{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9B0C25N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9B0C25N6","canonicalUrl":"https://aoctrl.com/schneider/ATV9B0C25N6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C25N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, ATV9B0C25N6, 160 kW at 500 V normal duty, 204 A line current, STO SIL 3, active production.","salesMarkdown":"The ATV9B0C25N6: Motor power: 160 kW at 500 V normal duty, 132 kW heavy duty. Line current at 500 V normal duty is 204 A, heavy duty 169 A — use the heavy-duty current for cable and fuse sizing if the load profile is continuous full torque. That means the drive can be used in safety-related applications up to SIL 3 without an external safety contactor — clean signal path for the safety CPU, just wire the STO inputs directly to the safety relay or PLC safety output. Integrated EMC filter meets IEC 61800-3 category C3 for 300 m cable runs. That covers most industrial installations without an external filter; if the line is longer or you need Category C2 for residential environments, plan for an add-on output filter. Switching frequency adjustable 2 to 4.9 kHz with derating. For a 160 kW motor, running at 2 kHz keeps thermal losses manageable; pushing to 4.9 kHz quiets the motor but derates output current — check the derating curve in the manual before committing the BOM line. ## Fieldbus and I/O options Comes with dual RJ45 Ethernet IP/Modbus TCP on terminal 1, plus a separate RJ45 for Modbus serial. Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45 or SUB-D 9 or screw terminals), or EtherCAT. Slots A, B, and C can take digital/analog I/O extension modules or output relay modules. Slot B also accepts encoder interfaces (5/12 V digital, analog, or resolver). That gives flexibility to match whatever fieldbus the controls integrator has already committed to — no need to respin the cabinet layout.","metaTitle":"Schneider Electric ATV9B0C25N6 Altivar Process ATV900, 160 k","metaDescription":"Schneider Electric ATV9B0C25N6 Altivar Process ATV900 drive, 160 kW at 500 V normal duty, 204 A line current, STO SIL 3, active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Frequency":"50...60 Hz +/- 5 %","Product Status":"Active","Pollution Degree":"Pollution degree 2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.2 °C","Temperature Storage":"-40...158 °F (-40...70 °C)","Main Product Or Component Type":"Variable speed drive"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV9B0C25N6/variable-speed-drive-altivar-process-atv900-apm-low-harmonic-regen-500-v-160-kw/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C25N6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9B0C25N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9B0C25N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}