{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9B0C56R4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9B0C56R4","canonicalUrl":"https://aoctrl.com/schneider/ATV9B0C56R4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C56R4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, modular drive, ATV9B0C56R4, 560 kW at 440 V normal duty, 450 kW heavy duty, STO SIL 3, integrated EMC filter C3.","salesMarkdown":"The ATV9B0C56R4: The 560 kW normal duty figure is the headline — that is the motor power you can drive continuously on a standard pump or fan load. The 450 kW heavy duty rating covers constant-torque applications like conveyors or extruders where the drive must hold torque at low speed. Both are at 440 V three-phase; if your line voltage differs, the apparent power figures (601 kVA normal, 483 kVA heavy) give you the scaling factor. Switching frequency is adjustable from 2.5 to 8 kHz, with derating above the default. For a motor cable run under 300 m, the integrated EMC filter meets IEC 61800-3 category C3 — that covers most industrial environments without an external filter. ## Fieldbus and I/O options The drive ships with two RJ45 ports for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial (RS-485, 2-wire, RTU frame). Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT communication modules. Slots B and C handle digital/analog I/O expansion, relay outputs, and encoder interfaces (digital 5/12 V, analog, resolver). That means you can match the fieldbus to your existing control architecture without a protocol gateway.","metaTitle":"Schneider Electric ATV9B0C56R4 Altivar Process ATV900, 560 k","metaDescription":"Schneider Electric ATV9B0C56R4 Altivar Process ATV900 drive, 560 kW at 440 V normal duty, 450 kW heavy duty. STO SIL 3, integrated EMC filter C3, Modbus TCP. Current production. So","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Current":"789.0 A at 440 V (normal duty) 634.0 A at 440 V (heavy duty) 684.6 A at 440 V regenerative mode (normal duty) 550.1 A at 440 V regenerative mode (heavy duty)","Frequency":"50...60 Hz +/- 5 %","Data Format":"8 bits, configurable odd, even or no parity for Modbus serial","Connector Type":"2 RJ45 for Ethernet IP/Modbus TCP on terminal 1 RJ45 for Modbus serial on terminal","Product Status":"Active","Pollution Degree":"2 conforming to IEC 61800-5-1","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.2 °C","Temperature Storage":"-40...70 °C","Main Product Or Component Type":"Variable speed drive"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/ATV9B0C56R4/variable-speed-drive-apm-atv900-low-harmonic-regen-drive-440-v-560-kw/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C56R4/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9B0C56R4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9B0C56R4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}