{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"BMXDRA0805","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"BMXDRA0805","canonicalUrl":"https://aoctrl.com/schneider/BMXDRA0805","factsUrl":"https://aoctrl.com/api/mcp/products/BMXDRA0805","rawCanonicalId":null},"summary":{"shortDescription":"Schneider BMXDRA0805 Plc Expansion Modules — now discontinued. Supplied from remaining channel stock; full specifications, lifecycle and same-series options are below.","salesMarkdown":"## Overview The BMXDRA0805 is a Modicon X80 discrete output module from Schneider, order code BMXDRA0805, with 8 relay outputs rated for 3 A switching current. Output voltage range covers 24...240 V AC (19...264 V) and 12...24 V DC (10...34 V). The module is rated IP20 and draws 2.7 W from the backplane. ## Lifecycle The BMXDRA0805 is discontinued as of 2022-02-18. For new designs or replacements, evaluate the BMXDRA0815 or other current Modicon X80 relay output modules. ## Compliance The module complies with California Proposition 65 and meets the Low Voltage Directive 2014/35/EU and EMC Directive 2014/30/EU.","metaTitle":"Schneider BMXDRA0805 Modicon X80 8-Channel Relay Output Module","metaDescription":"Schneider BMXDRA0805 Modicon X80 discrete output module: 8 relay outputs, 3 A switching current, 24...240 V AC / 12...24 V DC, IP20, discontinued.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Directives":"2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility","Status LED":"1 LED (green) module operating (RUN) 1 LED per channel (green) channel diagnostic 1 LED (red) module error (ERR) 1 LED (red) module I/O","lifecycle_stage":"current","MTBF reliability":"2119902 H","Range of product":"Modicon X80","Shock resistance":"30 gn","Relative humidity":"5...95 % at 55 °C without condensation","Operating altitude":"0...2000 m 2000...5000 m with derating factor","Dielectric strength":"2000 V AC at 50/60 Hz 1 min","Discrete output type":"Relay","Protective treatment":"Standard version","Vibration resistance":"3 gn","Electrical durability":"AC-15: 100000 cycles at 220 VA 200...240 V (load factor 0.35) AC-12: 1000000 cycles at 110 VA 110...120 V AC-12: 1000000 cycles at 220 VA 200...240 V AC-12: 1000000 cycles at 50 VA 48 V AC-15: 1000000 cycles at 110 VA 200...240 V (load factor 0.35) DC-12: 1000000 cycles at 24 W 24 V DC-13: 1000000 cycles at 24 W 24 V AC-15: 10000000 cycles at 10 VA 110...120 V (load factor 0.35) AC-15: 10000000 cycles at 10 VA 200...240 V (load factor 0.35) AC-15: 150000 cycles at 110 VA 110...120 V (load factor 0.35) AC-15: 1500000 cycles at 50 VA 110...120 V (load factor 0.35) AC-15: 2000000 cycles at 24 VA 48 V (load factor 0.35) DC-13: 2000000 cycles at 10 W 24 V DC-12: 300000 cycles at 40 W 24 V AC-15: 3000000 cycles at 50 VA 200...240 V (load factor 0.35) AC-12: 500000 cycles at 110 VA 48 V AC-12: 500000 cycles at 220 VA 110...120 V AC-15: 5000000 cycles at 10 VA 48 V (load factor 0.35) AC-15: 500000 cycles at 24 VA 24 V (load factor 0.35) AC-12: 700000 cycles at 50 VA 24 V","Insulation resistance":"> 10 MOhm 500 V DC","Discrete output number":"8 conforming to IEC 61131-2","Power dissipation in W":"2.7 W","Discrete output voltage":"24...240 V 19...264 V AC 12...24 V 10...34 V DC","IP degree of protection":"IP20","Response time on output":"< 10 ms activation < 8 ms deactivation","Minimum switching current":"10 mA 5 V DC","Product or component type":"Discrete output module","Output overload protection":"Use 1 fast blow fuse per channel or group of channel","Typical current consumption":"79 mA at 3.3 V DC","Environmental characteristic":"Corrosion resistance Dust resistant","Output overvoltage protection":"Use discharge diode on each output DC Use RC circuit on each output AC Use ZNO surge limiter on each output AC","Output short-circuit protection":"Use 1 fast blow fuse per channel or group of channel","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"0...60 °C","[Ith] conventional free air thermal current":"3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$319.00 – $568.15","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/23489e02045de16533bf6616d2db8c72.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/BMXDRA0805/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/BMXDRA0805","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/BMXDRA0805 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}