{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"BMXART0414H","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"BMXART0414H","canonicalUrl":"https://aoctrl.com/schneider/BMXART0414H","factsUrl":"https://aoctrl.com/api/mcp/products/BMXART0414H","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Modicon X80 BMXART0414H analog input module, 4 channels isolated, accepts TC/RTD/voltage/resistance, sigma-delta 16-bit, IEC 61131-2.","salesMarkdown":"## Integrator note — channel lineup and grounding The BMXART0414H: Four isolated analog inputs, each configurable for thermocouple (B, E, J, K, L, N, R, S, T, U), RTD (Pt100, Pt1000, Ni100, Ni1000, Cu10), voltage (±40 mV to ±1.28 V), or 2/3/4-wire resistance (400 Ω or 4000 Ω). Cold-junction compensation uses an external Pt100 probe. Sigma-delta conversion at 16 bits, resolution 15 bits + sign. Channel isolation keeps ground loops off the backplane; use shielded twisted-pair for thermocouple runs and connect the shield at the module end only. Power draw: 150 mA at 3.3 V DC and 40 mA at 24 V DC from the rack. The 40‑way connector is keyed; verify the mating cable part number matches the X80 backplane pinout before termination. ## Compliance and environmental rating Designed to IEC 61131-2 (PLC hardware), IEC 61000-6-4 (emission), IEC 61000-6-2 (immunity), and EN 61010-2-201 (control equipment safety). Complies with Low Voltage Directive 2014/35/EU and EMC Directive 2014/30/EU. The module carries conformal coating and is rated for severe environments: gas (Gx, 3C4), dust (3S4), sand (3S4), salt (level 2), mold and fungal spore (3B2), plus Class I Division 2 hazardous location. Operating temperature –25 to 70 °C, storage –40 to 85 °C, humidity 5–95 % at 55 °C non‑condensing. Shock resistance 30 gn, vibration 3 gn — suited for rotating machinery and mobile equipment installations within those limits. ## Measurement performance Common‑mode rejection 120 dB at 50/60 Hz; differential‑mode rejection 60 dB. Measurement error at 25 °C: ±0.7 °C on Ni1000, ±2.1 °C on Pt100, ±2.7 to ±3.7 °C on thermocouples (varies by type), and ±0.05 % FS on voltage ranges. Resolution is 0.1 °C across all temperature probes. Temperature drift held to 25 or 30 ppm/°C depending on range. Nominal read cycle 200 ms for thermocouples, 400 ms for RTDs.","metaTitle":"Schneider BMXART0414H Modicon X80 Analog Input, 4 TC/RTD Iso","metaDescription":"4-channel isolated analog input module for thermocouples, RTDs, voltage, and resistance. Sigma-delta 16-bit, 120 dB CMRR, active production. Source to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Standards":"IEC 61131-2 IEC 61000-6-4 IEC 61000-6-2 EN 61010-2-201","Directives":"2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility","Status LED":"1 LED (green) RUN 1 LED per channel (green) channel diagnostic 1 LED (red) ERR 1 LED (red) I/O","Input level":"Low level","Recalibration":"Internal","Detection type":"Open circuit Cu 10 Open circuit Ni 100 Open circuit Ni 1000 Open circuit Pt 100 Open circuit Pt 1000 Open circuit thermocouple B Open circuit thermocouple E Open circuit thermocouple J Open circuit thermocouple K Open circuit thermocouple L Open circuit thermocouple N Open circuit thermocouple R Open circuit thermocouple S Open circuit thermocouple T Open circuit thermocouple U","Type of filter":"First order digital