{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"BMXDRC0805","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"BMXDRC0805","canonicalUrl":"https://aoctrl.com/schneider/BMXDRC0805","factsUrl":"https://aoctrl.com/api/mcp/products/BMXDRC0805","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Modicon X80 relay discrete output module, BMXDRC0805, 8 outputs, 5...150 V DC / 24...240 V AC, active production.","salesMarkdown":"The BMXDRC0805 is a Modicon X80 relay output module from Schneider Electric with eight discrete outputs conforming to IEC 61131-2. It covers both AC and DC loads across 5...150 V DC and 24...240 V AC, making it a single SKU for mixed-voltage cabinets in an X80 rack. Thermal rating is 4 A at 40 °C, derated to 3 A at 50 °C and 2 A at 60 °C — factor that into slot loading if the rack runs warm. The module draws 101 mA at 24 V DC and dissipates 3.6 W. Protection is external: each output needs a fast-blow fuse for short-circuit and overload. For inductive DC loads, add a flyback diode per channel; for AC, an RC snubber or ZNO varistor. The module has no internal suppression, so a missing snubber will kill the relay contacts early. Deactivation time is 13 ms — that's the interval from coil drop to contact open. Not for fast-switching inductive loads where arcing time matters; but fine for general on/off of solenoids, contactors, and lamps. ## Electrical durability and sourcing Lifecycle stage is current and product status is Active. The BOM line is stable. Electrical durability varies widely with load. For AC-15 control circuits, expect 1,000,000 cycles at 10 VA / 100...120 V, but only 150,000 cycles at 220 VA. On DC-13 at 24 V, 100,000 cycles at 10 W, dropping to 40,000 cycles at 48 W. Match the duty class in the durability table to your actual load VA for realistic life planning.","metaTitle":"Schneider BMXDRC0805 Modicon X80 8 Relay Output Module","metaDescription":"BMXDRC0805 Modicon X80 relay output module, 8 channels, AC/DC 5-240V, active production, MTBF 2.65M H, 13ms deactivation.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Status LED":"1 LED (green) RUN 1 LED per channel (green) channel diagnostic 1 LED (red) ERR 1 LED (red) I/O","Protection type":"External short-circuit protection External overload protection External overvoltage protection, inductive AC network External overvoltage protection, inductive DC network","lifecycle_stage":"current","MTBF reliability":"2650000 H","Range of product":"Modicon X80","Shock resistance":"30 gn","Network frequency":"50/60 Hz","Relative humidity":"5...95 % at 0...60 °C without condensation","Operating altitude":"0...2000 m 2000...5000 m with derating factor","Dielectric strength":"1780 V AC at 50/60 Hz 1 min","Sensor power supply":"5...150 V 19...264 V","Protective treatment":"Standard version","Vibration resistance":"3 gn","Discrete output logic":"Positive or negative","Electrical connection":"40 ways terminal block","Electrical durability":"AC-12: 200000 cycles at 48 VA 24 V at 0...60 °C AC-12: 300000 cycles at 48 VA 48 V at 0...60 °C AC-12: 150000 cycles at 96 VA 48 V at 0...60 °C AC-12: 300000 cycles at 110 VA 100...120 V at 0...60 °C AC-12: 150000 cycles at 220 VA 100...120 V at 0...60 °C AC-12: 300000 cycles at 220 VA 200...250 V at 0...60 °C AC-12: 150000 cycles at 500 VA 200...250 V at 0...60 °C AC-15: 700000 cycles at 10 VA 24 V at 0...60 °C (load factor 0.4) AC-15: 500000 cycles at 24 VA 24 V at 0...60 °C (load factor 0.4) AC-15: 200000 cycles at 48 VA 24 V at 0...60 °C (load factor 0.4) AC-15: 700000 cycles at 10 VA 48 V at 0...60 °C (load factor 0.4) AC-15: 500000 cycles at 24 VA 48 V at 0...60 °C (load factor 0.4) AC-15: 300000 cycles at 48 VA 48 V at 0...60 °C (load factor 0.4) AC-15: 100000 cycles at 96 VA 48 V at 0...60 °C (load factor 0.4) AC-15: 1000000 cycles at 10 VA 100...120 V at 0...60 °C (load factor 0.4) AC-15: 300000 cycles at 50 VA 100...120 V at 0...60 °C (load factor 0.4) AC-15: 200000 cycles at 110 VA 100...120 V at 0...60 °C (load factor 0.4) AC-15: 70000 cycles at 220 VA 100...120 V at 0...60 °C (load factor 0.4) AC-15: 1000000 cycles at 10 VA 200...250 V at 0...60 °C (load factor 0.4) AC-15: 500000 cycles at 50 VA 200...250 V at 0...60 °C (load factor 0.4) AC-15: 200000 cycles at 110 VA 200...250 V at 0...60 °C (load factor 0.4) AC-15: 150000 cycles at 220 VA 200...250 V at 0...60 °C (load factor 0.4) DC-12: 200000 cycles at 24 W 24 V at 0...60 °C DC-12: 150000 cycles at 48 W 24 V at 0...60 °C DC-12: 150000 cycles at 40 W 48...60 V at 0...60 °C DC-12: 100000 cycles at 45 W 100...125 V at 0...60 °C DC-13: 100000 cycles at 10 W 24 V at 0...60 °C DC-13: 60000 cycles at 24 W 24 V at 0...60 °C DC-13: 40000 cycles at 48 W 24 V at 0...60 °C DC-13: 40000 cycles at 40 W 48...60 V at 0...60 °C DC-13: 100000 cycles at 15 W 100...125 V at 0...60 °C","Insulation resistance":"> 10 MOhm 500 V DC","Discrete output number":"8 conforming to IEC 61131-2","Power dissipation in W":"3.6 W","Discrete output voltage":"5...125 V 5...150 V DC 24...240 V 19...264 V AC","IP degree of protection":"IP20","Response time on output":"<= 13 ms deactivation","Network frequency limits":"47...63 Hz","Minimum switching current":"10 mA 5 V DC","Product or component type":"Relay discrete output module","Output overload protection":"Use 1 fast blow fuse per channel or group of channel","Typical current consumption":"40 mA at 3.3 V DC 101 mA at 24 V DC","Output overvoltage protection":"Use discharge diode on each output DC Use RC circuit on each output AC Use ZNO surge limiter on each output AC","Output short-circuit protection":"Use 1 fast blow fuse per channel or group of channel","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ith] conventional free air thermal current":"4 A 40 °C 3 A 50 °C 2 A 60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$204.47","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/BMXDRC0805/alternatives.json"},"ai":{"faq":[{"question":"What status LEDs does the BMXDRC0805 have?","answer":"One green RUN LED, one green LED per channel for channel diagnostics, one red ERR LED, and one red I/O LED."},{"question":"What protection type does the BMXDRC0805 require?","answer":"Protection is external: each output must be fused (fast-blow) for short-circuit and overload. For inductive DC loads, a discharge diode per output is required; for inductive AC loads, an RC snubber or ZNO surge limiter per output is required."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/BMXDRC0805","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/BMXDRC0805 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}