{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9B0C40N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9B0C40N6","canonicalUrl":"https://aoctrl.com/schneider/ATV9B0C40N6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C40N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900 series, ATV9B0C40N6 modular AC drive, 280 kW at 500 V normal duty, 352 A line current, cabinet mount, IP00 for enclosure integration.","salesMarkdown":"## Motor power and duty ratings that size the BOM The ATV9B0C40N6: Rated 280 kW at 500 V in normal duty, 220 kW in heavy duty — the heavy-duty figure governs continuous overload capability for conveyors, pumps, and compressors that cycle against a load. Line current at 500 V normal duty is 352 A, dropping to 278 A in heavy duty — this sets the cable cross-section and upstream protection sizing, not the motor nameplate alone. Apparent power of 305 kVA at 500 V normal duty confirms the transformer and switchgear headroom needed upstream. ## Safety integration and fieldbus slots Three option card slots (A, B, C) accept Profibus DP V1, PROFINET, EtherCAT, CANopen, DeviceNet, or digital/analog I/O extension modules — the fieldbus protocol is selected at ordering, not hardwired. Dual RJ45 Ethernet IP/Modbus TCP ports plus a separate RJ45 Modbus serial port allow the drive to sit on both the control network and a commissioning tool simultaneously. ## Cabinet integration and environmental limits Rated IP00 for integration into an IP21 or IP54 cabinet — the drive itself has no enclosure; the panel builder provides the environmental seal and cooling airflow. Integrated EMC filter meets IEC 61800-3 category C3 for 300 m motor cable — this covers most industrial installations without an external filter, though C3 limits conducted emissions to an industrial environment, not residential. Operating altitude limited to 2000 m with derating above 1000 m — a site at 1500 m needs the current derating factor applied before sizing the drive to the motor.","metaTitle":"Schneider Electric ATV9B0C40N6 Altivar Process ATV900","metaDescription":"Schneider Electric ATV9B0C40N6 AC drive, 280 kW at 500 V normal duty, 352 A line current, STO SIL 3, integrated EMC filter C3.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Frequency":"50...60 Hz +/- 5 %","Product Status":"Active","Pollution Degree":"Pollution degree 2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.2 °C","Temperature Storage":"-40...158 °F (-40...70 °C)","Main Product Or Component Type":"Variable speed drive"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ca/en/product/ATV9B0C40N6/variable-speed-drive-altivar-process-atv900-apm-low-harmonic-regen-500-v-280-kw/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C40N6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9B0C40N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9B0C40N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}