{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9B0M10N6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9B0M10N6","canonicalUrl":"https://aoctrl.com/schneider/ATV9B0M10N6","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9B0M10N6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900 series, ATV9B0M10N6 modular AC drive, 710 kW at 500 V normal duty, 560 kW heavy duty, STO SIL 3, IP00 chassis, cabinet-mount.","salesMarkdown":"## Motor power and duty-cycle selection The ATV9B0M10N6 drives asynchronous and synchronous motors at 710 kW on 500 V supply under normal duty, or 560 kW under heavy duty — the heavy-duty figure governs continuous overload capability for constant-torque loads like conveyors and extruders. Line current at 500 V normal duty is 884 A; heavy duty draws 701 A. These values determine the upstream fuse and cable cross-section per IEC 61800-5-1. ## Safety integration and EMC compliance The integrated EMC filter meets IEC 61800-3 category C3 with 300 m motor cable — this is the industrial second-environment limit; installation in a residential first-environment requires an external filter. ## Fieldbus and I/O expansion Three option slots (A, B, C) accept communication modules for Profibus DP V1, PROFINET, EtherCAT, DeviceNet, or CANopen, plus digital/analog I/O and encoder interface cards — the drive ships without these fitted; order the module matching your network topology. Dual RJ45 ports serve EtherNet/IP and Modbus TCP at 10/100 Mbit/s; a separate RS-485 port runs Modbus serial at up to 38.4 kbit/s for legacy fieldbus integration. ## Cabinet integration and environmental limits The drive is IP00 chassis — it must be installed in a cabinet rated IP21 or IP54 per IEC 61800-5-1. Forced convection cooling requires clearance above and below the heatsink per the mounting instruction. Operating altitude is 0–2000 m with current derating above 1000 m; ambient relative humidity range is 5–95% non-condensing. Vibration resistance is 1.5 mm peak-to-peak at 2–13 Hz and 0.5 gn at 13–200 Hz per IEC 60068-2-6.","metaTitle":"Schneider ATV9B0M10N6 Altivar Process VFD, 710 kW, 500 V","metaDescription":"Schneider Electric ATV9B0M10N6 Altivar Process ATV900 AC drive, 710 kW at 500 V normal duty, STO SIL 3, integrated EMC filter C3.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Frequency":"50...60 Hz +/- 5 %","Product Status":"Active","Pollution Degree":"Pollution degree 2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"1.2 °C","Temperature Storage":"-40...158 °F (-40...70 °C)","Main Product Or Component Type":"Variable speed drive"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/th/en/product/ATV9B0M10N6/variable-speed-drive-altivar-process-atv900-apm-low-harmonic-regen-500-v-710-kw/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV9B0M10N6/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9B0M10N6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9B0M10N6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}