{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C1035Z100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C1035Z100","canonicalUrl":"https://aoctrl.com/schneider/C1035Z100","factsUrl":"https://aoctrl.com/api/mcp/products/C1035Z100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, MicroLogic 5.2 A-Z electronic trip unit, 3 poles, 100 A at 40 °C, LSI protection, LCD display, zone selective interlocking.","salesMarkdown":"The Schneider Electric C1035Z100 is a MicroLogic 5.2 A-Z electronic trip unit for the ComPacT NSX100...250 molded-case circuit breaker platform. It's the brains of the breaker — the part that measures current, decides when to trip, and logs what happened. This is an electronic trip unit, not a thermal-magnetic one. That means you get adjustable long-time (L), short-time (S), and instantaneous (I) protection — LSI — plus a full LCD display that shows metered values, alarm logs, and event histories. It communicates via the breaker's internal bus — energy metering, protection settings, time-stamped events, demand values, and maintenance indicators all come through that channel. Zone selective interlocking (ZSI) is built in, so in a multi-tier distribution panel you can wire the trip units together to clear a fault at the closest breaker without waiting for a time delay. That's the difference between a coordinated shutdown and a whole-floor blackout. The long-time pickup Ir is adjustable from 40 to 100 A in nine steps, with a delay Tr adjustable from 15 to 400 seconds at 1.5 x Ir. That range lets you set the overload curve to match a transformer inrush or a motor start without nuisance tripping, but also clear a sustained overload before the cable insulation degrades. The short-time pickup Isd adjusts from 1.5 to 10 x Ir with a delay tsd from 0 to 0.4 seconds, I²t on or off. Instantaneous pickup Ii goes from 1.5 to 12 x In. If you're doing a selective coordination study per IEC 60947-2, these are the knobs you turn to get the time-current curves to stack properly. ## Physical and environmental fit It's a 3-pole unit with 3D protected poles, designed for fixed mounting in the ComPacT NSX100...250 breaker frame. No earth-leakage protection built in — if you need that, you'd pair it with a Vigi module or an external RCD.","metaTitle":"Schneider Electric C1035Z100 MicroLogic 5.2 A-Z Trip Unit, 1","metaDescription":"Schneider Electric C1035Z100 MicroLogic 5.2 A-Z trip unit for ComPacT NSX100-250. 100 A rating, LSI protection, LCD display, ZSI. Active lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Range":"ComPacT","Standards":"EN/IEC 60947-2","Display type":"LCD display","Thermal memory":"20 minutes before and after tripping","Trip unit name":"MicroLogic 5.2 A-Z","Protection type":"L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection","lifecycle_stage":"current","Local signalling":"Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload","Pollution degree":"3 conforming to IEC 60947-1","Range of product":"ComPacT NSX100...250","Trip unit rating":"100 A at 40 °C","Poles description":"3P","Device application":"16 Hz 2/3 networks","Type of measurement":"Ammeter","Trip unit technology":"Electronic","Communication of data":"Energy metering Protection and alarm settings Time-stamped histories and event tables Instantaneous and demand values Maintenance indicators Demand current and power Power quality Maximeters/minimeters","IP degree of protection":"IP40 conforming to IEC 60529","Earth-leakage protection":"Without","Electrical data recording":"Maintenance indicators","Product or component type":"Trip unit","Protected poles description":"3D","Circuit breaker mounting mode":"Fixed","Trip unit protection functions":"LSI","[Ue] rated operational voltage":"250/500 V AC 16 Hz 2/3","Zone selective interlocking ZSI":"With","Electrical shock protection class":"Class II","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","Long-time protection delay adjustment type tr":"Adjustable","Short-time protection delay adjustment type tsd":"Adjustable","[Tr] Long-Time Protection Delay Adjustment Range":"15...400 s at 1.5 x Ir 0.35...11 s at 7.2 x Ir 0.5...16 s at 6 x Ir","Short-time protection pick-up adjustment type Isd":"Adjustable 9 settings","[Ir] long-time protection pick-up adjustment range":"40...100 A","[tsd] Short-time protection delay adjustment range":"0...0.4 s I²t=off 0.1...0.4 s I²t=on","Instantaneous protection pick-up adjustment type Ii":"Adjustable","[Isd] Short-time protection pick-up adjustment range":"1.5...10 x Ir","[Ii] instantaneous protection pick-up adjustment range":"1.5...12 x In","Long-time pick-up adjustment type Ir (thermal protection)":"Adjustable 9 settings"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/550e634f27aa5c5ea98b38a7d444a1bd.pdf","sourceUrl":"https://www.se.com/nz/en/product/C1035Z100/trip-unit-micrologic-5-2az-compact-nsx100-160-250-3-poles-electronic-basic-protections-special-applications-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C1035Z100/alternatives.json"},"ai":{"faq":[{"question":"What standards does the C1035Z100 comply with?","answer":"It complies with EN/IEC 60947-2, the standard for low-voltage switchgear and controlgear — specifically for circuit breakers. Pollution degree 3 per IEC 60947-1 and electrical shock protection Class II also apply."},{"question":"What protection functions does the MicroLogic 5.2 A-Z trip unit provide?","answer":"LSI protection: long-time (L) for overload, short-time (S) for short-circuit with adjustable delay, and instantaneous (I) for high-level faults. All three are adjustable independently, with the ranges listed in the spec table."},{"question":"Where can I buy the C1035Z100 and get current pricing?","answer":"We source the C1035Z100 to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ and we'll come back with a commercial offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C1035Z100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C1035Z100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}