{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"BMXART0414","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"BMXART0414","canonicalUrl":"https://aoctrl.com/schneider/BMXART0414","factsUrl":"https://aoctrl.com/api/mcp/products/BMXART0414","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Modicon X80 BMXART0414 analog input module, 4 isolated low-level channels for thermocouples and RTDs, 15-bit plus sign resolution, IEC 61131-2 / IEC 61000-6-4 / IEC 61000-6-2 / EN 61010-2-201 compliant.","salesMarkdown":"## What lands in the rack The BMXART0414: Each channel lands on a 40-way front connector and is galvanically isolated from the backplane at 1400 V DC and from adjacent channels and ground at 750 V DC, which lets one module span thermocouple zones that would otherwise demand a barrier — useful when mixing a grounded-junction probe with a floating one on the same rack. Conversion is a 16-bit sigma-delta ADC presented to the application as 15 bits + sign; nominal read cycle time is 400 ms with an RTD and 200 ms with a thermocouple, which is the figure to plan against for a control loop rather than the headline channel count. ## Where the numbers actually decide the fit Measurement error is the spec a thermocouple panel really gets judged on: at a 25 °C reference the module reads Ni 1000 to ±0.7 °C, Pt 100 / Pt 1000 / Ni 100 to ±2 °C, thermocouple R/S to ±3.2 °C, and thermocouple K/N/E/T to ±3.7 °C; widened to the 0…60 °C operating span those figures roughly double (e.g. Pt 100 / Pt 1000 ±2 °C → ±2 °C, but thermocouple B climbs from ±3.5 °C to ±5 °C). Cold-junction compensation is handled externally via a Pt100 probe. Temperature drift sits at 25 ppm/°C for the RTD ranges and most thermocouples, and 30 ppm/°C for the mV ranges and the higher-resistance Pt/Ni probes, so warm-cabinet derating is small but non-zero across long cable runs. Common-mode rejection is 120 dB at 50/60 Hz and differential-mode rejection 60 dB at the same frequencies, with permitted overload on every voltage input of ±7.5 V — the ruggedness margin an integrator wants when field wiring comes from a noisy plant. Maximum wiring resistance is 200 Ohm 2-wire / 3-wire for Ni 1000 and Pt 1000, 500 Ohm 4-wire for the same, and 20 Ohm / 50 Ohm for the lower-resistance probes — the limit that decides whether you can run a 4-wire Pt100 across a long conduit or have to step to the high-resistance Pt 1000. ## Backplane budget and panel placement The module draws 150 mA at 3.3 V DC and 40 mA at 24 V DC from the X80 rack, which is the figure to carry into a backplane power calculation when the rack already holds discrete I/O or fast analog outputs; the IP20 housing and 0…60 °C operating envelope match the rest of the Modicon X80 family, with shock 30 gn, vibration 3 gn, and 5…95 % RH non-condensing at 55 °C. Above 2000 m the module can still operate up to 5000 m with a derating factor applied per the Modicon X80 system manual, and storage tolerates −40…85 °C so handling and staging in a panel shop is unconstrained. Front-panel indicators are one green RUN LED, one green per-channel diagnostic LED, a red ERR LED, and a red I/O LED — enough granularity to fault-isolate a single open thermocouple from the rack without pulling the module. Resolution is 0.1 °C across every thermocouple and RTD type, and per-range on the voltage inputs (e.g. 40/2^14 mV on the ±40 mV range, 12.5 mΩ on the 400 Ohm range), with first-order digital filtering on the input stage. ## Compliance declaration The module is declared against IEC 61131-2, IEC 61000-6-4, and IEC 61000-6-2, and meets EN 61010-2-201, with