{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9B0C71R4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9B0C71R4","canonicalUrl":"https://aoctrl.com/schneider/ATV9B0C71R4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C71R4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, modular cabinet drive, ATV9B0C71R4, 710 kW at 440 V normal duty, STO SIL 3, integrated EMC filter C3.","salesMarkdown":"The ATV9B0C71R4 is a modular cabinet-mount drive from the Altivar Process ATV900 family, rated for 710 kW at 440 V normal duty (560 kW heavy duty) with a corresponding line current of 995 A normal duty (789 A heavy duty). It supports both synchronous and asynchronous motors, and the switching frequency is adjustable from 2.5 to 8 kHz with derating. ## Control supply and safety Control wiring requires an external 24 V DC supply (19...30 V) for digital inputs, and an internal 24 V DC supply (21...27 V) powers the STO (safe torque off) circuit, which is certified to SIL 3. The drive also provides a 10.5 V DC ±5 % reference for a 1 to 10 kΩ potentiometer. Insulation resistance is 1 MΩ at 500 V DC for 1 minute to earth. ## Fieldbus and option slots Native communication includes dual RJ45 for Ethernet IP/Modbus TCP (10/100 Mbit/s) and one RJ45 for Modbus serial (4.8 to 38.4 kbit/s, RTU, 2-wire RS-485). Three option slots (A, B, C) accept fieldbus modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT, as well as digital/analog I/O or relay extension modules. Slot B also supports encoder or resolver interface modules. Cabinet mount, IP00 (requires IP21 or IP54 enclosure). Forced convection cooling. Operating altitude 0 to 4800 m with derating above 1000 m. Ambient humidity 5 to 95 % non-condensing. Shock resistance 4 gn for 11 ms; vibration resistance 1.5 mm peak-to-peak at 2-13 Hz and 0.5 gn at 13-200 Hz. Noise level 78 dB.","metaTitle":"Schneider ATV9B0C71R4 ATV900 Drive, 710 kW at 440 V, STO SIL","metaDescription":"ATV9B0C71R4 Altivar Process ATV900 drive. 710 kW normal duty at 440 V, 995 A line current. STO SIL 3, integrated EMC filter C3. Current production. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Current":"995.0 A at 440 V (normal duty) 789.0 A at 440 V (heavy duty) 872.5 A at 440 V regenerative mode (normal duty) 684.6 A at 440 V regenerative mode (heavy duty)","Frequency":"50...60 Hz +/- 5 %","Data Format":"8 bits, configurable odd, even or no parity for Modbus serial","Connector Type":"2 RJ45 for Ethernet IP/Modbus TCP on terminal 1 RJ45 for Modbus serial on terminal","Product Status":"Active","Pollution Degree":"2 conforming to IEC 61800-5-1","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.2 °C","Temperature Storage":"-40...70 °C","Main Product Or Component Type":"Variable speed drive"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV9B0C71R4/variable-speed-drive-apm-atv900-low-harmonic-regen-drive-440-v-710-kw/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV9B0C71R4/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9B0C71R4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9B0C71R4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}