{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"BMEAHO0412C","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"BMEAHO0412C","canonicalUrl":"https://aoctrl.com/schneider/BMEAHO0412C","factsUrl":"https://aoctrl.com/api/mcp/products/BMEAHO0412C","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Modicon X80 analog output module, 4 channels 4-20 mA with HART, 15-bit resolution, isolated channels, conformal coated.","salesMarkdown":"## Isolation and environment The BMEAHO0412C: Channels are isolated from each other at 1000 V DC and from ground and the bus at 1400 V DC — you can drive separate loops without common-mode headaches. The module carries conformal coating and is rated for gas (Gx, 3C4), dust (3S4), salt (level 2), and mold (3B2) resistance per ISA and IEC. It also holds Class I Division 2 hazardous location approval. The module includes broken wire detection and supports point-to-point topology. It complies with IEC 61131-2, UL 61010-2-201, CSA C22.2 No 61010-2-201, IACS, and IEC 61850-3 (location G). ATEX directive 2014/34/EU is covered. Termination is via a 20-way Telefast terminal block. Load impedance is 600 Ω for 0-20 mA range (570 Ω for 0-21 mA). Temperature drift is 45 ppm/°C.","metaTitle":"BMEAHO0412C Modicon X80 Analog Output, 4 Ch 4-20mA HART","metaDescription":"Active Modicon X80 analog output module: 4 channels 4-20mA with HART, 15-bit resolution, channel isolation 1000V DC, conformal coated, hazardous location rated. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Checks":"Broken wire detection","Topology":"Point-to-point","Standards":"IEC 61131-2 IEC 61010-2-201 UL 61010-2-201 CSA C22.2 No 61010-2-201 IACS E10 IEC 61000-6-5, interface type 1 and type 2 IEC 61850-3, location G IEC 60079-0","Directives":"2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive","lifecycle_stage":"current","Range of product":"Modicon X80","Isolation voltage":"1000 V DC for 60 s between channels 1400 V DC for 60 s between channels and ground 1400 V DC for 60 s between channels and bus","Measurement error":"0.1 % of full scale 25 °C 0.45 % of full scale - 25...60 °C","Temperature drift":"45 ppm/°C","Function available":"I/O mapping","Operating altitude":"0...2000 m 2000...5000 m with derating factor","Analogue output type":"Current: 4...20 mA","Load impedance ohmic":"600 Ohm 0...20 mA 570 Ohm 0...21 mA","Protective treatment":"Conformal coating","Electrical connection":"20 ways terminal block Telefast","Analogue output number":"4","Application specific I/O":"HART","Product or component type":"Analog output module","Analogue output resolution":"15 bits + sign","Isolation between channels":"Isolated","Environmental characteristic":"Gas resistant class Gx conforming to ISA S71.04 Gas resistant class 3C4 conforming to IEC 60721-3-3 Dust resistant class 3S4 conforming to IEC 60721-3-3 Sand resistant class 3S4 conforming to IEC 60721-3-3 Salt resistant level 2 conforming to IEC 68252 Mold growth resistant class 3B2 conforming to IEC 60721-3-3 Fungal spore resistant class 3B2 conforming to IEC 60721-3-3 Hazardous location class I division 2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1a035613f7c6b4a254ae54eb10747662.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/BMEAHO0412C/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation is available for this module?","answer":"The module carries IEC 61131-2, UL 61010-2-201, CSA C22.2 No 61010-2-201, IACS, and IEC 61850-3 (location G) standards. It also meets the ATEX directive 2014/34/EU for explosive atmospheres."},{"question":"What are the key ratings of the BMEAHO0412C?","answer":"4 channels of 4-20 mA output with HART, 15-bit resolution plus sign, channel isolation 1000 V DC, isolation to ground/bus 1400 V DC, accuracy 0.1% FS at 25 °C, operating temperature -25 to 60 °C."},{"question":"What environmental protections does this module have?","answer":"Conformal coating; gas resistance class Gx (ISA S71.04) and 3C4 (IEC 60721-3-3); dust and sand resistance 3S4; salt resistance level 2; mold and fungal spore resistance 3B2. Also rated for Class I Division 2 hazardous locations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/BMEAHO0412C","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/BMEAHO0412C when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}