the EU declarations covering 2014/35/EU (low voltage) and 2014/30/EU (electromagnetic compatibility) — the standard set a process skid or a panel destined for an EU line expects to see on the decl pack. MTBF is rated at 1,400,000 H, which for spares planning reads as a long-life component rather than a wear item.","metaTitle":"BMXART0414 Modicon X80 analog input, 4 ch, low-level","metaDescription":"BMXART0414 — current-production Modicon X80 analog input module, 4 isolated low-level inputs for thermocouples and RTDs, IEC 61131-2 compliant. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Standards":"IEC 61131-2 IEC 61000-6-4 IEC 61000-6-2 EN 61010-2-201","Directives":"2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility","Status LED":"1 LED (green) RUN 1 LED per channel (green) channel diagnostic 1 LED (red) ERR 1 LED (red) I/O","Input level":"Low level","Recalibration":"Internal","Detection type":"Open circuit Cu 10 Open circuit Ni 100 Open circuit Ni 1000 Open circuit Pt 100 Open circuit Pt 1000 Open circuit thermocouple B Open circuit thermocouple E Open circuit thermocouple J Open circuit thermocouple K Open circuit thermocouple L Open circuit thermocouple N Open circuit thermocouple R Open circuit thermocouple S Open circuit thermocouple T Open circuit thermocouple U","Product weight":"0.135 kg","Type of filter":"First order digital filtering","lifecycle_stage":"current","MTBF reliability":"1400000 H","Range of product":"Modicon X80","Shock resistance":"30 gn","Isolation voltage":"1400 V DC between channels and bus 750 V DC between channels 750 V DC between channels and ground","Measurement error":"+/- 0.7 °C Ni 1000 25 °C +/- 1.3 °C Ni 1000 0...60 °C +/- 2 °C Pt 100 0...60 °C +/- 2 °C Pt 1000 0...60 °C +/- 2.1 °C Ni 100 25 °C +/- 2.1 °C Pt 100 25 °C +/- 2.1 °C Pt 1000 25 °C +/- 2.7 °C thermocouple U 25 °C +/- 2.8 °C thermocouple J 25 °C +/- 3 °C Ni 100 0...60 °C +/- 3 °C thermocouple L 25 °C +/- 3.2 °C thermocouple R 25 °C +/- 3.2 °C thermocouple S 25 °C +/- 3.5 °C thermocouple B 25 °C +/- 3.7 °C thermocouple E 25 °C +/- 3.7 °C thermocouple K 25 °C +/- 3.7 °C thermocouple N 25 °C +/- 3.7 °C thermocouple T 25 °C +/- 4 °C Cu 10 0...60 °C +/- 4 °C Cu 10 25 °C +/- 4.5 °C thermocouple J 0...60 °C +/- 4.5 °C thermocouple L 0...60 °C +/- 4.5 °C thermocouple R 0...60 °C +/- 4.5 °C thermocouple S 0...60 °C +/- 4.5 °C thermocouple U 0...60 °C +/- 5 °C thermocouple B 0...60 °C +/- 5 °C thermocouple E 0...60 °C +/- 5 °C thermocouple K 0...60 °C +/- 5 °C thermocouple N 0...60 °C +/- 5 °C thermocouple T 0...60 °C 0.05 % of full scale +/- 1.28 V 25 °C 0.05 % of full scale +/- 160 mV 25 °C 0.05 % of full scale +/- 320 mV 25 °C 0.05 % of full scale +/- 40 mV 25 °C 0.05 % of full scale +/- 640 mV 25 °C 0.05 % of full scale +/- 80 mV 25 °C 0.12 % of full scale 400 Ohm 25 °C 0.12 % of full scale 4000 Ohm 25 °C","Relative humidity":"5...95 % at 55 °C without condensation","Temperature drift":"25 ppm/°C 400 Ohm 25 ppm/°C 4000 Ohm 25 ppm/°C Ni 1000 25 ppm/°C thermocouple B 25 ppm/°C thermocouple E 25 ppm/°C thermocouple J 25 ppm/°C thermocouple K 25 ppm/°C thermocouple L 25 ppm/°C thermocouple N 25 ppm/°C thermocouple R 25 ppm/°C thermocouple S 25 ppm/°C thermocouple T 25 ppm/°C thermocouple U 30 ppm/°C +/- 1.28 V 30 ppm/°C +/- 160 mV 30 ppm/°C +/- 320 mV 30 ppm/°C +/- 40 mV 30 ppm/°C +/- 640 mV 30 ppm/°C +/- 80 mV 30 ppm/°C Cu 10 30 ppm/°C Ni 100 30 ppm/°C Pt 100 30 ppm/°C Pt 1000","Operating altitude":"0...2000 m 2000...5000 m with derating factor","Analogue input type":"Voltage +/- 1.28 V Voltage +/- 160 mV Voltage +/- 320 mV Voltage +/- 40 mV Voltage +/- 640 mV Voltage +/- 80 mV Resistor 400 Ohm 2 wires Resistor 400 Ohm 3 wires Resistor 400 Ohm 4 wires Resistor 4000 Ohm 2 wires Resistor 4000 Ohm 3 wires Resistor 4000 Ohm 4 wires Temperature probe -100...