{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C063H460FM","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C063H460FM","canonicalUrl":"https://aoctrl.com/schneider/C063H460FM","factsUrl":"https://aoctrl.com/api/mcp/products/C063H460FM","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NS new generation, C063H460FM, 4P MCCB, 630 A at 50 °C, MicroLogic 6.0 electronic trip unit, 70 kA Icu at 415 V AC, fixed mount.","salesMarkdown":"## 630 A, 4-pole MCCB with MicroLogic 6.0 LSI protection It carries a MicroLogic 6.0 electronic trip unit providing LSI protection — long-time (L) for overload, short-time (S) for short-time short-circuit, and instantaneous (I) for high-fault clearing. The H breaking capacity code delivers 70 kA Icu at 380/415 V AC, 50/60 Hz per IEC 60947-2, making it suitable for distribution switchboards where high fault current and selectivity are required. Rated 630 A at 50 °C, this breaker sits in the ComPacT NS630b...1600 new generation family, used for main or feeder protection in LV distribution panels. The 4P configuration with neutral left handles three-phase plus neutral loads without a separate neutral disconnect. The H-rated frame gives 85 kA Icu at 240 V, 70 kA at 415 V, 65 kA at 440 V, and 42 kA at 690 V AC. For a 630 A main breaker on a 415 V system, 70 kA Icu provides solid short-circuit withstand for most industrial service-entrance applications — enough headroom for coordination with downstream 25–50 kA rated feeders. Category B utilization (IEC 60947-2) means it is designed for selectivity, not just cable protection. Fixed mount on a backplate, 327 mm high × 280 mm wide × 147 mm deep. Front-side connection both top and bottom — no rear-access requirement. ## Trip unit and diagnostics MicroLogic 6.0 is fully electronic, with 20-minute thermal memory for accurate overload replay after a trip. Four red LEDs indicate fault type (long-time, short-time, instantaneous, ground fault) and one yellow LED signals overload pre-alarm — useful for field troubleshooting without plugging in a handheld. No earth-leakage protection built in; add a Vigi module externally if ground-fault protection is needed.","metaTitle":"Schneider Electric C063H460FM ComPacT NS 630A 4P MCCB, 70kA","metaDescription":"Schneider Electric C063H460FM ComPacT NS new generation MCCB, 630A at 50°C, 4P, MicroLogic 6.0 trip unit, 70kA Icu at 415V AC. Active lifecycle. Order to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"147 mm","Poles":"4P","Width":"280 mm","Height":"327 mm","Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Control Type":"Manually operated","Product Status":"Active","Terminal Pitch":"70 mm","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Breaking Capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"800 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Utilization Category":"Category B","Connection Surface Top":"Front","Electrical Life Cycles":"2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2","Mechanical Life Cycles":"10000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a8ebbf150a639320ff7ddda3819be7e.pdf","sourceUrl":"https://www.se.com/th/en/product/C063H460FM/circuit-breaker-compact-ns630bh-70ka-at-415vac-4p-fixed-manually-operated-micrologic-6-0-control-unit-630a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C063H460FM/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C063H460FM","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C063H460FM when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}