{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C100N460FM","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C100N460FM","canonicalUrl":"https://aoctrl.com/schneider/C100N460FM","factsUrl":"https://aoctrl.com/api/mcp/products/C100N460FM","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NS new generation, C100N460FM, 4P fixed circuit breaker, 1000 A, MicroLogic 6.0 electronic trip unit, 85 kA Icu at 240 V AC, 50 kA at 415 V AC, EN/IEC 60947-2.","salesMarkdown":"The C100N460FM is a Schneider Electric ComPacT NS new generation 4-pole fixed circuit breaker, rated 1000 A at 50 °C, with a MicroLogic 6.0 electronic trip unit providing L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection. The 85 kA Icu at 240 V AC and 50 kA at 415 V AC mean this breaker can safely interrupt fault currents up to those levels without upstream coordination failure; the N breaking capacity code (50 kA at 415 V) tells you it's rated for high-fault industrial networks. The 1000 A frame and trip unit are matched, so you don't need to oversize the breaker for the load — it's already sized for a 1000 A feeder or main. ## Trip unit and protection logic MicroLogic 6.0 is an electronic trip unit with a 20-minute thermal memory. That memory means the breaker remembers prior heating from overloads and shortens the trip time on a repeated event — important for motor or transformer feeders where inrush can mask a developing fault. The L, S, I, G protection curves are adjustable via the trip unit's dials, giving you selectivity coordination downstream. No integral earth-leakage protection is included; if you need that, you add an external Vigi module. Fixed mounting on a backplate, with front connections both upside and downside. Neutral is on the left. Dimensions: 280 mm wide, 327 mm high, 147 mm deep. IK07 impact rating handles accidental tool strikes during installation. ## Local signalling and diagnostics Four red LEDs for fault indication (trip cause) and one yellow LED for overload pre-alarm. That saves time on troubleshooting — you can read the trip history without plugging in a laptop. The manually operated control type means no motor operator is built in; add one externally if remote switching is needed.","metaTitle":"C100N460FM ComPacT NS Circuit Breaker, 1000 A, 85 kA Icu","metaDescription":"Schneider Electric C100N460FM ComPacT NS new generation 4P circuit breaker. 1000 A rating, 85 kA Icu at 240 V AC, MicroLogic 6.0 electronic trip unit. EN/IEC 60947-2. Current produ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Range":"ComPacT","Depth (D)":"147 mm","Standards":"EN/IEC 60947-2","Width (W)":"280 mm","Height (H)":"327 mm","Control type":"Manually operated","Network type":"AC","Power losses":"22 W","Product name":"ComPacT NS new generation","Mounting mode":"Fixed","Thermal memory":"20 mn","Trip unit name":"MicroLogic 6.0","Number of poles":"4P","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection","lifecycle_stage":"current","Connection pitch":"70 mm","Local signalling":"4 LEDs (red) for fault indication 1 LED (yellow) for overload","Mounting support":"Backplate","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60947","Range of product":"ComPacT NS630b...1600 new generation","Trip unit rating":"1000 A at 50 °C","Breaking capacity":"85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","Network frequency":"50/60 Hz","Relative humidity":"0...95 %","Upside connection":"Front","Device application":"Distribution","Operating altitude":"0...2000 m without derating 2000 m...5000 m with derating","[In] rated current":"1000 A at 50 °C","Downside connection":"Front","Overvoltage category":"III","Trip unit technology":"Electronic","Utilisation category":"Category B","Electrical durability":"2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2","Mechanical durability":"10000 cycles","Breaking capacity code":"N 50 kA 415 V AC","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2","Neutral protection setting":"No protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D)","Protected poles description":"4D","Auxiliary contact composition":"1 NO/NC","[Ui] rated insulation voltage":"800 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz","Zone selective interlocking ZSI":"Without","Electrical shock protection class":"Class II on front face","Ambient air temperature for storage":"-50...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"12.5...600 s at 1.5 x Ir 0.5...24 s at 6 x Ir 0.7...16.6 s at 7.2 x Ir","[Uimp] rated impulse withstand voltage":"8 kV conforming to IEC 60947-2","[Tsd] Short-Time Delay Adjustment Range":"0.1...0.4 s I²t=on 0...0.4 s I²t=off","[Icw] rated short-time withstand current":"19.2 kA 1 s conforming to IEC 60947-2","[Ig] ground-fault pick-up adjustment range":"0.3...1 x In for In 0.2...1 x In for 400 A < In < 1250 A 500...1200 A for In >= 1250 A","Long-time protection delay adjustment type tr":"Adjustable 9 settings","[tg] Ground-fault time delay adjustment range":"0.1...0.4 s I²t=on 0...0.4 s I²t=off","Short-time protection delay adjustment type tsd":"Adjustable","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","Ground-fault protection pick-up adjustment type Ig":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"0.4...1 x In","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","Ground-fault protection time delay adjustment type tg":"Adjustable","[Ii] instantaneous protection pick-up adjustment range":"Off 2...15 x In","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9911f05b3d60c76eefb23e716992ae4f.pdf","sourceUrl":"https://www.se.com/id/en/product/C100N460FM/circuit-breaker-compact-ns1000n-50ka-at-415vac-4p-fixed-manually-operated-micrologic-6-0-control-unit-1000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C100N460FM/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for C100N460FM?","answer":"Submit an RFQ through this listing. The part is sourced and quoted to order through independent distribution; availability and current pricing are confirmed at quote time. No stock count or price is published here."},{"question":"What is the closest alternative to C100N460FM in the ComPacT family?","answer":"Within the ComPacT NS new generation range, the closest alternative would be a breaker with the same 1000 A frame and MicroLogic 6.0 trip unit but a different breaking capacity code (e.g., S or H) if your fault level is lower or higher than the N code's 50 kA at 415 V. The physical footprint and connection pitch are identical across the range, so swapping the breaking capacity code is a direct mechanical fit. Verify the Icu requirement against your system's prospective fault current before substituting."},{"question":"What compliance documentation does Schneider Electric provide for C100N460FM?","answer":"The breaker is certified to EN/IEC 60947-2. It carries an IK07 impact rating per EN 50102 and IP40 per IEC 60529. Pollution degree 3 per IEC 60947 and overvoltage category III are declared. Schneider typically provides a Declaration of Performance and CE marking for this range; RoHS/REACH declarations are available on request from the manufacturer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C100N460FM","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C100N460FM when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}