{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"BMXDAO1605H","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"BMXDAO1605H","canonicalUrl":"https://aoctrl.com/schneider/BMXDAO1605H","factsUrl":"https://aoctrl.com/api/mcp/products/BMXDAO1605H","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Modicon X80 discrete output module, BMXDAO1605H, 16 triac outputs, 100–240 V AC, 0.6 A per channel, severe environment rated.","salesMarkdown":"The BMXDAO1605H: Per-channel current is 0.6 A at 60 °C, but drops to 0.24 A at 70 °C. The module max is 4.8 A at 60 °C (1.92 A at 70 °C). If your panel ambient runs near 70 °C, derate early — that's on the critical path for output budget. It carries conformal coating and gas, dust, sand, salt, and mold resistance — rated for severe environments (Gx, 3C4, 3S4, etc.). That means it lands before the window in places where standard modules wouldn't survive a season. Against the BMXDDO1602H (16-channel solid-state 24 V DC): this module is AC only, with triac outputs. The BMXDDO1602H has electronic short-circuit protection and a 1.5 A per channel limit, but runs on 24 V DC. If the BOM calls for AC loads (valves, contactors, indicators), the BMXDAO1605H fits; if it's a 24 V DC control panel, stick with the BMXDDO1602H. Against the BMXDRA0804T (8-channel relay, 100–150 V DC / 100–240 V AC): half the channel count, mechanical contacts, slower response (~10 ms). The BMXDAO1605H gives you twice the density with solid-state switching at 1 ms. Use the relay module if you need galvanic isolation per point or switch higher inrush; use the triac module for fast, frequent AC switching. ## Lifecycle and sourcing — what you need for the BOM freeze Directives on file: 2014/35/EU (Low Voltage) and 2014/30/EU (EMC). No specific RoHS, REACH, or UL statements in this record, but the conformal coating and severe-environment test set (gas, dust, salt) suggest it was designed for IEC 60068-2-type qualification. If a compliance pack is needed, flag it on the order. Requires an external fast-blow fuse per group; the module itself doesn't carry fuses onboard. Inrush peaks at 20 A, so size the fuse and wiring accordingly. That's a sourcing detail to confirm before the panel build window closes. The BMXDAO1605H fits any Modicon X80 rack slot. Spring-cage terminals on the front (not included in spec, but typical for X80 discrete modules — verify with the product manual if wiring detail is critical). IP20, so it belongs in an enclosure. Leakage current: 1.5 mA at 120 V AC, 3 mA at 240 V AC. If you're driving small PLC inputs or high-impedance loads, that leakage may hold the circuit on — plan a bleed resistor or verify load impedance above the leakage threshold. Response time: ≤1.011 ms resistive deactivation (AC zero-cross turn-off). For fast-acting solenoids or contactors, that's typically fine. If you need sub-ms switching, note the triac turns off at current zero, so there's a natural half-cycle delay.","metaTitle":"BMXDAO1605H, Modicon X80 16-Output Triac Module, 100-240V","metaDescription":"Active Modicon X80 16-output triac module, 100–240VAC, 0.6A per channel, severe environment rated, 1.8Mh MTBF. Sourced to order. Directives 2014/35/EU & 2014/30/EU.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Directives":"2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility","Status LED":"1 LED (green) module operating (RUN) 1 LED per channel (green) channel diagnostic 1 LED (red) module error (ERR) 1 LED (red) module I/O","Inrush current":"20 A","Protection type":"1 external fuse fast blow","lifecycle_stage":"current","MTBF reliability":"1800000 H","Range of product":"Modicon X80","Shock resistance":"30 gn","Relative humidity":"5...95 % at 55 °C without condensation","Operating altitude":"0...2000 m 2000...5000 m with derating factor","Current per channel":"0.24 A at 70 °C 0.6 A at 60 °C","Dielectric strength":"2830 V AC at 50/60 Hz 1 min","Discrete output type":"Triac","Maximum voltage drop":"10 MOhm 500 V DC","Protective treatment":"Conformal coating","Vibration resistance":"3 gn","Output current limits":"0.025...4.8 A","Discrete output number":"16","Discrete output current":"0.6 A","Discrete output voltage":"100...240 V AC","IP degree of protection":"IP20","Maximum leakage current":"1.5 mA at state 0 120 V AC 60 Hz 3 mA at state 0 240 V AC 60 Hz","Response time on output":"<= 1.011 ms resistive deactivation","Product or component type":"Discrete output module","Maximum current per module":"1.92 A 70 °C 4.8 A 60 °C","Typical current consumption":"79 mA at 3.3 V DC","Environmental characteristic":"Gas resistant class Gx Gas resistant class 3C4 Dust resistant class 3S4 Sand resistant class 3S4 Salt resistant level 2 Mold growth resistant class 3B2 Fungal spore resistant class 3B2","Product specific application":"For severe environments","Maximum current per output common":"2.4 A","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,052.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/176dca48b0fb65043eaf1eddc2347feb.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/BMXDAO1605H/alternatives.json"},"ai":{"faq":[{"question":"When sourcing BMXDAO1605H, what's the closest functional second-source — BMXDDO1602H?","answer":"The BMXDDO1602H is not a direct second-source because it is a 24 V DC solid-state module, while the BMXDAO1605H is 100–240 V AC triac. They share the same form factor but require different wiring and supply voltages."},{"question":"What compliance documents are available for BMXDAO1605H?","answer":"The listed directives are 2014/35/EU (Low Voltage) and 2014/30/EU (EMC). No further RoHS, REACH, or UL declarations are present in this record."},{"question":"What does the Status LED indicate?","answer":"The module has one green LED for RUN, one red for module error (ERR), one red for module I/O, and one green LED per channel for channel diagnostic."},{"question":"Will BMXDAO1605H drop into a panel that was specified around BMXDDO1602H without rewiring?","answer":"No. The BMXDAO1605H uses 100–240 V AC for outputs, while the BMXDDO1602H uses 24 V DC. The wiring, fuse rating, and load types are different. You would need to rewire the output field and possibly the power supply."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/BMXDAO1605H","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/BMXDAO1605H when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}