filtering","lifecycle_stage":"current","MTBF reliability":"1400000 H","Range of product":"Modicon X80","Shock resistance":"30 gn","Measurement error":"+/- 0.7 °C Ni 1000 25 °C +/- 2.1 °C Ni 100 25 °C +/- 2.1 °C Pt 100 25 °C +/- 2.1 °C Pt 1000 25 °C +/- 2.7 °C thermocouple U 25 °C +/- 2.8 °C thermocouple J 25 °C +/- 3 °C thermocouple L 25 °C +/- 3.2 °C thermocouple R 25 °C +/- 3.2 °C thermocouple S 25 °C +/- 3.5 °C thermocouple B 25 °C +/- 3.7 °C thermocouple E 25 °C +/- 3.7 °C thermocouple K 25 °C +/- 3.7 °C thermocouple N 25 °C +/- 3.7 °C thermocouple T 25 °C +/- 4 °C Cu 10 25 °C 0.05 % of full scale +/- 1.28 V 25 °C 0.05 % of full scale +/- 160 mV 25 °C 0.05 % of full scale +/- 320 mV 25 °C 0.05 % of full scale +/- 40 mV 25 °C 0.05 % of full scale +/- 640 mV 25 °C 0.05 % of full scale +/- 80 mV 25 °C 0.12 % of full scale 400 Ohm 25 °C 0.12 % of full scale 4000 Ohm 25 °C +/- 1.5 °C Ni 1000 - 25...70 °C +/- 3.5 °C Ni 100 - 25...70 °C +/- 3.5 °C Pt 100 - 25...70 °C +/- 3.5 °C Pt 1000 - 25...70 °C +/- 4.5 °C Cu 10 - 25...70 °C +/- 5.5 °C thermocouple J - 25...70 °C +/- 5.5 °C thermocouple L - 25...70 °C +/- 5.5 °C thermocouple R - 25...70 °C +/- 5.5 °C thermocouple S - 25...70 °C +/- 5.5 °C thermocouple U - 25...70 °C +/- 6 °C thermocouple B - 25...70 °C +/- 6 °C thermocouple E - 25...70 °C +/- 6 °C thermocouple K - 25...70 °C +/- 6 °C thermocouple N - 25...70 °C +/- 6 °C thermocouple T - 25...70 °C <= 0.3 % of full scale 4000 Ohm - 25...70 °C","Relative humidity":"5...95 % at 55 °C without condensation","Temperature drift":"25 ppm/°C 400 Ohm 25 ppm/°C 4000 Ohm 25 ppm/°C Ni 1000 25 ppm/°C thermocouple B 25 ppm/°C thermocouple E 25 ppm/°C thermocouple J 25 ppm/°C thermocouple K 25 ppm/°C thermocouple L 25 ppm/°C thermocouple N 25 ppm/°C thermocouple R 25 ppm/°C thermocouple S 25 ppm/°C thermocouple T 25 ppm/°C thermocouple U 30 ppm/°C +/- 1.28 V 30 ppm/°C +/- 160 mV 30 ppm/°C +/- 320 mV 30 ppm/°C +/- 40 mV 30 ppm/°C +/- 640 mV 30 ppm/°C +/- 80 mV 30 ppm/°C Cu 10 30 ppm/°C Ni 100 30 ppm/°C Pt 100 30 ppm/°C Pt 1000","Operating altitude":"0...2000 m 2000...5000 m with derating factor","Analogue input type":"Voltage +/- 1.28 V Voltage +/- 160 mV Voltage +/- 320 mV Voltage +/- 40 mV Voltage +/- 640 mV Voltage +/- 80 mV Resistor 400 Ohm 2 wires Resistor 400 Ohm 3 wires Resistor 400 Ohm 4 wires Resistor 4000 Ohm 2 wires Resistor 4000 Ohm 3 wires Resistor 4000 Ohm 4 wires Temperature probe -100...+260 °C Cu 10 Temperature probe -100...+450 °C Pt 100 conforming to UL/JIS Temperature probe -100...+450 °C Pt 1000 conforming to UL/JIS Temperature probe -200...+850 °C Pt 100 conforming to IEC Temperature probe -200...+850 °C Pt 1000 conforming to IEC Temperature probe -60...+180 °C Ni 100 Temperature probe -60...+180 °C Ni 1000 Thermocouple +130...+1820 °C thermocouple B Thermocouple +270...+1300 °C thermocouple N Thermocouple -200...+600 °C thermocouple U Thermocouple -200...+760 °C thermocouple J Thermocouple -200...+900 °C thermocouple L Thermocouple -270...+1000 °C thermocouple E Thermocouple -270...+1370 °C thermocouple K Thermocouple -270...+400 °C thermocouple T Thermocouple -50...+1769 °C thermocouple R Thermocouple -50...