{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ATV9B0M10T4","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ATV9B0M10T4","canonicalUrl":"https://aoctrl.com/schneider/ATV9B0M10T4","factsUrl":"https://aoctrl.com/api/mcp/products/ATV9B0M10T4","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Altivar Process ATV900 series, ATV9B0M10T4 AC Drive (VFD), 1000 HP at 480 V normal duty, 800 HP heavy duty, STO SIL 3, integrated EMC filter C3, cabinet mount.","salesMarkdown":"## 1000 HP at 480 V — normal and heavy duty ratings The ATV9B0M10T4 is a modular Altivar Process ATV900 drive rated 1000 HP at 480 V in normal duty and 800 HP at 480 V in heavy duty, per the specification. The corresponding apparent power is 815 kVA normal duty and 652 kVA heavy duty. Line current at 480 V is 1348 A normal duty and 1156 A heavy duty; for regenerative mode the figures are 1170 A normal duty and 1004 A heavy duty. ## Safety function and standards compliance The drive complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, and UL 61800-5-1. The integrated EMC filter covers 300 m cable runs to IEC 61800-3 category C3. ## Fieldbus and I/O expansion options Three option-card slots (A, B, C) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), EtherCAT, and Ethernet IP/Modbus TCP. Digital and analog I/O extension modules and encoder interface modules (digital 5/12 V, analog, resolver) are available for the same slots. Standard onboard communication includes two RJ45 Ethernet IP/Modbus TCP ports and one RJ45 Modbus serial port running RTU at 4.8 to 38.4 kbit/s.","metaTitle":"Schneider Electric ATV9B0M10T4 Altivar Process AC Drive","metaDescription":"Schneider Electric ATV9B0M10T4 Altivar Process ATV900 AC Drive, 1000 HP at 480 V normal duty, 800 HP heavy duty, STO SIL 3, integrated EMC filter C3, active","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["AC Drive (VFD) 480V"],"specifications":{"title":"ATV9B0M10T4","Supply":"External supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm at 500 V DC, 1 min","Marking":"CE","Variant":"Modular version","Standards":"IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1","EMC filter":"Integrated 984.3 ft (300 m) IEC 61800-3 category C3","Data format":"8 bits, configurable odd, even or no parity Modbus serial","Noise level":"79 dB 86/188/EEC","Option card":"Slot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A communication module EtherCAT Slot A/slot B/slot C digital and analog I/O extension module Slot A/slot B/slot C output relay extension module Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module","description":"variable speed drive, Altivar Process ATV900, APM, Low Harmonic/Regen 480V, 1400hp","Line current":"1348.0 A 480 V normal duty) 1156.0 A 480 V heavy duty) 1170.0 A 480 V regenerative mode normal duty) 1004.0 A 480 V regenerative mode heavy duty)","Maximum THDI":"<5 % full load IEEE 519","Exchange mode":"Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP","Mounting mode":"Cabinet mount","Apparent power":"815.0 kVA at 480 V normal duty 652.0 kVA at 480 V heavy duty 973.0 kVA at 480 V normal duty regenerative mode 835.0 kVA at 480 V heavy duty regenerative mode","Connector type":"2 RJ45 Ethernet IP/Modbus TCP on terminal 1 RJ45 Modbus serial on terminal","Motor power hp":"1000.0 hp at 480 V normal duty 800.0 hp at 480 V heavy duty 1000.0 hp at 480 V normal duty regenerative mode 800.0 hp at 480 V heavy duty regenerative mode","Motor power kW":"1000.0 kW at 480 V normal duty 800.0 kW at 480 V heavy duty 1000.0 kW at 480 V normal duty regenerative mode 800.0 kW at 480 V heavy duty regenerative mode","Kit composition":"1 control unit mechanical mounting kits power connection set of fuses 6 power module 160 kW 5 front cover","Protection type":"Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive","Safety function":"STO (safe torque off) SIL 3","Type of cooling":"Forced convection","lifecycle_stage":"current","Method of access":"Slave Modbus TCP","Pollution degree":"2 IEC 61800-5-1","Range of product":"Altivar Process ATV900","Shock resistance":"4 gn 11 ms IEC 60068-2-27","Supply frequency":"50...60 Hz +/- 5 %","Device short name":"ATV9B0","Relative humidity":"5...95 % without condensation IEC 60068-2-3","Transmission rate":"10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial","Operating altitude":"0...4800 m with current derating above 1000m","Physical interface":"2-wire RS 485 Modbus serial","Transmission frame":"RTU Modbus serial","Number of addresses":"1...247 Modbus serial","Product destination":"Synchronous motors Asynchronous motors","Switching frequency":"2.5...8 kHz adjustable with derating factor 2...8 kHz","Frequency resolution":"Display unit 0.1 Hz Analog input 0.012/50 Hz","Prospective line Isc":"50 kA","Type of polarization":"No impedance Modbus serial","Vibration resistance":"1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6","Electrical connection":"Control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars","Power dissipation in W":"Forced convection 45.4 W normal duty) Forced convection 36.9 W heavy duty)","IP degree of protection":"IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529","Motor slip compensation":"Adjustable Automatic whatever the load Not available in permanent magnet motor law Can be suppressed","Network number of phases":"3 phases","Continuous output current":"1770.0 A at 2.5 kHz normal duty 1420.0 A at 2.5 kHz heavy duty 1770.0 A at 2.5 kHz normal duty regenerative mode 1420.0 A at 2.5 kHz heavy duty regenerative mode","Maximum transient current":"2124.0 A 60 s normal duty) 2130.0 A 60 s heavy duty) 2124.0 A 60 s regenerative mode normal duty) 2130.0 A 60 s regenerative mode heavy duty)","Product or component type":"Variable speed drive","[Us] rated supply voltage":"480 V - 10...10 %","Communication port protocol":"EtherNet/IP Modbus serial Modbus TCP","Nominal switching frequency":"2.5 kHz","Environmental characteristic":"Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3","Speed drive output frequency":"0.1...599 Hz","Electromagnetic compatibility":"Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6","Synchronous motor control profile":"Permanent magnet motor Synchronous reluctance motor","Asynchronous motor control profile":"Optimized torque mode Variable torque standard Constant torque standard","Acceleration and deceleration ramps":"Linear adjustable separately from 0.01...9999 s","Ambient air temperature for storage":"-40...158 °F (-40...70 °C)","Permissible temporary current boost":"1.2 x In 60 s normal duty) 1.5 x In 60 s heavy duty)","Ambient air temperature for operation":"23...104 °F (-5...40 °C) without derating 104...122 °F (40...50 °C) with derating factor"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/ca/en/product/ATV9B0M10T4/variable-speed-drive-altivar-process-atv900-apm-low-harmonic-regen-480v-1400hp/"},"ai":{"faq":[{"question":"Where can I buy ATV9B0M10T4 and how do I get a price?","answer":"The ATV9B0M10T4 is available to order through independent distribution."},{"question":"What compliance documentation does Schneider Electric provide for ATV9B0M10T4?","answer":"The drive carries CE marking and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and UL 61800-5-1. RoHS and REACH declarations are standard with the documentation package."},{"question":"What is ATV9B0M10T4's listed supply for digital inputs and STO?","answer":"The external supply for digital inputs is 24 V DC (19...30 V). The internal supply for STO and digital inputs is 24 V DC (21...27 V). A separate 10.5 V DC ±5 % supply is provided for a reference potentiometer (1 to 10 kOhm)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ATV9B0M10T4","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ATV9B0M10T4 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}