+260 °C Cu 10 Temperature probe -100...+450 °C Pt 100 conforming to UL/JIS Temperature probe -100...+450 °C Pt 1000 conforming to UL/JIS Temperature probe -200...+850 °C Pt 100 conforming to IEC Temperature probe -200...+850 °C Pt 1000 conforming to IEC Temperature probe -60...+180 °C Ni 100 Temperature probe -60...+180 °C Ni 1000 Thermocouple +130...+1820 °C thermocouple B Thermocouple +270...+1300 °C thermocouple N Thermocouple -200...+600 °C thermocouple U Thermocouple -200...+760 °C thermocouple J Thermocouple -200...+900 °C thermocouple L Thermocouple -270...+1000 °C thermocouple E Thermocouple -270...+1370 °C thermocouple K Thermocouple -270...+400 °C thermocouple T Thermocouple -50...+1769 °C thermocouple R Thermocouple -50...+1769 °C thermocouple S","Current consumption":"150 mA at 3.3 V DC 40 mA at 24 V DC","Protective treatment":"Standard version","Vibration resistance":"3 gn","Analogue input number":"4","Common mode rejection":"120 dB 50/60 Hz","Electrical connection":"40 ways 1 connector","Measurement resolution":"0.1 °C Cu 10 0.1 °C Ni 100 0.1 °C Ni 1000 0.1 °C Pt 100 0.1 °C Pt 1000 0.1 °C thermocouple B 0.1 °C thermocouple E 0.1 °C thermocouple J 0.1 °C thermocouple K 0.1 °C thermocouple L 0.1 °C thermocouple N 0.1 °C thermocouple R 0.1 °C thermocouple S 0.1 °C thermocouple T 0.1 °C thermocouple U 1280/2exp14 mV +/- 1.28 V 160/2exp14 mV +/- 160 mV 320/2exp14 mV +/- 320 mV 40/2exp14 mV +/- 40 mV 12.5 mOhm 400 Ohm 125 mOhm 4000 Ohm 640/2exp14 mV +/- 640 mV 80/2exp14 mV +/- 80 mV","IP degree of protection":"IP20","Nominal read cycle time":"400 ms with temperature probe 200 ms with thermocouple","Maximum conversion value":"+/- 100 % 400 Ohm +/- 100 % 4000 Ohm +/- 102.5 % +/- 1.28 V +/- 102.5 % +/- 160 mV +/- 102.5 % +/- 320 mV +/- 102.5 % +/- 40 mV +/- 102.5 % +/- 640 mV +/- 102.5 % +/- 80 mV","Analog/digital conversion":"Sigma delta 16 bits","Analogue input resolution":"15 bits + sign","Maximum wiring resistance":"20 Ohm 2 wires Cu 10 20 Ohm 2 wires Ni 100 20 Ohm 2 wires Pt 100 20 Ohm 3 wires Cu 10 20 Ohm 3 wires Ni 100 20 Ohm 3 wires Pt 100 200 Ohm 2 wires Ni 1000 200 Ohm 2 wires Pt 1000 200 Ohm 3 wires Ni 1000 200 Ohm 3 wires Pt 1000 50 Ohm 4 wires Cu 10 50 Ohm 4 wires Ni 100 50 Ohm 4 wires Pt 100 500 Ohm 4 wires Ni 1000 500 Ohm 4 wires Pt 1000","Product or component type":"Analog input module","Cold junction compensation":"External by Pt100 probe","Isolation between channels":"Isolated","Differential mode rejection":"60 dB 50/60 Hz","Permitted overload on inputs":"+/- 7.5 V +/- 1.28 V +/- 7.5 V +/- 160 mV +/- 7.5 V +/- 320 mV +/- 7.5 V +/- 40 mV +/- 7.5 V +/- 640 mV +/- 7.5 V +/- 80 mV","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"0...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$290.72 – $719.88","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c03f76f097f0308b65dff5da1a7b22af.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/BMXART0414/alternatives.json"},"ai":{"faq":[{"question":"What standards does BMXART0414 carry?","answer":"IEC 61131-2, IEC 61000-6-4, IEC 61000-6-2, and EN 61010-2-201."},{"question":"What EU directives does BMXART0414 comply with?","answer":"2014/35/EU (low voltage) and 2014/30/EU (electromagnetic compatibility)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/BMXART0414","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/BMXART0414 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}