{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9A0M10T6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9A0M10T6","canonicalUrl":"https://aoctrl.com/schneider/ATV9A0M10T6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9A0M10T6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Altivar Process ATV900, modular drive, 1000 hp at 600 V normal duty, 800 hp heavy duty.","salesMarkdown":"The ATV9A0M10T6: Line current pulls 833 A in normal duty, 673 A in heavy duty at 600 V. That's the number your wire and bus bar sizing starts from, not the hp rating. ## What the duty ratings mean for fit The 833 A normal-duty figure also sets the SCCR — prospective line Isc is 50 kA. Verify your upstream breaker's interrupting rating coordinates, especially on a 600 V service where fault current runs high. ## Mounting and wiring notes for the panel builder Cabinet mount only. The box ships as a kit: one control unit, one power module (200 kW, forced-convection cooled), front cover, mechanical mounting kits, and a power connection set with fuses. Control wiring lands on removable screw terminals (0.5–1.5 mm² / AWG 20–16). Line and motor connections are M10 bars — plan for lugs that fit a 10 mm bolt. EMC filter is integrated and shields up to 300 m of cable under C3 environment; no external filter needed unless you're chasing stricter emissions limits. Switching frequency is adjustable between 2 and 4.9 kHz. Higher frequency quiets the motor but derates current — factor that into your thermal design if running near full load. IP00 rating inside the cabinet (IP21 or IP54 in an enclosure). Keep the enclosure's pollution degree ≤2 per IEC 61800-5-1.","metaTitle":"Schneider ATV9A0M10T6 Altivar 900 Drive, 1000 hp","metaDescription":"Active-production 1000 hp ATV900 drive. Modular cabinet mount, 833 A normal duty, integrated EMC filter C3, STO SIL 3. Source to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Current":"833.0 A 600 V normal duty) 673.0 A 600 V heavy duty)","Frequency":"50...60 Hz +/- 5 %","Horsepower":"1000.0 hp at 600 V normal duty 800.0 hp at 600 V heavy duty","Data Format":"8 bits, configurable odd, even or no parity Modbus serial","Product Status":"Active","Pollution Degree":"Pollution degree 2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.2 °C","Temperature Storage":"-40...158 °F (-40...70 °C)","Main Product Or Component Type":"Variable speed drive","Ambient Air Temperature Operation":"23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ca/en/product/ATV9A0M10T6/variable-speed-drive-altivar-process-atv900-apm-single-600-v-1000-hp/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV9A0M10T6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9A0M10T6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9A0M10T6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}