{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"BMXDAI1614","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"BMXDAI1614","canonicalUrl":"https://aoctrl.com/schneider/BMXDAI1614","factsUrl":"https://aoctrl.com/api/mcp/products/BMXDAI1614","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Modicon X80 discrete input module, 16 isolated AC inputs, 100-120V, positive logic (sink), 86×32×134.6 mm, IP20.","salesMarkdown":"## Ratings that drive the fit The BMXDAI1614: Sixteen 120V AC inputs, each pulling 2 mA – so you get a Type 1 load curve without flooding the backplane. Guaranteed ON above 79V, OFF below 40V (sensor OK/fault threshold at 85V). Response: 10 ms ON, 20 ms OFF – slow enough to ignore contact bounce, fast enough for conveyor interlock logic. Channel-to-channel and channel-to-bus isolation at 1780 Vrms for one minute – that's the 60 Hz dielectric strength that keeps PLC ground loops from becoming cascading failures. Pollution degree 2, 5000 m altitude with derating. 86 mm deep, 32 mm wide, 134.6 mm tall – sits on a standard DIN rail in the X80 rack. IP20, so keep it inside a closed panel. 2- or 3-wire sensors: you need one external fast-blow 0.25A fuse per group of channels. Power draw: 126 mA at 3.3V DC plus 76 mA typical from the backplane, total dissipation 5 W. That leaves headroom for a few more slices in the same rack. Local diagnosis: green RUN LED, red ERR and I/O LEDs, plus one green per channel. MTBF 3700000 H.","metaTitle":"Schneider BMXDAI1614 Modicon X80 16-input AC module, 100-120","metaDescription":"BMXDAI1614 discrete input module, 16 isolated 100-120V AC inputs, IEC 61131-2 Type 1. Current production. 86mm depth. CE/UKCA/CULus/EAC/RCM. RFQ for stock and lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"86 mm","Width":"32 mm","Height":"134.6 mm","Marking":"CE UKCA CULus EAC RCM","Standards":"IEC 61131-2","Product weight":"0.157 kg","Protection type":"1 external fuse per group of channel0.25 A fast blow","lifecycle_stage":"current","Local signalling":"1 LED (green) for module operating (RUN) 1 LED per channel (green) for channel diagnostic 1 LED (red) for module error (ERR) 1 LED (red) for module I/O","MTBF reliability":"3700000 H","Pollution degree":"2","Range of product":"Modicon X80","Shock resistance":"30 gn","Input wiring mode":"2 or 3 wires","Relative humidity":"5...95 % at 0...60 °C without condensation","Device application":"Industrial application","Operating altitude":"0...2000 m 2000...5000 m with derating","Current consumption":"<= 126 mA at 3.3 V DC","Dielectric strength":"1780 V AC at 50/60 Hz 1 min","Sensor power supply":": 85...132 V","Discrete input logic":"Positive logic (sink)","Protective treatment":"Standard version","Vibration resistance":"3 gn","Discrete input number":"16","Discrete input current":"2 mA at 100...120 V AC","Discrete input voltage":"100...120 V AC for isolated","Power dissipation in W":"5 W","IP degree of protection":"IP20","Product or component type":"Discrete input module","Current state 0 guaranteed":"10 MOhm 500 V DC","Isolation between channels":"1780 Vrms for 1 minute","Voltage state 0 guaranteed":"= 2 mA","Voltage state 1 guaranteed":">= 79 V","AC activation response time":"10 ms","Typical current consumption":"76 mA DC","Voltage detection threshold":"< 40 V AC sensor fault > 85 V AC sensor OK","AC deactivation response time":"20 ms","Isolation between channels and bus":"1780 Vrms for 1 minute","Ambient air temperature for storage":"-40...85 °C","Complementary/Discrete input number":"16 isolated conforming to IEC 60947-5-2 at 100...120 V AC 16 isolated conforming to IEC 61131-2 Type 1 at 100...120 V AC","Ambient air temperature for operation":"0...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$577.85 – $1,307.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/106e4573aee89f3ee44fc9c5cb2980db.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/BMXDAI1614/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions of BMXDAI1614?","answer":"Depth 86 mm, width 32 mm, height 134.6 mm. Fits a standard Modicon X80 rack on DIN rail. IP20 protected for cabinet mounting."},{"question":"What compliance documentation is available for this module?","answer":"BMXDAI1614 carries CE, UKCA, CULus, EAC, and RCM markings and is built to IEC 61131-2. Schematics and declaration of conformity are standard deliverables."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/BMXDAI1614","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/BMXDAI1614 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}