{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9A0C71Q4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9A0C71Q4","canonicalUrl":"https://aoctrl.com/schneider/ATV9A0C71Q4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9A0C71Q4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, ATV9A0C71Q4, 710 kW at 400 V normal duty, 560 kW heavy duty, integrated EMC filter, STO SIL 3.","salesMarkdown":"The Schneider ATV9A0C71Q4 is an Altivar Process ATV900 modular drive rated for 710 kW at 400 V normal duty and 560 kW at 400 V heavy duty, with a corresponding line current of 1192 A normal duty and 951 A heavy duty. It drives both asynchronous and synchronous motors, with an integrated EMC filter rated for 300 m cable run per IEC 61800-3 Category C3. ## Control supply and fieldbus Control power comes from two separate 24 V DC rails: one for digital inputs (19...30 V) and one for digital inputs and STO (21...27 V). An internal 10.5 V DC supply powers a 1 to 10 kOhm reference potentiometer. The drive ships with dual RJ45 ports for Ethernet IP/Modbus TCP at 10/100 Mbit/s and one RJ45 for Modbus serial (RTU, 2-wire RS485, 4.8 to 38.4 kbit/s). Three option slots (A, B, C) accept fieldbus modules for Profibus DP V1, PROFINET, DeviceNet, EtherCAT, CANopen, plus digital/analog I/O or relay extensions. Cabinet-mount design, IP00 rated for integration into IP21 or IP54 enclosures. Forced convection cooling. Operating altitude up to 4800 m with current derating above 1000 m. Ambient humidity 5...95 % non-condensing. Switching frequency adjustable 2...8 kHz with derating factor. Prospective line Isc rated at 50 kA.","metaTitle":"Schneider ATV9A0C71Q4 Altivar Process ATV900, 710 kW","metaDescription":"Schneider ATV9A0C71Q4 Altivar Process ATV900 drive, 710 kW at 400 V normal duty, 560 kW heavy duty. Integrated EMC filter, STO SIL 3, Modbus TCP. Current lifecycle stage. Sourced t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"ATV9A0C71Q4","Supply":"External supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm at 500 V DC, 1 min, earth","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated with 300 m conforming to IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity for Modbus serial","Noise level":"74 dB conforming to 86/188/EEC","Option card":"Slot A: communication module for Profibus DP V1 Slot A: communication module for PROFINET Slot A: communication module for DeviceNet Slot A: communication module for EtherCAT Slot A: communication module for CANopen daisy chain RJ45 Slot A: communication module for CANopen SUB-D 9 Slot A: communication module for CANopen screw terminals Slot A/slot B/slot C: digital and analog I/O extension module Slot A/slot B/slot C: output relay extension module Slot B: 5/12 V digital encoder interface module Slot B: analog encoder interface module Slot B: resolver encoder interface module","description":"Variable speed drive, Altivar Process ATV900, APM, single 400 V, 710 kW","Line current":"1192.0 A at 400 V (normal duty) 951.0 A at 400 V (heavy duty)","Maximum THDI":"<48 % from 80...100 % of load","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"826.0 kVA at 400 V normal duty 659.0 kVA at 400 V heavy duty","Connector type":"2 RJ45 for Ethernet IP/Modbus TCP on the control block 1 RJ45 for Modbus serial on the control block","Motor power kW":"710.0 kW at 400 V normal duty 560.0 kW at 400 V heavy duty","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 5.0 power module 160 kW 4 front cover","Protection type":"Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process ATV900","Shock resistance":"7 gn for 11 ms conforming to IEC 60068-2-27","Supply frequency":"50...60 Hz +/- 5 %","Device short name":"ATV9A0","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Transmission rate":"10/100 Mbit/s for Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial","Operating altitude":"0...4800 m with current derating above 1000m","Physical interface":"2-wire RS 485 for Modbus serial","Transmission frame":"RTU for Modbus serial","Number of addresses":"1...247 for Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2.5...8 kHz with derating factor 2...8 kHz adjustable","Frequency resolution":"Display unit: 0.1 Hz Analog input: 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance for Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Electrical connection":"Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16 Line side: screw terminal Motor: M10 x 2 bars","IP degree of protection":"IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529","Motor slip compensation":"Adjustable Automatic whatever the load Not available in permanent magnet motor law Can be suppressed","Network number of phases":"3 phases","Continuous output current":"1260.0 A at 2.5 kHz normal duty 1020.0 A at 2.5 kHz heavy duty","Maximum transient current":"1512.0 A during 60 s (normal duty) 1530.0 A during 60 s (heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"400 V - 15...10 %","Communication port protocol":"EtherNet/IP Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3","Speed drive output frequency":"0.1...599 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Optimized torque mode Variable torque standard Constant torque standard","Acceleration and deceleration ramps":"Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...70 °C","Permissible temporary current boost":"1.2 x In during 60 s (normal duty) 1.5 x In during 60 s (heavy duty)","Ambient air temperature for operation":"-10...40 °C without derating 40...50 °C with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"{'url': 'https://www.se.com/th/en/product/download-pdf/ATV9A0C71Q4?filename=Schneider+Electric_Altivar-Process-ATV900_ATV9A0C71Q4.pdf', 'path_name': '3f8006668689c8b6873ac3a6ceb555b9.pdf', 'path_url': 'https://s3.lax.sharktech.net/viassion/datasheets/schneider_electric/3f8006668689c8b6873ac3a6ceb555b9.pdf', 'status': 1}","sourceUrl":"https://www.se.com/in/en/product/ATV9A0C71Q4/variable-speed-drive-altivar-process-atv900-apm-single-400-v-710-kw/"},"ai":{"faq":[{"question":"What are the key power ratings for the ATV9A0C71Q4?","answer":"Motor power is 710 kW at 400 V normal duty and 560 kW at 400 V heavy duty. Line current is 1192 A normal duty and 951 A heavy duty. Apparent power is 826 kVA normal duty and 659 kVA heavy duty."},{"question":"What fieldbus options are available for the ATV9A0C71Q4?","answer":"The drive has three option slots (A, B, C) supporting Profibus DP V1, PROFINET, DeviceNet, EtherCAT, CANopen (daisy chain RJ45, SUB-D 9, or screw terminals), plus digital/analog I/O and relay extension modules. Built-in ports include dual RJ45 for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial."},{"question":"What is the integrated EMC filter rating?","answer":"The integrated EMC filter is rated for 300 m cable run, conforming to IEC 61800-3 Category C3."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9A0C71Q4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9A0C71Q4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}