+1769 °C thermocouple S","Current consumption":"150 mA at 3.3 V DC 40 mA at 24 V DC","Protective treatment":"Conformal coating","Vibration resistance":"3 gn","Analogue input number":"4","Common mode rejection":"120 dB 50/60 Hz","Electrical connection":"40 ways 1 connector","Measurement resolution":"0.1 °C Cu 10 0.1 °C Ni 100 0.1 °C Ni 1000 0.1 °C Pt 100 0.1 °C Pt 1000 0.1 °C thermocouple B 0.1 °C thermocouple E 0.1 °C thermocouple J 0.1 °C thermocouple K 0.1 °C thermocouple L 0.1 °C thermocouple N 0.1 °C thermocouple R 0.1 °C thermocouple S 0.1 °C thermocouple T 0.1 °C thermocouple U 1280/2exp14 mV +/- 1.28 V 160/2exp14 mV +/- 160 mV 320/2exp14 mV +/- 320 mV 40/2exp14 mV +/- 40 mV 12.5 mOhm 400 Ohm 125 mOhm 4000 Ohm 640/2exp14 mV +/- 640 mV 80/2exp14 mV +/- 80 mV","IP degree of protection":"IP20","Nominal read cycle time":"200 ms with thermocouple 400 ms with temperature probe","Maximum conversion value":"+/- 100 % 400 Ohm +/- 100 % 4000 Ohm +/- 102.5 % +/- 1.28 V +/- 102.5 % +/- 160 mV +/- 102.5 % +/- 320 mV +/- 102.5 % +/- 40 mV +/- 102.5 % +/- 640 mV +/- 102.5 % +/- 80 mV","Analog/digital conversion":"Sigma delta 16 bits","Analogue input resolution":"15 bits + sign","Maximum wiring resistance":"20 Ohm 2 wires Cu 10 20 Ohm 2 wires Ni 100 20 Ohm 2 wires Pt 100 20 Ohm 3 wires Cu 10 20 Ohm 3 wires Ni 100 20 Ohm 3 wires Pt 100 200 Ohm 2 wires Ni 1000 200 Ohm 2 wires Pt 1000 200 Ohm 3 wires Ni 1000 200 Ohm 3 wires Pt 1000 50 Ohm 4 wires Cu 10 50 Ohm 4 wires Ni 100 50 Ohm 4 wires Pt 100 500 Ohm 4 wires Ni 1000 500 Ohm 4 wires Pt 1000","Product or component type":"Analog input module","Cold junction compensation":"External by Pt100 probe","Isolation between channels":"Isolated","Differential mode rejection":"60 dB 50/60 Hz","Environmental characteristic":"Gas resistant class Gx Gas resistant class 3C4 Dust resistant class 3S4 Sand resistant class 3S4 Salt resistant level 2 Mold growth resistant class 3B2 Fungal spore resistant class 3B2 Hazardous location class I division 2","Permitted overload on inputs":"+/- 7.5 V +/- 1.28 V +/- 7.5 V +/- 160 mV +/- 7.5 V +/- 320 mV +/- 7.5 V +/- 40 mV +/- 7.5 V +/- 640 mV +/- 7.5 V +/- 80 mV","Product specific application":"For severe environments","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$506.73 – $853.00","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/BMXART0414H/alternatives.json"},"ai":{"faq":[{"question":"What types of inputs does the BMXART0414H accept?","answer":"Four isolated channels, each configurable for thermocouples (B, E, J, K, L, N, R, S, T, U), RTDs (Pt100, Pt1000, Ni100, Ni1000, Cu10), low‑level voltage, and resistance (400 Ω or 4000 Ω, 2/3/4‑wire)."},{"question":"What key standards does the BMXART0414H comply with?","answer":"IEC 61131-2, IEC 61000-6-4 (emission), IEC 61000-6-2 (immunity), EN 61010-2-201, plus Low Voltage Directive 2014/35/EU and EMC Directive 2014/30/EU."},{"question":"What is the common‑mode rejection of the BMXART0414H?","answer":"120 dB at 50/60 Hz, with differential‑mode rejection of 60 dB."},{"question":"Can the BMXART0414H be used in harsh environments?","answer":"Yes, it carries conformal coating and is rated for severe environments including gas, dust, sand, salt, mold, and fungal spore resistance, plus Class I Division 2 hazardous locations. Operating temperature –25 to 70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/BMXART0414H","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/BMXART0414H when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}