{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"BMXDRA1605","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"BMXDRA1605","canonicalUrl":"https://aoctrl.com/schneider/BMXDRA1605","factsUrl":"https://aoctrl.com/api/mcp/products/BMXDRA1605","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Modicon X80 discrete output module, BMXDRA1605, 16 normally open relay outputs, 24-240 V AC / 24-48 V DC, 2 A thermal current.","salesMarkdown":"## Ratings that matter for sizing The BMXDRA1605: Minimum switching current is 1 mA at 5 V DC — the relay can handle low-power signals, not just motor or lamp loads. Response times clock in under 8 ms activation and under 10 ms deactivation, adequate for most valve and contactor sequences. Electrical durability is specified across AC-15, AC-12, DC-12, and DC-13 categories, with 100,000 cycles typical at common voltage/VA combinations and up to 300,000 cycles at reduced loads. Power dissipation totals 3 W for the module. ## Installation notes Typical current consumption is 100 mA from the 3.3 V backplane and 95 mA from the 24 V field supply. Each output requires an external fast-blow fuse for short-circuit and overload protection; use a free-wheeling diode across DC loads and an RC snubber across AC loads to suppress overvoltage. LEDs provide per-channel green channel diagnostics plus a red ERR and red I/O fault indication — no need for external annunciators.","metaTitle":"BMXDRA1605 Modicon X80 16-Relay Output Module, Active","metaDescription":"BMXDRA1605 discrete output module, 16 NO relay outputs, 24-240VAC/24-48VDC, 2A thermal current, active lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Status LED":"1 LED (green) RUN 1 LED per channel (green) channel diagnostic 1 LED (red) ERR 1 LED (red) I/O","lifecycle_stage":"current","MTBF reliability":"2100000 H","Range of product":"Modicon X80","Shock resistance":"30 gn","Relative humidity":"5...95 % at 55 °C without condensation","Operating altitude":"0...2000 m 2000...5000 m with derating factor","Dielectric strength":"2000 V AC at 50/60 Hz 1 min","Discrete output type":"Relay","Protective treatment":"Standard version","Vibration resistance":"3 gn","Discrete output logic":"Positive","Electrical durability":"AC-15: 100000 cycles at 240 VA 200 V (load factor 0.7) AC-15: 100000 cycles at 120 VA 200 V (load factor 0.35) AC-12: 100000 cycles at 200 VA 100 V AC-12: 100000 cycles at 80 VA 48 V AC-12: 100000 cycles at 50 VA 24 V AC-15: 100000 cycles at 120 VA 100 V AC-15: 100000 cycles at 120 VA 24 V AC-15: 100000 cycles at 120 VA 48 V DC-12: 100000 cycles at 24 W 24 V DC-13: 100000 cycles at 10 W 24 V DC-13: 100000 cycles at 10 W 48 V AC-15: 300000 cycles at 72 VA 200 V (load factor 0.7) AC-15: 300000 cycles at 36 VA 200 V (load factor 0.35) AC-12: 300000 cycles at 200 VA 200 V AC-12: 300000 cycles at 80 VA 100 V AC-12: 300000 cycles at 50 VA 48 V AC-15: 300000 cycles at 36 VA 100 V AC-15: 300000 cycles at 72 VA 100 V AC-15: 300000 cycles at 36 VA 48 V AC-15: 300000 cycles at 72 VA 48 V AC-15: 300000 cycles at 36 VA 24 V AC-15: 300000 cycles at 72 VA 24 V DC-13: 300000 cycles at 3 W 24 V DC-13: 300000 cycles at 3 W 48 V DC-13: 7000 cycles at 24 W 24 V DC-13: 7000 cycles at 24 W 48 V DC-12: 50000 cycles at 24 W 48 V","Insulation resistance":"> 10 MOhm 500 V DC","Discrete output number":"16 conforming to IEC 61131-2","Power dissipation in W":"3 W","Discrete output voltage":"24...48 V 19...60 V DC 24...240 V 19...264 V AC","IP degree of protection":"IP20","Response time on output":"< 8 ms activation < 10 ms deactivation","Minimum switching current":"1 mA 5 V DC","Product or component type":"Discrete output module","Output overload protection":"Use 1 fast blow fuse per channel or group of channel","Typical current consumption":"100 mA at 3.3 V DC 95 mA at 24 V DC","Output overvoltage protection":"Use discharge diode on each output DC Use RC circuit on each output AC Use ZNO surge limiter on each output AC","Output short-circuit protection":"Use 1 fast blow fuse per channel or group of channel","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"0...60 °C","[Ith] conventional free air thermal current":"2 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$184.15 – $419.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7af824bd6d3eabe9286f840908df9d69.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/BMXDRA1605/alternatives.json"},"ai":{"faq":[{"question":"What are the response times?","answer":"Activation time is under 8 ms; deactivation under 10 ms."},{"question":"What protection is built in?","answer":"No built-in short-circuit or overload protection; each channel or group requires an external fast-blow fuse. For overvoltage suppression, use a discharge diode on DC outputs and an RC circuit or ZNO limiter on AC outputs."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/BMXDRA1605","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/BMXDRA1605 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}