{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C1044A040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C1044A040","canonicalUrl":"https://aoctrl.com/schneider/C1044A040","factsUrl":"https://aoctrl.com/api/mcp/products/C1044A040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100...250, MicroLogic 4.2 AL electronic trip unit, 40 A at 40 °C, 4P, EN/IEC 60947-2, integrated earth-leakage protection.","salesMarkdown":"The Schneider Electric C1044A040 is a MicroLogic 4.2 AL electronic trip unit for the ComPacT NSX100...250 range, rated 40 A at 40 °C with 4 poles (4P). The trip unit integrates earth-leakage protection (Class A) and provides LSoI protection functions: long-time (L), short-time (So), and instantaneous (I) short-circuit protection, plus overload protection. ## Protection settings and adjustment ranges The long-time protection pick-up (Ir) is adjustable from 18 to 40 A, with fixed delay settings: 400 s at 1.5 x Ir, 16 s at 6 x Ir, and 11 s at 7.2 x Ir. The short-time protection pick-up (Isd) adjusts from 1.5 to 10 x Ir with a fixed delay. Instantaneous protection (Ii) is fixed at 600 A. Earth-leakage sensitivity (IΔn) and time delay (Δt) are both adjustable. The neutral protection settings offer three options: 0.5 x Ir (3D + N/2), 1 x Ir (4D), or no protection (3D). Rated for ambient air temperatures from -25 to 70 °C during operation and -40 to 85 °C in storage. IP40 protection per IEC 60529. The trip unit mounts fixed in the ComPacT NSX breaker; neutral position is left. Local signalling includes a flashing green LED for ready status, red LED at 105% Ir for overload, orange LED at 90% Ir for overload, and a yellow indicator for residual current.","metaTitle":"Schneider Electric C1044A040 MicroLogic 4.2 AL Trip Unit, 40","metaDescription":"Schneider Electric C1044A040 MicroLogic 4.2 AL electronic trip unit for ComPacT NSX. 40 A at 40 °C, 4P, EN/IEC 60947-2. Integrated earth-leakage protection. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Product Status":"Active","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/09718ca3e5103c17f4c7b6d3ca0324cd.pdf","sourceUrl":"https://www.se.com/be/en/product/C1044A040/trip-unit-micrologic-vigi-4-2al-compact-nsx100-160-250-4-poles-electronic-basic-protections-earth-leakage-alarm-40a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C1044A040/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C1044A040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C1044A040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}