{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"BMXDAO1615H","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"BMXDAO1615H","canonicalUrl":"https://aoctrl.com/schneider/BMXDAO1615H","factsUrl":"https://aoctrl.com/api/mcp/products/BMXDAO1615H","rawCanonicalId":null},"summary":{"shortDescription":"Modicon X80 discrete output module, 16 isolated triac channels, 24…240 V AC, 1.2 A per channel, conformal coated, IP20, active production.","salesMarkdown":"The BMXDAO1615H: Each channel is isolated from the backplane and from each other; no shared commons beyond the 4 A per common group limit. The module draws 61 mA from the 3.3 V rail and 50 mA from the 24 V backplane supply, so power budget in the rack is modest. ## Built for severe environments This module carries a conformal coating and is rated for gas (Gx, 3C4), dust (3S4), sand (3S4), salt (level 2), and mold (3B2) resistance. Operating temperature spans -25…70 °C, storage -40…85 °C, and it shrugs off 30 gn shock and 3 gn vibration. That's a module you can drop into a water treatment plant, a steel mill, or an offshore skid without second-guessing the environment. ## Key ratings to watch when sizing Per-channel current: 1.2 A at 60 °C, derated to 0.6 A at 70 °C. Module total: 4 A at 60 °C, 2 A at 70 °C. Off-state leakage climbs with supply voltage — 1 mA at 24 V, 2.5 mA at 240 V — so if your load needs true zero-power when off, factor in that bleed. Response time is ≤10 ms for resistive deactivation, fast enough for medium-speed on/off control but not for PWM. Inrush current is 30 A, so a single fast-blow 4 A fuse per channel (external, not integrated) protects the triac. A varistor on each output handles overvoltage spikes from inductive kicks — no external snubber needed for typical motorized valve or contactor coils. Dielectric strength is 3000 V AC for 1 minute between output and backplane — solid isolation for environments with high common-mode noise. ## Physical and diagnostic fit Status LEDs: one green RUN LED for module operational, one red ERR LED for module error, one green LED per channel for channel diagnostics. That's enough to ring out a dead output at the cabinet door without a laptop. IP20 front, conformal coated board — mounts in any Modicon X80 rack slot, takes up one position. Power dissipation is only 1.45 W typical, so no forced air needed even in a densely packed rack at 60 °C. ## A note on the rating labels Absolute altitude limit: 2000 m full rating, 2000…5000 m with derating. If your site is above 2000 m, let me know — we'll recalculate headroom.","metaTitle":"BMXDAO1615H Modicon X80 16-Ch Triac Output Module, 1.2 A, Se","metaDescription":"Active Modicon X80 discrete output module. 16 isolated triac channels, 24–240 V AC, 1.2 A per channel, conformal coated for severe environments. MTBF 500k hours. RFQ for quantity p","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Status LED":"1 LED (green) module operating (RUN) 1 LED per channel (green) channel diagnostic 1 LED (red) module error (ERR) 1 LED (red) module I/O","Inrush current":"30 A","Protection type":"1 external fuse4 A fast blow","lifecycle_stage":"current","MTBF reliability":"500000 H","Range of product":"Modicon X80","Shock resistance":"30 gn","Network frequency":"50/60 Hz","Relative humidity":"0...95 % at -25...70 °C without condensation","Operating altitude":"0...2000 m 2000...5000 m with derating factor","Current per channel":"1.2 A at 60 °C 0.6 A at 70 °C","Dielectric strength":"3000 V AC at 50/60 Hz 1 min","Sensor power supply":"20...264 V","Discrete output type":"Triac","Maximum voltage drop":"10 MOhm 500 V DC","Protective treatment":"Conformal coating","Vibration resistance":"3 gn","Output current limits":"0.005...10 A","Discrete output number":"16 conforming to IEC 61131-2","Power dissipation in W":"1.45 W","Discrete output current":"1.2 A","Discrete output voltage":"24...240 V 20...264 V AC","IP degree of protection":"IP20","Maximum leakage current":"1 mA at state 0 24 V 1 mA at state 0 48 V 2 mA at state 0 115 V 2.5 mA at state 0 240 V","Response time on output":"<= 10 ms resistive deactivation","Network frequency limits":"47...63 Hz","Product or component type":"Discrete output module","Maximum current per module":"4 A 60 °C 2 A 70 °C","Output overload protection":"With varistor","Typical current consumption":"61 mA at 3.3 V DC 50 mA at 24 V DC","Environmental characteristic":"Gas resistant class Gx Gas resistant class 3C4 Dust resistant class 3S4 Sand resistant class 3S4 Salt resistant level 2 Mold growth resistant class 3B2","Product specific application":"For severe environments","Maximum current per output common":"4 A","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$453.39","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9e8a4a00536b84fec17adccad6fb1621.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/BMXDAO1615H/alternatives.json"},"ai":{"faq":[{"question":"What status LEDs does the BMXDAO1615H have?","answer":"One green RUN LED for module operating, one red ERR LED for module error, and one green LED per channel for channel diagnostics. No BAUD or network status — it's a simple output module."},{"question":"What is the inrush current rating?","answer":"The module is rated for 30 A inrush. Each output should be protected externally with a 4 A fast-blow fuse; the inrush won't blow it as long as the load is within the module's rated current."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/BMXDAO1615H","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/BMXDAO1615H when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}