{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"BMXAMI0800","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"BMXAMI0800","canonicalUrl":"https://aoctrl.com/schneider/BMXAMI0800","factsUrl":"https://aoctrl.com/api/mcp/products/BMXAMI0800","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Modicon X80 BMXAMI0800 analog input module, 8 inputs, 16-bit conversion, fast read cycle time, current/voltage ranges, 1400 V DC isolation, active production.","salesMarkdown":"## Key ratings in context The BMXAMI0800: The module draws 150 mA at 3.3 V DC and 41 mA at 24 V DC, with a typical power consumption of 0.90 W at 24 V DC. First-order digital filtering is built in. Temperature drift is 30 ppm/°C on voltage ranges and 50 ppm/°C on current ranges. Common-mode rejection is 100 dB; minimum crosstalk attenuation is 80 dB. MTBF is 1,700,000 hours. The IP20-rated unit uses a single 28-way connector and fits directly into a Modicon X80 rack slot.","metaTitle":"BMXAMI0800 Modicon X80 Analog Input Module, 8 Ch, Fast","metaDescription":"Modicon X80 BMXAMI0800 8-channel analog input module, fast read cycle, ±0.15% accuracy, 16-bit, IEC/UL. Active production, sourced to order. RFQ for BOM pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Standards":"IEC 61010-2-201 IEC 61131-2 UL 61010-2-201 CSA C22.2 No 61010-2-201","Directives":"2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility","Status LED":"1 LED (green) RUN 1 LED per channel (green) channel diagnostic 1 LED (red) ERR 1 LED (red) I/O","Input level":"High level","Recalibration":"Factory calibrated","Type of filter":"First order digital filtering","Input impedance":"10 MOhm in voltage mode 250 Ohm in current mode","lifecycle_stage":"current","MTBF reliability":"1700000 H","Range of product":"Modicon X80","Shock resistance":"30 gn","Isolation voltage":"1400 V DC between channels and ground 1400 V DC between channels and bus","Measurement error":"0.15 % of full scale +/- 20 mA 25 °C 0.15 % of full scale 0...20 mA 25 °C 0.15 % of full scale 4...20 mA 25 °C 0.075 % of full scale +/- 10 V 25 °C 0.075 % of full scale 0...10 V 25 °C 0.075 % of full scale 0...5 V 25 °C 0.075 % of full scale 1...5 V 25 °C 0.075 % of full scale +/- 5 V 25 °C","Relative humidity":"5...95 % at 55 °C without condensation","Temperature drift":"30 ppm/°C +/- 10 V 30 ppm/°C +/- 5 V 30 ppm/°C 0...10 V 30 ppm/°C 0...5 V 30 ppm/°C 1...5 V 50 ppm/°C +/- 20 mA 50 ppm/°C 0...20 mA 50 ppm/°C 4...20 mA","Operating altitude":"0...2000 m 2000...5000 m with derating factor","Analogue input type":"Current +/- 20 mA Current 0...20 mA Current 4...20 mA Voltage +/- 10 V Voltage +/- 5 V Voltage 0...10 V Voltage 0...5 V Voltage 1...5 V","Current consumption":"150 mA at 3.3 V DC 41 mA at 24 V DC","Digital value format":"- 32768 to + 32767 in maximum user scale +/- 10000 by default","Fast read cycle time":"1 ms + 1 ms x number of channels used","Protective treatment":"Standard version","Vibration resistance":"3 gn","Analogue input number":"8","Common mode rejection":"100 dB","Electrical connection":"28 ways 1 connector","Measurement resolution":"0.36 mV +/- 10 V 0.36 mV 0...10 V 0.36 mV 0...5 V 0.36 mV 1...5 V 0.36 mV +/- 5 V 1.4 µA +/- 20 mA 1.4 µA 0...20 mA 1.4 µA 4...20 mA","Power consumption in W":"0.90 W 24 V DC typical 1.10 W 24 V DC maximum 0.32 W 3.3 V DC typical 0.48 W 3.3 V DC maximum","IP degree of protection":"IP20","Nominal read cycle time":"9 ms for 8 channels","Maximum conversion value":"+/- 11.4 V +/- 10 V +/- 11.4 V 0...10 V +/- 11.4 V 0...5 V +/- 11.4 V 1...5 V 0...30 mA +/- 20 mA 0...30 mA 0...20 mA 0...30 mA 4...20 mA 0...30 mA +/- 5 V","Analog/digital conversion":"16 bits","Analogue input resolution":"15 bits + sign","Product or component type":"Analog input module","Isolation between channels":"Non isolated","Permitted overload on inputs":"+/- 30 mA 0...20 mA +/- 30 mA 4...20 mA +/- 30 V +/- 10 V +/- 30 V +/- 5 V +/- 30 V 0...10 V +/- 30 V 0...5 V +/- 30 V 1...5 V +/- 30 mA +/- 20 mA","Minimum crosstalk attenuation":"80 dB","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"0...60 °C","Precision of internal conversion resistor":"0.1 % - 15 ppm/°C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$347.00 – $935.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/70dce68ea42c2efd847264d6dd1659d7.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/BMXAMI0800/alternatives.json"},"ai":{"faq":[{"question":"What standards and directives does it comply with?","answer":"It complies with IEC 61010-2-201, IEC 61131-2, UL 61010-2-201, CSA C22.2 No 61010-2-201, Low Voltage Directive 2014/35/EU, and EMC Directive 2014/30/EU."},{"question":"What are the key analog input ratings?","answer":"8 inputs configurable for ±20 mA, 0-20 mA, 4-20 mA, ±10 V, 0-10 V, 0-5 V, 1-5 V, ±5 V. Fast read cycle 1 ms + 1 ms per channel. 16-bit conversion (15 bits + sign). Measurement error 0.15% FS (current) or 0.075% FS (voltage) at 25 °C. Isolation 1400 V DC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/BMXAMI0800","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/BMXAMI0800 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}