{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9B0C25Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9B0C25Q6","canonicalUrl":"https://aoctrl.com/schneider/ATV9B0C25Q6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C25Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, ATV9B0C25Q6, 250 kW at 690 V normal duty, 228 A line current, modular cabinet-mount drive.","salesMarkdown":"## Drive selection memo for a 250 kW motor at 690 V The ATV9B0C25Q6 is a Schneider Altivar Process ATV900 drive sized for a 250 kW asynchronous or synchronous motor on a 690 V line, normal duty. Line current draws 228 A at 690 V normal duty; heavy duty knocks that to 200 kW and 183 A. Apparent power runs 273 kVA normal duty, 219 kVA heavy. The integrated EMC filter meets IEC 61800-3 category C3 for 300 m cable runs. Safe torque off (STO) is built in at SIL 3, so you can skip an external safety relay for the drive stop. ## Fieldbus and I/O expansion slots This modular drive ships with a control unit, power module, front cover, and mechanical mounting kit. Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT. Slots A, B, and C also accept digital/analog I/O extension or output relay modules. Slot B can take a 5/12 V digital encoder interface, analog encoder, or resolver interface. The control terminal uses removable screw terminals 0.5…1.5 mm².","metaTitle":"Schneider ATV9B0C25Q6 Altivar Process ATV900, 250 kW at 690","metaDescription":"ATV9B0C25Q6 is an active Altivar Process ATV900 drive rated 250 kW at 690 V normal duty, 228 A line current, with integrated EMC filter and STO SIL 3. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 600V"],"specifications":{"title":"ATV9B0C25Q6","Supply":"External supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm at 500 V DC, 1 min","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"73 dB 86/188/EEC","Option card":"Slot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A communication module EtherCAT Slot A/slot B/slot C digital and analog I/O extension module Slot A/slot B/slot C output relay extension module Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module","description":"Variable speed drive, Altivar Process ATV900, APM, Low Harmonic/Regen 690 V, 250 kW","Line current":"228.0 A 690 V normal duty) 183.0 A 690 V heavy duty) 191.0 A 690 V regenerative mode normal duty) 152.0 A 690 V regenerative mode heavy duty)","Maximum THDI":"<5 % full load IEEE 519","Mounting mode":"Cabinet mount","Apparent power":"273.0 kVA at 690 V normal duty 219.0 kVA at 690 V heavy duty 228.0 kVA at 690 V normal duty regenerative mode 182.0 kVA at 690 V heavy duty regenerative mode","Connector type":"2 RJ45 Ethernet IP/Modbus TCP on terminal 1 RJ45 Modbus serial on terminal","Motor power kW":"250.0 kW at 690 V normal duty 200.0 kW at 690 V heavy duty 250.0 kW at 690 V normal duty regenerative mode 200.0 kW at 690 V heavy duty regenerative mode","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 2.0 power module 200 kW 1 front cover","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV900","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz +/- 5 %","Device short name":"ATV9B0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"0...2000 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2...4.9 kHz adjustable with derating factor","Degree of protection":"UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Adjustable Automatic whatever the load Not available in permanent magnet motor law Can be suppressed","Network number of phases":"3 phases","Continuous output current":"275.0 A at 2.5 kHz normal duty 215.0 A at 2.5 kHz heavy duty 275.0 A at 2.5 kHz normal duty regenerative mode 215.0 A at 2.5 kHz heavy duty regenerative mode","Maximum transient current":"330.0 A 60 s normal duty) 322.5 A 60 s heavy duty) 330.0 A 60 s regenerative mode normal duty) 322.5 A 60 s regenerative mode heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"690 V - 10...15 %","Communication port protocol":"EtherNet/IP Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3","Speed drive output frequency":"0.1...599 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Optimized torque mode Variable torque standard Constant torque standard","Acceleration and deceleration ramps":"Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.2 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV9B0C25Q6/variable-speed-drive-altivar-process-atv900-apm-low-harmonic-regen-690-v-250-kw/"},"ai":{"faq":[{"question":"What are the key power ratings for the ATV9B0C25Q6?","answer":"Rated 250 kW at 690 V normal duty, 200 kW heavy duty. Line current 228 A normal duty, 183 A heavy duty. Apparent power 273 kVA normal duty, 219 kVA heavy duty."},{"question":"What safety functions does the ATV9B0C25Q6 include?","answer":"Built-in Safe Torque Off (STO) rated SIL 3."},{"question":"What fieldbus options are available for the ATV9B0C25Q6?","answer":"Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT communication modules."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9B0C25Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9B0C25Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}