal duty 120.0 kVA at 690 V heavy duty","Motor power kW":"110.0 kW at 690 V normal duty 90.0 kW at 690 V heavy duty","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 1.0 power module 200 kW","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV900","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz +/- 5 %","Device short name":"ATV9A0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"0...2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Adjustable Automatic whatever the load Not available in permanent magnet motor law Can be suppressed","Network number of phases":"3 phases","Continuous output current":"125.0 A at 2.5 kHz normal duty 105.0 A at 2.5 kHz heavy duty","Maximum transient current":"150.0 A 60 s normal duty) 157.5 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"690 V - 10...15 %","Communication port protocol":"EtherNet/IP Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3","Speed drive output frequency":"0.1...599 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Optimized torque mode Variable torque standard Constant torque standard","Acceleration and deceleration ramps":"Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.2 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/za/en/product/ATV9A0C11Q6/variable-speed-drive-altivar-process-atv900-apm-single-690-v-110-kw/"},"ai":{"faq":[{"question":"What is the supply voltage configuration for this drive?","answer":"Digital inputs use a 24 V DC external supply (19–30 V). The reference potentiometer (1–10 kΩ) gets an internal 10.5 V DC ±5 % supply. The STO circuit requires a separate 24 V DC internal supply (21–27 V). Insulation resistance: 1 MΩ at 500 V DC for 1 minute."},{"question":"What compliance marking and standards does the ATV9A0C11Q6 carry?","answer":"CE marked. Standards met: IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonic limits), IEC 60721-3 (environmental), IEC 61508 and IEC 13849-1 (functional safety)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9A0C11Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9A0C11Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}