{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9A0C56R4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9A0C56R4","canonicalUrl":"https://aoctrl.com/schneider/ATV9A0C56R4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9A0C56R4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, modular drive, ATV9A0C56R4, 560 kW at 440 V normal duty, 450 kW heavy duty, IP00, forced convection cooling.","salesMarkdown":"## Control power and safety circuit The control section needs an external 24 V DC supply (19...30 V) for digital inputs, plus an internal 24 V DC (21...27 V) rail for digital inputs and the Safe Torque Off (STO) function, which is rated SIL 3. There is also a 10.5 V DC ±5 % reference supply for a 1 to 10 kΩ potentiometer. The STO circuit is separate from the main DC bus — if you are wiring a safety relay or PLC safety output, land it on the STO terminals, not the general-purpose digital inputs. ## EMC and compliance — what is built in An integrated EMC filter meets IEC 61800-3 category C3 for 300 m of motor cable — enough for most industrial installations without an external filter. The drive carries CE marking and complies with IEC 61800-5-1 (safety), IEC 61508 and IEC 13849-1 (functional safety), plus IEC 61000-3-12 (harmonic limits) and IEC 60721-3 (environmental). Pollution degree 2 applies, so it is suited for a clean, dry cabinet environment. The IP00 chassis requires enclosure integration to reach IP21 or IP54. ## Fieldbus and I/O expansion The control block has two RJ45 ports for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial (RS-485, 2-wire, RTU). Transmission rates are 10/100 Mbit/s on Ethernet and 4.8 to 38.4 kbit/s on serial. Slot A accepts communication option cards for Profibus DP V1, PROFINET, DeviceNet, EtherCAT, or CANopen (RJ45, SUB-D 9, or screw terminals). Slots A, B, and C also accept digital/analog I/O extension modules and encoder interfaces (digital 5/12 V, analog, resolver). If you need a second fieldbus or additional encoder feedback, plan the option card slot allocation before panel layout.","metaTitle":"Schneider ATV9A0C56R4 Altivar Process ATV900 Drive, 560 kW N","metaDescription":"Schneider ATV9A0C56R4 Altivar Process ATV900 drive, 560 kW at 440 V normal duty, 450 kW heavy duty. Active lifecycle, sourced to order. Integrated EMC filter C3, STO SIL 3. RFQ for","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Current":"865.0 A 440 V normal duty) 703.0 A 440 V heavy duty)","Frequency":"50...60 Hz +/- 5 %","Data Format":"8 bits, configurable odd, even or no parity Modbus serial","Connector Type":"2 RJ45 Ethernet IP/Modbus TCP on the control block 1 RJ45 Modbus serial on the control block","Product Status":"Active","Pollution Degree":"Pollution degree 2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.2 °C","Temperature Storage":"-40...158 °F (-40...70 °C)","Main Product Or Component Type":"Variable speed drive","Ambient Air Temperature Operation":"14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/sg/en/product/ATV9A0C56R4/variable-speed-drive-altivar-process-atv900-apm-single-440-v-560-kw/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV9A0C56R4/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9A0C56R4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9A0C56R4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}