{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9B0M10Q4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9B0M10Q4","canonicalUrl":"https://aoctrl.com/schneider/ATV9B0M10Q4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9B0M10Q4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900, modular VFD, ATV9B0M10Q4, 1000 kW normal duty at 400 V, 1550 A line current, integrated EMC filter C3.","salesMarkdown":"The Schneider ATV9B0M10Q4 is a modular Altivar Process ATV900 drive rated for 1000 kW normal duty at 400 V, with a line current of 1550 A normal duty and 1240 A heavy duty. It handles synchronous and asynchronous motors, and includes an integrated EMC filter compliant with IEC 61800-3 category C3 for 300 m cable runs. The 1000 kW normal duty rating at 400 V sets the motor power it can drive continuously with typical industrial loads. Heavy duty at 800 kW gives headroom for constant-torque applications like conveyors or extruders. The line current figures — 1550 A normal duty, 1240 A heavy duty — are what you size the input wiring and upstream protection for, not the motor FLA alone. Switching frequency is adjustable from 2.5 to 8 kHz, with derating above 2.5 kHz. That matters when you're trying to quiet motor noise or reduce harmonics — but you lose output current capacity as you go up. The drive also carries a prospective line short-circuit current rating of 50 kA, so it can be installed on high-fault-capacity supplies without additional series reactors in many cases. Safe torque off (STO) is rated SIL 3 per IEC 61508, which covers the safety function for the motor and the drive itself. That simplifies integration into safety circuits — no external safety relay needed for the stop function if the drive handles it. Cabinet mount, forced convection cooling. The modular version ships as a kit: one control unit, mechanical mounting kits, power connection set, fuse set, six 160 kW power modules, and a front cover. That means you're not piecing together a drive from separate line items — it arrives as a single orderable assembly. Three option card slots (A, B, C) accept communication modules for Profibus DP, PROFINET, DeviceNet, CANopen, EtherCAT, plus digital/analog I/O and relay extension modules. Slot B also takes encoder interface modules (digital 5/12 V, analog, resolver). The drive ships with dual RJ45 for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial, so basic networking is ready out of the box.","metaTitle":"Schneider ATV9B0M10Q4 Altivar Process ATV900 Drive, 1000 kW","metaDescription":"Schneider ATV9B0M10Q4 Altivar Process ATV900 drive, 1000 kW normal duty at 400 V, 1550 A line current, STO SIL 3, integrated EMC filter C3, current production. Sourced to order aga","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"Supply":"External supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), 1 MOhm at 500 V DC, 1 min","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1","EMC filter":"Integrated with 300 m conforming to IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity for Modbus serial","Noise level":"79 dB conforming to 86/188/EEC","Option card":"Slot A: communication module for Profibus DP V1 Slot A: communication module for PROFINET Slot A: communication module for DeviceNet Slot A: communication module for CANopen daisy chain RJ45 Slot A: communication module for CANopen SUB-D 9 Slot A: communication module for CANopen screw terminals Slot A: communication module for EtherCAT Slot A/slot B/slot C: digital and analog I/O extension module Slot A/slot B/slot C: output relay extension module Slot B: 5/12 V digital encoder interface module Slot B: analog encoder interface module Slot B: resolver encoder interface module","Line current":"1550.0 A at 400 V (normal duty) 1240.0 A at 400 V (heavy duty) 1344.0 A at 400 V regenerative mode (normal duty) 1076.0 A at 400 V regenerative mode (heavy duty)","Maximum THDI":"<5 % full load conforming to IEEE 519","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"1074.0 kVA at 400 V normal duty 859.0 kVA at 400 V heavy duty 931.0 kVA at 400 V normal duty regenerative mode 745.0 kVA at 400 V heavy duty regenerative mode","Connector type":"2 RJ45 for Ethernet IP/Modbus TCP on terminal 1 RJ45 for Modbus serial on terminal","Motor power kW":"1000.0 kW at 400 V normal duty 800.0 kW at 400 V heavy duty 1000.0 kW at 400 V normal duty regenerative mode 800.0 kW at 400 V heavy duty regenerative mode","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 6 power module 160 kW 5 front cover","Protection type":"Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 conforming to IEC 61800-5-1","Range of product":"Altivar Process ATV900","Shock resistance":"4 gn for 11 ms conforming to IEC 60068-2-27","Supply frequency":"50...60 Hz +/- 5 %","Device short name":"ATV9B0","Relative humidity":"5...95 % without condensation conforming to IEC 60068-2-3","Transmission rate":"10/100 Mbit/s for Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial","Operating altitude":"0...4800 m with current derating above 1000m","Physical interface":"2-wire RS 485 for Modbus serial","Transmission frame":"RTU for Modbus serial","Number of addresses":"1...247 for Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2.5...8 kHz adjustable with derating factor 2...8 kHz","Frequency resolution":"Display unit: 0.1 Hz Analog input: 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance for Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Electrical connection":"Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16 Line side: screw terminal Motor: M10 x 2 bars","Power dissipation in W":"Forced convection: 44.5 W (normal duty) Forced convection: 34.4 W (heavy duty)","IP degree of protection":"IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529","Motor slip compensation":"Adjustable Automatic whatever the load Not available in permanent magnet motor law Can be suppressed","Network number of phases":"3 phases","Continuous output current":"1770.0 A at 2.5 kHz normal duty 1420.0 A at 2.5 kHz heavy duty 1770.0 A at 2.5 kHz normal duty regenerative mode 1420.0 A at 2.5 kHz heavy duty regenerative mode","Maximum transient current":"2124.0 A during 60 s (normal duty) 2130.0 A during 60 s (heavy duty) 2124.0 A during 60 s regenerative mode (normal duty) 2130.0 A during 60 s regenerative mode (heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"400 V - 15...10 %","Communication port protocol":"EtherNet/IP Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3 Humidity resistant class 3K3 conforming to IEC 60721-3-3","Speed drive output frequency":"0.1...599 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Optimized torque mode Variable torque standard Constant torque standard","Acceleration and deceleration ramps":"Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...70 °C","Permissible temporary current boost":"1.2 x In during 60 s (normal duty) 1.5 x In during 60 s (heavy duty)","Ambient air temperature for operation":"-5...40 °C without derating 40...50 °C with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/ATV9B0M10Q4/variable-speed-drive-altivar-process-atv900-apm-low-harmonic-regen-400v-1000kw/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ATV9B0M10Q4/alternatives.json"},"ai":{"faq":[{"question":"What are the key motor power and current ratings?","answer":"Normal duty: 1000 kW at 400 V with 1550 A line current. Heavy duty: 800 kW at 400 V with 1240 A line current. Regenerative mode ratings are also available at the same power levels with slightly lower line currents."},{"question":"What safety functions does the drive include?","answer":"Safe torque off (STO) rated SIL 3, plus thermal protection, overcurrent, short-circuit, overvoltage, undervoltage, phase loss, and overspeed protection for both the motor and the drive."},{"question":"What communication options are available?","answer":"The drive has dual RJ45 for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial as standard. Option card slot A accepts Profibus DP, PROFINET, DeviceNet, CANopen, or EtherCAT modules. Slots A, B, and C also accept I/O and relay extension modules."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9B0M10Q4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9B0M10Q4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}