{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C080H360FM","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C080H360FM","canonicalUrl":"https://aoctrl.com/schneider/C080H360FM","factsUrl":"https://aoctrl.com/api/mcp/products/C080H360FM","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NS new generation, C080H360FM, 3P 800 A circuit breaker with MicroLogic 6.0 electronic trip unit, 85 kA Icu at 240 V AC, fixed mount.","salesMarkdown":"## What this 800 A breaker brings to a distribution panel The Schneider C080H360FM is a ComPacT NS new generation 3-pole circuit breaker rated 800 A at 50 °C, carrying a MicroLogic 6.0 electronic trip unit. The H breaking capacity code means 85 kA Icu at 220/240 V AC and 70 kA at 380/415 V AC — enough to handle high-fault utility feeds without cascading upstream. The trip unit covers L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground fault) protection, all configurable via the front interface. It is manually operated, fixed-mounted to a backplate, and suited for isolation per EN/IEC 60947-2. The 85 kA at 240 V AC matters for North American 208/240 V services — it clears a bolted fault at the main before the let-through energy damages branch devices. The 65 kA at 440 V and 50 kA at 500/525 V cover the higher-voltage distribution common in mining or marine installations. Category B utilization means it is listed for selectivity with other breakers in the same series. Fixed mount to a backplate. Width 210 mm, height 327 mm, depth 147 mm — the depth is the dimension that determines gland-plate clearance in a shallow enclosure. Connection pitch is 70 mm, front-connected both upside and downside. IP40 enclosure rating, IK07 impact resistance. Power dissipation 15 W at rated current — account for that in the panel thermal budget. ## Durability and thermal memory Mechanical endurance is 10 000 cycles. Electrical endurance at full rated current: 2000 cycles at 690 V In, 4000 cycles at 690 V In/2, 5000 cycles at 440 V In, 6000 cycles at 440 V In/2. The MicroLogic 6.0 includes a 20-minute thermal memory — after a trip, it remembers the thermal state of the conductor for that window, preventing nuisance reclose on a still-hot circuit.","metaTitle":"Schneider C080H360FM ComPacT NS 800A, 85 kA Icu 240V AC","metaDescription":"C080H360FM is a Schneider ComPacT NS new generation 3P 800A circuit breaker with MicroLogic 6.0 trip unit. 85 kA Icu at 240V AC, 70 kA at 415V AC. Active production. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"147 mm","Standards":"EN/IEC 60947-2","Width (W)":"210 mm","Height (H)":"327 mm","Control type":"Manually operated","Network type":"AC","Power losses":"15 W","Product name":"ComPacT NS new generation","Mounting mode":"Fixed","Thermal memory":"20 mn","Trip unit name":"MicroLogic 6.0","Number of poles":"3P","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection","lifecycle_stage":"current","Connection pitch":"70 mm","Local signalling":"4 LEDs (red) for fault indication 1 LED (yellow) for overload","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"ComPacT NS630b...1600 new generation","Trip unit rating":"800 A at 50 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Network frequency":"50/60 Hz","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"800 A at 50 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category B","Electrical durability":"2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2","Mechanical durability":"10000 cycles","Breaking capacity code":"H 70 kA 415 V AC","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Protected poles description":"3D","Auxiliary contact composition":"1 NO/NC","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"12.5...600 s at 1.5 x Ir 0.5...24 s at 6 x Ir 0.7...16.6 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Tsd] Short-Time Delay Adjustment Range":"0.1...0.4 s I²t=on 0...0.4 s I²t=off","[Icw] rated short-time withstand current":"19.2 kA 1 s conforming to IEC 60947-2","[Ig] ground-fault pick-up adjustment range":"0.3...1 x In for In 0.2...1 x In for 400 A < In < 1250 A 500...1200 A for In >= 1250 A","Long-time protection delay adjustment type tr":"Adjustable 9 settings","[tg] Ground-fault time delay adjustment range":"0.1...0.4 s I²t=on 0...0.4 s I²t=off","Short-time protection delay adjustment type tsd":"Adjustable","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","Ground-fault protection pick-up adjustment type Ig":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"0.4...1 x In","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","Ground-fault protection time delay adjustment type tg":"Adjustable","[Ii] instantaneous protection pick-up adjustment range":"Off 2...15 x In","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/14bcf7c11eb16b3fa7c13ac02618d795.pdf","sourceUrl":"https://www.se.com/ie/en/product/C080H360FM/circuit-breaker-compact-ns800h-70ka-at-415vac-3p-fixed-manually-operated-micrologic-6-0-control-unit-800a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C080H360FM/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for C080H360FM?","answer":"Submit an RFQ against this order code. Pricing and stock are confirmed at quote time through independent distribution channels."},{"question":"What is C080H360FM's breaking capacity at 415 V?","answer":"70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2."},{"question":"What protection functions does the MicroLogic 6.0 trip unit provide?","answer":"It covers L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault) protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C080H360FM","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C080H360FM when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}