{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9B0C11R4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9B0C11R4","canonicalUrl":"https://aoctrl.com/schneider/ATV9B0C11R4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C11R4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, ATV9B0C11R4, modular AC drive, 110 kW normal duty / 90 kW heavy duty at 440 V, 480 V class, cabinet mount, IP00.","salesMarkdown":"## 110 kW normal duty, 90 kW heavy duty — the duty-cycle split The ATV9B0C11R4 is a modular Altivar Process ATV900 drive rated 110 kW at 440 V in normal duty and 90 kW at 440 V in heavy duty, with corresponding line currents of 159 A and 132 A at 440 V. The heavy-duty rating governs continuous overload capability for high-start-torque loads like conveyors or crushers; the normal-duty figure applies to variable-torque applications such as fans and pumps. Regenerative-mode ratings are also specified: 110 kW normal duty and 90 kW heavy duty at 440 V, with line currents of 131 A and 106 A respectively. This matters for applications that decelerate frequently — the drive can return energy to the line without an external braking resistor. ## Safety function and control supply The control supply includes a dedicated 24 V DC (21...27 V) rail for digital inputs and STO, plus a 10.5 V DC reference for an external potentiometer. The drive ships as a kit: control unit, mechanical mounting hardware, power connection set, fuses, a 160 kW power module, and a front cover. Cabinet-mount only — IP00 rating means the enclosure must provide the IP21 or IP54 protection. ## Fieldbus and option slots Three option slots (A, B, C) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT, or digital/analog I/O and relay extensions. Slot B also supports encoder interfaces (5/12 V digital, analog, resolver). Native Ethernet IP/Modbus TCP via dual RJ45 ports, plus a separate RJ45 for Modbus serial at 4.8–38.4 kbit/s. The integrated EMC filter meets IEC 61800-3 category C3 with 300 m of motor cable.","metaTitle":"Schneider Electric ATV9B0C11R4 AC Drive, 110 kW Normal Duty","metaDescription":"Schneider Electric ATV9B0C11R4 Altivar Process ATV900 drive, 110 kW at 440 V normal duty, 90 kW heavy duty. Active production, CE marked, STO SIL 3.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Current":"159.0 A at 440 V (normal duty) 132.0 A at 440 V (heavy duty) 131.0 A at 440 V regenerative mode (normal duty) 106.0 A at 440 V regenerative mode (heavy duty)","Frequency":"50...60 Hz +/- 5 %","Data Format":"8 bits, configurable odd, even or no parity for Modbus serial","Connector Type":"2 RJ45 for Ethernet IP/Modbus TCP on terminal 1 RJ45 for Modbus serial on terminal","Product Status":"Active","Pollution Degree":"2 conforming to IEC 61800-5-1","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.2 °C","Temperature Storage":"-40...70 °C","Main Product Or Component Type":"Variable speed drive"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/ATV9B0C11R4/variable-speed-drive-apm-atv900-low-harmonic-regen-drive-400-v-110-kw/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C11R4/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9B0C11R4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9B0C11R4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}