{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9A0C11T6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9A0C11T6","canonicalUrl":"https://aoctrl.com/schneider/ATV9A0C11T6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9A0C11T6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, ATV9A0C11T6, modular variable speed drive, 125 hp at 600 V normal duty, 100 hp heavy duty, integrated EMC filter IEC 61800-3 category C3, STO SIL3.","salesMarkdown":"## Drive fit at a glance The Schneider ATV9A0C11T6 is a current-production Altivar Process ATV900 drive in a modular cabinet-mount form. It's sized for 125 hp at 600 V normal duty or 100 hp under heavy duty, drawing 112 A or 92 A line current respectively. The integrated EMC filter meets IEC 61800-3 category C3 for 300 m motor cable, and the Safe Torque Off function is rated SIL 3, which covers most process safety loops without an external safety relay. Control power comes from multiple internal rails: 24 V DC (19-30 V) for digital inputs, a separate 21-27 V supply for digital inputs and STO, and a 10.5 V DC reference for a 1-10 kOhm potentiometer. The internal supply for STO means you don't need a dedicated 24 V safety bus — but watch the current budget if you're feeding many inputs externally. Built for asynchronous and synchronous motors, the drive supports Modbus serial (RS-485, RTU) and dual Ethernet ports (EtherNet/IP, Modbus TCP) at 10/100 Mbit. Slot A/ B/ C accept option cards for Profibus DP, PROFINET, DeviceNet, EtherCAT, CANopen, and analog/digital I/O extensions. Switching frequency is adjustable from 2 to 4.9 kHz with derating — useful for quieter motor operation but watch the thermal limit at higher frequencies. The drive includes comprehensive protection: motor thermal, phase loss, overvoltage, undervoltage, ground fault, and overspeed.","metaTitle":"Schneider ATV9A0C11T6 ATV900 Drive, 125HP","metaDescription":"Active production. 125HP at 600V normal duty (100HP heavy), STO SIL3, integrated EMC filter C3. Sourced to order from distributor stock.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV9A0C11T6","Supply":"External supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm at 500 V DC, 1 min","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"69 dB 86/188/EEC","Option card":"Slot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module EtherCAT Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A/slot B/slot C digital and analog I/O extension module Slot A/slot B/slot C output relay extension module Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module","description":"Variable speed drive, Altivar Process ATV900, APM, single 600 V, 125 hp","Line current":"112.0 A 600 V normal duty) 92.0 A 600 V heavy duty)","Maximum THDI":"<48 % from 80...100 % of load","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"116.0 kVA at 600 V normal duty 96.0 kVA at 600 V heavy duty","Motor power hp":"125.0 hp at 600 V normal duty 100.0 hp at 600 V heavy duty","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 1.0 power module 200 kW","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV900","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz +/- 5 %","Device short name":"ATV9A0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"0...2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Adjustable Automatic whatever the load Not available in permanent magnet motor law Can be suppressed","Network number of phases":"3 phases","Continuous output current":"125.0 A at 2.5 kHz normal duty 105.0 A at 2.5 kHz heavy duty","Maximum transient current":"150.0 A 60 s normal duty) 157.5 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"600 V - 10...15 %","Communication port protocol":"EtherNet/IP Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3","Speed drive output frequency":"0.1...599 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Optimized torque mode Variable torque standard Constant torque standard","Acceleration and deceleration ramps":"Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.2 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV9A0C11T6/variable-speed-drive-altivar-process-atv900-apm-single-600-v-125-hp/"},"ai":{"faq":[{"question":"What is the supply voltage for the control electronics?","answer":"Digital inputs need an external 24 V DC (19-30 V). There is a separate internal 24 V DC supply (21-27 V) for digital inputs and STO, plus a 10.5 V DC reference output for a 1-10 kOhm potentiometer."},{"question":"What compliance markings does it carry?","answer":"It is marked CE and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and UL 61800-5-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9A0C11T6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9A0C11T6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}