{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9B0C31N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9B0C31N6","canonicalUrl":"https://aoctrl.com/schneider/ATV9B0C31N6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C31N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900 series, modular VFD, ATV9B0C31N6, 220 kW at 500 V normal duty, 160 kW heavy duty, IP00 for cabinet integration, CE marked.","salesMarkdown":"## Power stage and duty-cycle rating The ATV9B0C31N6: The line current at 500 V normal duty is 278 A; heavy duty drops to 204 A, and regenerative modes carry their own lower figures (231 A normal, 167 A heavy). Apparent power follows the same pattern: 241 kVA normal duty, 176 kVA heavy duty, with regenerative-mode ratings at 200 kVA and 145 kVA respectively. The 50 kA prospective line Isc rating means the input circuit must coordinate with upstream protection capable of interrupting that fault level. ## Safety, compliance, and fieldbus integration The integrated EMC filter handles 300 m cable runs at Category C3 per IEC 61800-3, which covers second-environment industrial installations. Three option-card slots (Slot A, B, C) accept fieldbus modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT, plus digital/analog I/O and output relay expansion. The native Modbus serial port (2-wire RS-485, RTU) and dual RJ45 Ethernet IP/Modbus TCP ports are on the terminal block — no extra card needed for basic Ethernet comms.","metaTitle":"Schneider ATV9B0C31N6 AC Drive, 220 kW at 500 V","metaDescription":"Schneider Electric ATV9B0C31N6 Altivar Process ATV900 VFD, 220 kW normal duty at 500 V. Active production, sourced to order against RFQ. CE marked, SIL 3 STO.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Current":"278.0 A 500 V normal duty) 204.0 A 500 V heavy duty) 231.0 A 500 V regenerative mode normal duty) 167.0 A 500 V regenerative mode heavy duty)","Frequency":"50...60 Hz +/- 5 %","Data Format":"8 bits, configurable odd, even or no parity Modbus serial","Connector Type":"2 RJ45 Ethernet IP/Modbus TCP on terminal 1 RJ45 Modbus serial on terminal","Product Status":"Active","Pollution Degree":"Pollution degree 2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.2 °C","Temperature Storage":"-40...158 °F (-40...70 °C)","Main Product Or Component Type":"Variable speed drive","Ambient Air Temperature Operation":"23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV9B0C31N6/variable-speed-drive-altivar-process-atv900-apm-low-harmonic-regen-500-v-220-kw/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C31N6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9B0C31N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9B0C31N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}