{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9B0C16Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9B0C16Q6","canonicalUrl":"https://aoctrl.com/schneider/ATV9B0C16Q6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C16Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, modular variable speed drive, ATV9B0C16Q6, 160 kW at 690 V normal duty, 132 kW heavy duty, STO SIL 3, integrated EMC filter C3.","salesMarkdown":"The Schneider ATV9B0C16Q6 is an Altivar Process ATV900 modular drive rated for 160 kW at 690 V normal duty and 132 kW at 690 V heavy duty, with a corresponding line current of 148 A normal and 122 A heavy. It includes Safe Torque Off (STO) rated SIL 3 and an integrated EMC filter compliant with IEC 61800-3 category C3. ## Control supply and fieldbus options The drive accepts an external 24 V DC supply for digital inputs (19...30 V) and provides an internal 10.5 V DC ±5 % supply for a reference potentiometer (1 to 10 kΩ). It also supplies 24 V DC (21...27 V) for digital inputs and STO. Communication options include slot A modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT, and dual RJ45 Ethernet IP/Modbus TCP ports plus one RJ45 Modbus serial port. Modbus serial runs at 4.8, 9.6, 19.2, 38.4 kbit/s; Ethernet ports at 10/100 Mbit/s. ## Protection and safety Protection functions cover thermal protection for motor and drive, motor phase break, overcurrent between output phases and earth, short-circuit, overvoltage/undervoltage on the DC bus and line supply, line phase loss, overspeed, and break on the control circuit.","metaTitle":"Schneider ATV9B0C16Q6 Altivar Process ATV900 Drive, 160 kW a","metaDescription":"Schneider Altivar Process ATV900 drive ATV9B0C16Q6, 160 kW at 690 V normal duty, STO SIL 3, integrated EMC filter C3. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV9B0C16Q6","Supply":"External supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm at 500 V DC, 1 min","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"70 dB 86/188/EEC","Option card":"Slot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A communication module EtherCAT Slot A/slot B/slot C digital and analog I/O extension module Slot A/slot B/slot C output relay extension module Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module","description":"Variable speed drive, Altivar Process ATV900, APM, Low Harmonic/Regen 690 V, 160 kW","Line current":"148.0 A 690 V normal duty) 122.0 A 690 V heavy duty) 121.0 A 690 V regenerative mode normal duty) 99.0 A 690 V regenerative mode heavy duty)","Maximum THDI":"<5 % full load IEEE 519","Mounting mode":"Cabinet mount","Apparent power":"177.0 kVA at 690 V normal duty 146.0 kVA at 690 V heavy duty 145.0 kVA at 690 V normal duty regenerative mode 119.0 kVA at 690 V heavy duty regenerative mode","Connector type":"2 RJ45 Ethernet IP/Modbus TCP on terminal 1 RJ45 Modbus serial on terminal","Motor power kW":"160.0 kW at 690 V normal duty 132.0 kW at 690 V heavy duty 160.0 kW at 690 V normal duty regenerative mode 132.0 kW at 690 V heavy duty regenerative mode","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 1.0 power module 200 kW","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV900","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz +/- 5 %","Device short name":"ATV9B0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"0...2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Adjustable Automatic whatever the load Not available in permanent magnet motor law Can be suppressed","Network number of phases":"3 phases","Continuous output current":"175.0 A at 2.5 kHz normal duty 145.0 A at 2.5 kHz heavy duty 175.0 A at 2.5 kHz normal duty regenerative mode 145.0 A at 2.5 kHz heavy duty regenerative mode","Maximum transient current":"210.0 A 60 s normal duty) 217.5 A 60 s heavy duty) 210.0 A 60 s regenerative mode normal duty) 217.5 A 60 s regenerative mode heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"690 V - 10...15 %","Communication port protocol":"EtherNet/IP Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3","Speed drive output frequency":"0.1...599 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Optimized torque mode Variable torque standard Constant torque standard","Acceleration and deceleration ramps":"Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.2 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV9B0C16Q6/variable-speed-drive-altivar-process-atv900-apm-low-harmonic-regen-690-v-160-kw/"},"ai":{"faq":[{"question":"What are the motor power ratings for this drive?","answer":"It is rated 160 kW at 690 V normal duty and 132 kW at 690 V heavy duty."},{"question":"What safety function does it support?","answer":"It includes Safe Torque Off (STO) rated SIL 3."},{"question":"What fieldbus options are available?","answer":"Slot A accepts modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, and EtherCAT. It also has dual Ethernet IP/Modbus TCP ports and one Modbus serial port."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9B0C16Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9B0C16Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}