{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9A0C16R4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9A0C16R4","canonicalUrl":"https://aoctrl.com/schneider/ATV9A0C16R4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9A0C16R4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, modular VFD, ATV9A0C16R4, 160 kW at 440 V normal duty, 255 A line current.","salesMarkdown":"The Schneider Electric ATV9A0C16R4 is a modular Altivar Process ATV900 drive rated for 160 kW at 440 V normal duty and 132 kW heavy duty, with corresponding line currents of 255 A and 214 A. It handles synchronous and asynchronous motors and includes an integrated EMC filter compliant with IEC 61800-3 category C3 for cable runs up to 300 m. ## Duty ratings and motor sizing Normal duty delivers 160 kW at 440 V with 255 A line current; heavy duty drops to 132 kW at 214 A. The apparent power at 440 V is 194 kVA normal duty and 163 kVA heavy duty. Switching frequency is adjustable from 2.5 to 8 kHz with derating above 2.5 kHz. ## Safety and compliance STO (Safe Torque Off) rated SIL 3 is built in. The drive meets IEC 61800-3, IEC 61800-5-1, IEC 61508, and IEC 13849-1. Pollution degree 2 per IEC 61800-5-1. CE marked. ## Communication and option slots Slave Modbus TCP via dual RJ45 on the control block, plus one RJ45 for Modbus serial. Three option slots (A, B, C) accept Profibus DP V1, PROFINET, DeviceNet, EtherCAT, CANopen, digital/analog I/O, relay, and encoder interface modules. Modbus serial runs RTU at 4.8 to 38.4 kbit/s on 2-wire RS-485. Cabinet mount, IP00 (requires IP21 or IP54 enclosure). Forced convection cooling. Operating altitude up to 4800 m with derating above 1000 m. Ambient humidity 5–95% non-condensing. Vibration resistance 1.5 mm pk-pk at 2–13 Hz, 0.5 gn at 13–200 Hz. Shock 7 gn for 11 ms.","metaTitle":"Schneider ATV9A0C16R4 Altivar Process 160 kW VFD, 255 A ND","metaDescription":"Schneider Electric ATV9A0C16R4 Altivar Process ATV900 drive, 160 kW at 440 V normal duty, 255 A line current. Active production, sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"ATV9A0C16R4","Supply":"External supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm at 440 V DC, 1 min, earth","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated with 300 m conforming to IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity for Modbus serial","Noise level":"69 dB conforming to 86/188/EEC","Option card":"Slot A: communication module for Profibus DP V1 Slot A: communication module for PROFINET Slot A: communication module for DeviceNet Slot A: communication module for EtherCAT Slot A: communication module for CANopen daisy chain RJ45 Slot A: communication module for CANopen SUB-D 9 Slot A: communication module for CANopen screw terminals Slot A/slot B/slot C: digital and analog I/O extension module Slot A/slot B/slot C: output relay extension module Slot B: 5/12 V digital encoder interface module Slot B: analog encoder interface module Slot B: resolver encoder interface module","description":"Variable speed drive, Altivar Process ATV900, APM, single 440 V, 160 kW","Line current":"255.0 A at 440 V (normal duty) 214.0 A at 440 V (heavy duty)","Maximum THDI":"<48 % from 80...100 % of load","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"194.0 kVA at 440 V normal duty 163.0 kVA at 440 V heavy duty","Connector type":"2 RJ45 for Ethernet IP/Modbus TCP on the control block 1 RJ45 for Modbus serial on the control block","Motor power kW":"160.0 kW at 440 V normal duty 132.0 kW at 440 V heavy duty","Kit composition":"1.0 power module 160 kW 1 control unit mechanical mounting kits power connection set of fuses","Protection type":"Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process ATV900","Shock resistance":"7 gn for 11 ms conforming to IEC 44068-2-27","Supply frequency":"50...60 Hz +/- 5 %","Device short name":"ATV9A0","Relative humidity":"5...95 % without condensation conforming to IEC 44068-2-3","Transmission rate":"10/100 Mbit/s for Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial","Operating altitude":"0...4800 m with current derating above 1000m","Physical interface":"2-wire RS 485 for Modbus serial","Transmission frame":"RTU for Modbus serial","Number of addresses":"1...247 for Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2.5...8 kHz with derating factor 2...8 kHz adjustable","Frequency resolution":"Display unit: 0.1 Hz Analog input: 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance for Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 44068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Electrical connection":"Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16 Line side: screw terminal Motor: M10 x 2 bars","IP degree of protection":"IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529","Motor slip compensation":"Adjustable Automatic whatever the load Not available in permanent magnet motor law Can be suppressed","Network number of phases":"3 phases","Continuous output current":"302.0 A at 2.5 kHz normal duty 250.0 A at 2.5 kHz heavy duty","Maximum transient current":"362.4 A during 60 s (normal duty) 375.0 A during 60 s (heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"440 V - 15...10 %","Communication port protocol":"EtherNet/IP Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3","Product specific application":"Process and utilities","Speed drive output frequency":"0.1...599 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Optimized torque mode Variable torque standard Constant torque standard","Acceleration and deceleration ramps":"Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...70 °C","Permissible temporary current boost":"1.2 x In during 60 s (normal duty) 1.5 x In during 60 s (heavy duty)","Ambient air temperature for operation":"-10...40 °C without derating 40...50 °C with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/th/en/product/download-pdf/ATV9A0C16R4?filename=Schneider+Electric_Altivar-Process-ATV900_ATV9A0C16R4.pdf', 'path_name': '3eb1e7cf964cc93f6c91f3cf4b93e516.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/3eb1e7cf964cc93f6c91f3cf4b93e516.pdf', 'status': 1}","sourceUrl":"https://www.se.com/in/en/product/ATV9A0C16R4/variable-speed-drive-altivar-process-atv900-apm-single-440-v-160-kw/"},"ai":{"faq":[{"question":"What is the motor power rating of the ATV9A0C16R4?","answer":"160 kW at 440 V normal duty, 132 kW at 440 V heavy duty."},{"question":"What safety functions does the ATV9A0C16R4 include?","answer":"STO (Safe Torque Off) rated SIL 3 is built in."},{"question":"What communication protocols does the ATV9A0C16R4 support?","answer":"Slave Modbus TCP via Ethernet, and Modbus serial RTU on RS-485. Option slots add Profibus DP V1, PROFINET, DeviceNet, EtherCAT, and CANopen."},{"question":"What standards does the ATV9A0C16R4 comply with?","answer":"IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. CE marked."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9A0C16R4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9A0C16R4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}