{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C1042G100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C1042G100","canonicalUrl":"https://aoctrl.com/schneider/C1042G100","factsUrl":"https://aoctrl.com/api/mcp/products/C1042G100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100...250, MicroLogic 2.2 G trip unit, 4-pole, 100 A at 40 °C, LSoI protection, generator application.","salesMarkdown":"The C1042G100 is a MicroLogic 2.2 G electronic trip unit for the ComPacT NSX100...250 range, rated 100 A at 40 °C. It provides LSoI protection — long-time overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I) — tailored for generator applications. The 4-pole design handles 3D + N/2, 4D, or 3D neutral configurations. The long-time pickup (Ir) is adjustable from 40 to 100 A in nine steps, so you dial in the generator's full-load amp rating, not a fixed value. Short-time pickup (Isd) adjusts from 1.5 to 9 x Ir, giving you selectivity headroom downstream. Instantaneous pickup (Ii) is fixed at 1500 A, which clears hard faults fast. This is the trip unit only — it mounts into a ComPacT NSX100, NSX160, or NSX250 molded-case circuit breaker frame. The breaker itself is fixed-mount, 4-pole, with neutral on the left.","metaTitle":"C1042G100 MicroLogic 2.2 G trip unit, 100A, generator protec","metaDescription":"C1042G100 trip unit for ComPacT NSX100-250. 100A, MicroLogic 2.2 G, LSoI protection, generator application. Active production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"690 V AC 50/60 Hz","IP Rating":"IP40","Application":"Generator","Product Status":"Active","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3d211005cd70e889e3ab7d9f91ae0a1e.pdf","sourceUrl":"https://www.se.com/ng/en/product/C1042G100/trip-unit-micrologic-2-2g-compact-nsx100-160-250-4-poles-electronic-basic-protections-generator-protection-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C1042G100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C1042G100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C1042G100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}