{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9A0C13Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9A0C13Q6","canonicalUrl":"https://aoctrl.com/schneider/ATV9A0C13Q6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9A0C13Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Altivar Process ATV900, ATV9A0C13Q6, modular drive, 132 kW (normal duty) / 110 kW (heavy duty) at 690 V, STO SIL 3, integrated C3 EMC filter.","salesMarkdown":"The ATV9A0C13Q6: Line current pulls 138 A under normal duty, 118 A under heavy duty at 690 V. Prospective line short-circuit rating is 50 kA — ensure upstream SCCR coordination. ## Safety & compliance fit The drive meets IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, and IEC 60721-3 — it carries CE marking. ## Network & I/O integration Slot A accepts fieldbus option cards for Profibus DP, PROFINET, DeviceNet, EtherCAT, CANopen (RJ45, SUB-D 9, screw terminals). Internal Ethernet port handles Modbus TCP at 10/100 Mbit/s with auto-negotiation. Modbus serial via 2-wire RS-485 runs RTU at 4.8–38.4 kbit/s, up to 247 addresses. Slots A, B, and C support digital/analog I/O extension modules and output relay extensions; slot B accommodates encoder (digital 5/12 V, analog, or resolver) interfaces. Control wiring uses removable screw terminals (0.5–1.5 mm²). ## Supply & environmental derating External 24 V DC supply for digital inputs (19…30 V); internal supplies provide 10.5 V DC for the reference potentiometer (1–10 kΩ) and 24 V DC for digital inputs and STO (21…27 V). Insulation resistance is 1 MΩ at 500 V DC. Integrated EMC filter meets IEC 61800-3 category C3 for 300 m cable runs. Switching frequency is adjustable 2–4.9 kHz with derating. Forced convection cooling; noise level 69 dB.","metaTitle":"Schneider ATV9A0C13Q6 Altivar Process ATV900, 132 kW","metaDescription":"Schneider ATV9A0C13Q6 Altivar Process ATV900 drive, 132 kW / 110 kW HD at 690 V, STO SIL 3, integrated C3 EMC filter, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV9A0C13Q6","Supply":"External supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm at 500 V DC, 1 min","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"69 dB 86/188/EEC","Option card":"Slot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module EtherCAT Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A/slot B/slot C digital and analog I/O extension module Slot A/slot B/slot C output relay extension module Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module","description":"Variable speed drive, Altivar Process ATV900, APM, single 690 V, 132 kW","Line current":"138.0 A 690 V normal duty) 118.0 A 690 V heavy duty)","Maximum THDI":"<48 % from 80...100 % of load","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"165.0 kVA at 690 V normal duty 141.0 kVA at 690 V heavy duty","Motor power kW":"132.0 kW at 690 V normal duty 110.0 kW at 690 V heavy duty","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 1.0 power module 200 kW","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV900","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz +/- 5 %","Device short name":"ATV9A0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"0...2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Adjustable Automatic whatever the load Not available in permanent magnet motor law Can be suppressed","Network number of phases":"3 phases","Continuous output current":"145.0 A at 2.5 kHz normal duty 125.0 A at 2.5 kHz heavy duty","Maximum transient current":"174.0 A 60 s normal duty) 187.5 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"690 V - 10...15 %","Communication port protocol":"EtherNet/IP Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3","Speed drive output frequency":"0.1...599 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Optimized torque mode Variable torque standard Constant torque standard","Acceleration and deceleration ramps":"Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.2 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/za/en/product/ATV9A0C13Q6/variable-speed-drive-altivar-process-atv900-apm-single-690-v-132-kw/"},"ai":{"faq":[{"question":"What are the key ratings for this drive?","answer":"It is rated 132 kW normal duty / 110 kW heavy duty at 690 V, with 165 kVA / 141 kVA apparent power. Line current is 138 A ND / 118 A HD at 690 V. Prospective short-circuit current is 50 kA."},{"question":"Which fieldbus options are available?","answer":"Slot A accepts Profibus DP, PROFINET, DeviceNet, EtherCAT, and CANopen modules. Built-in Ethernet supports Modbus TCP and the serial port runs Modbus RTU."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9A0C13Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9A0C13Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}