{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"BMXAMI0410H","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"BMXAMI0410H","canonicalUrl":"https://aoctrl.com/schneider/BMXAMI0410H","factsUrl":"https://aoctrl.com/api/mcp/products/BMXAMI0410H","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Modicon X80 BMXAMI0410H Analog Input Module, 4 Inputs, 16-bit Resolution, Isolated Channels.","salesMarkdown":"The BMXAMI0410H is a 4-channel analog input module in the Modicon X80 family, configurable for voltage (±10 V, ±5 V, 0–10 V, 0–5 V, 1–5 V) or current (±20 mA, 0–20 mA, 4–20 mA) signals with 24-bit internal conversion and 16-bit resolution. Channel-to-channel isolation holds at 300 VDC, while channel-to-ground and channel-to-bus isolation both hit 1400 VDC — plenty of headroom for breaking ground loops on long sensor runs. The module draws 150 mA from the 3.3 V backplane and 45 mA from 24 V field supply, typical power consumption under 0.82 W at 24 V. That's light enough that you don't need to recalculate your rack budget when you swap it in. It's built for severe environments: conformal coating on the PCB, rated for gas class Gx and 3C4, dust 3S4, sand 3S4, salt level 2, and fungal spore resistance. Operating temperature spans -25 to 70 °C. ## 4-channel vs 8-channel — picking the right density The closest function sibling in the same X80 family is the BMXAMI0810, which carries 8 analog inputs instead of 4. Everything else — input ranges, resolution, isolation, environmental ratings — is the same. If your design calls for exactly 4 channels per module, the BMXAMI0410H saves you a slot and keeps the wiring tidy. If you anticipate scaling beyond 4, the BMXAMI0810 lets you keep the I/O count lower and occupy less rack space. Connection is via a single 20-way connector — one plug, one cable. The IP20 housing is rack-mounted in a Modicon X80 backplane. Status LEDs are on the front: one green RUN, one red ERR, one red I/O, and one green diagnostic LED per channel. That per-channel LED makes commissioning and fault finding straightforward — you can see which input is active or in alarm without a handheld. First-order digital filtering is built in, and recalibration is internal — no manual trim pots. Measurement accuracy at 25 °C runs 0.075 % of full scale on voltage ranges and 0.15 % on current ranges, with temperature drift of 15 ppm/°C (voltage) or 30 ppm/°C (current). If you're installing this in a panel that vibrates or sees shock, it's rated for 3 gn vibration and 30 gn shock — the conformal coating helps keep things intact. Derate above 2000 m altitude if you're in a high plant or mine site.","metaTitle":"Schneider BMXAMI0410H Modicon X80 Analog Input Module, 4-Ch","metaDescription":"Active production - BMXAMI0410H 4-channel analog input module for Modicon X80. Isolated channels (1400 VDC), conformal coated, severe environment rated. 16-bit resolution, 24-bit A","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Standards":"IEC 61010-2-201 IEC 61131-2 UL 61010-2-201 CSA C22.2 No 61010-2-201","Directives":"2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility","Status LED":"1 LED (green) RUN 1 LED per channel (green) channel diagnostic 1 LED (red) ERR 1 LED (red) I/O","Input level":"High level","Recalibration":"Internal","Type of filter":"First order digital filtering","Input impedance":"10 MOhm in voltage mode 250 Ohm + 3.6...50 Ohm internal protective resistor in current mode","lifecycle_stage":"current","MTBF reliability":"1200000 H","Range of product":"Modicon X80","Shock resistance":"30 gn","Isolation voltage":"300 V DC between channels 1400 V DC between channels and ground 1400 V DC between channels and bus","Measurement error":"0.075 % of full scale +/- 10 V 25 °C 0.075 % of full scale +/- 5 V 25 °C 0.075 % of full scale 0...10 V 25 °C 0.075 % of full scale 0...5 V 25 °C 0.075 % of full scale 1...5 V 25 °C 0.15 % of full scale +/- 20 mA 25 °C 0.15 % of full scale 0...20 mA 25 °C 0.15 % of full scale 4...20 mA 25 °C <= 0.55 % of full scale 4...20 mA - 25...70 °C","Relative humidity":"5...95 % at 55 °C without condensation","Temperature drift":"15 ppm/°C +/- 10 V 15 ppm/°C +/- 5 V 15 ppm/°C 0...10 V 15 ppm/°C 0...5 V 15 ppm/°C 1...5 V 30 ppm/°C +/- 20 mA 30 ppm/°C 0...20 mA 30 ppm/°C 4...20 mA","Operating altitude":"0...2000 m 2000...5000 m with derating factor","Analogue input type":"Current +/- 20 mA Current 0...20 mA Current 4...20 mA Voltage +/- 10 V Voltage +/- 5 V Voltage 0...10 V Voltage 0...5 V Voltage 1...5 V","Current consumption":"150 mA at 3.3 V DC 45 mA at 24 V DC","Digital value format":"- 32768 to + 32767 in maximum user scale +/- 10000 by default","Fast read cycle time":"1 ms + 1 ms x number of channels used","Protective treatment":"Conformal coating","Vibration resistance":"3 gn","Analogue input number":"4","Common mode rejection":"90 dB","Electrical connection":"20 ways 1 connector","Measurement resolution":"0.35 mV +/- 10 V 0.35 mV +/- 5 V 0.35 mV 0...10 V 0.35 mV 0...5 V 0.35 mV 1...5 V 0.92 µA +/- 20 mA 0.92 µA 0...20 mA 0.92 µA 4...20 mA","Power consumption in W":"0.82 W 24 V DC typical 1.30 W 24 V DC maximum 0.32 W 3.3 V DC typical 0.48 W 3.3 V DC maximum","IP degree of protection":"IP20","Nominal read cycle time":"5 ms for 4 channels","Maximum conversion value":"+/- 11.4 V +/- 10 V +/- 11.4 V +/- 5 V +/- 11.4 V 0...10 V +/- 11.4 V 0...5 V +/- 11.4 V 1...5 V 0...30 mA +/- 20 mA 0...30 mA 0...20 mA 0...30 mA 4...20 mA","Analog/digital conversion":"24 bits","Analogue input resolution":"16 bits","Product or component type":"Analog input module","Isolation between channels":"Isolated","Environmental characteristic":"Gas resistant class Gx Gas resistant class 3C4 Dust resistant class 3S4 Sand resistant class 3S4 Salt resistant level 2 Mold growth resistant class 3B2 Fungal spore resistant class 3B2 Hazardous location","Permitted overload on inputs":"+/- 30 V +/- 10 V +/- 30 V +/- 5 V +/- 30 V 0...10 V +/- 30 V 0...5 V +/- 30 V 1...5 V +/- 90 mA +/- 20 mA +/- 90 mA 0...20 mA +/- 90 mA 4...20 mA","Product specific application":"For severe environments","Minimum crosstalk attenuation":"80 dB","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","Precision of internal conversion resistor":"0.1 % - 15 ppm/°C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$289.56 – $662.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/70dce68ea42c2efd847264d6dd1659d7.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/BMXAMI0410H/alternatives.json"},"ai":{"faq":[{"question":"What are the key standards and directives for BMXAMI0410H?","answer":"It complies with IEC 61010-2-201, IEC 61131-2, UL 61010-2-201, and CSA C22.2 No 61010-2-201. It also meets the Low Voltage Directive (2014/35/EU) and EMC Directive (2014/30/EU)."},{"question":"How does BMXAMI0410H compare to the BMXAMI0810?","answer":"The main difference is channel count: BMXAMI0410H has 4 analog inputs, BMXAMI0810 has 8. Input ranges, isolation, resolution, environmental ratings, and form factor are the same. Choose based on how many signals you need per module."},{"question":"What isolation does the BMXAMI0410H provide?","answer":"Channel-to-channel isolation is 300 VDC, and channel-to-ground / channel-to-bus isolation is 1400 VDC each."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/BMXAMI0410H","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/BMXAMI0410H when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}