{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9A0C13S6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9A0C13S6","canonicalUrl":"https://aoctrl.com/schneider/ATV9A0C13S6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9A0C13S6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, modular VFD, ATV9A0C13S6, 150 hp at 600 V normal duty, 131 A line current.","salesMarkdown":"The Schneider Electric ATV9A0C13S6 is an Altivar Process ATV900 modular drive rated for 150 hp at 600 V normal duty and 125 hp at 600 V heavy duty, drawing 131 A and 112 A line current respectively. It handles both synchronous and asynchronous motors and includes an integrated EMC filter compliant with IEC 61800-3 category C3 for cable runs up to 300 m. Supply architecture is split: digital inputs and STO need a 24 V DC supply in the 21–27 V range, while the reference potentiometer gets its own 10.5 V DC ±5 % rail. That means you cannot share a single 24 V bus between the control logic and the pot wiper without a separate regulator — the 10.5 V rail is dedicated. ## Safety and connectivity STO (Safe Torque Off) is built in at SIL 3, so you can wire a safety relay or light curtain directly without an external safety contactor. The drive also monitors motor phase break, output phase-to-earth faults, DC bus overvoltage, and line supply phase loss — all listed in the protection set. Three option slots (A, B, C) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT, plus I/O and encoder interface modules. Slot A is the typical fieldbus slot; slots B and C handle encoder feedback or relay extensions. The base unit includes dual RJ45 Ethernet IP/Modbus TCP ports and one RJ45 Modbus serial port, so you can talk to the PLC and a local HMI without an extra card.","metaTitle":"Schneider ATV9A0C13S6 Altivar Process ATV900, 150 HP at 600","metaDescription":"Schneider Electric ATV9A0C13S6 Altivar Process ATV900 drive. 150 hp normal duty at 600 V, 131 A line current. Active production, sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV9A0C13S6","Supply":"External supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm at 500 V DC, 1 min","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"69 dB 86/188/EEC","Option card":"Slot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A communication module EtherCAT Slot A/slot B/slot C digital and analog I/O extension module Slot A/slot B/slot C output relay extension module Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module","description":"Variable speed drive, Altivar Process ATV900, APM, single 600 V, 150 hp","Line current":"131.0 A 600 V normal duty) 112.0 A 600 V heavy duty)","Maximum THDI":"<48 % from 80...100 % of load","Mounting mode":"Cabinet mount","Apparent power":"136.0 kVA at 600 V normal duty 116.0 kVA at 600 V heavy duty","Connector type":"2 RJ45 Ethernet IP/Modbus TCP on terminal 1 RJ45 Modbus serial on terminal","Motor power hp":"150.0 hp at 600 V normal duty 125.0 hp at 600 V heavy duty","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 1.0 power module 200 kW","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV900","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz +/- 5 %","Device short name":"ATV9A0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"0...2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Adjustable Automatic whatever the load Not available in permanent magnet motor law Can be suppressed","Network number of phases":"3 phases","Continuous output current":"145.0 A at 2.5 kHz normal duty 125.0 A at 2.5 kHz heavy duty","Maximum transient current":"174.0 A 60 s normal duty) 187.5 A 60 s heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"600 V - 10...15 %","Communication port protocol":"EtherNet/IP Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3","Speed drive output frequency":"0.1...599 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Optimized torque mode Variable torque standard Constant torque standard","Acceleration and deceleration ramps":"Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.2 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/ATV9A0C13S6/variable-speed-drive-altivar-process-atv900-apm-single-600-v-150-hp/"},"ai":{"faq":[{"question":"What are the key electrical ratings for the ATV9A0C13S6?","answer":"It is rated 150 hp at 600 V normal duty and 125 hp at 600 V heavy duty, with line currents of 131 A and 112 A respectively. Apparent power is 136 kVA at 600 V normal duty."},{"question":"What safety functions does this drive include?","answer":"It includes Safe Torque Off (STO) rated SIL 3, plus thermal protection, overcurrent, short-circuit, phase loss, and DC bus overvoltage monitoring on both motor and drive sides."},{"question":"What fieldbus options are available for the ATV9A0C13S6?","answer":"The base unit has dual Ethernet IP/Modbus TCP ports and one Modbus serial port. Option slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT modules. Slots B and C accept I/O extension, relay, or encoder interface modules."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9A0C13S6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9A0C13S6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}