{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C1044A100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C1044A100","canonicalUrl":"https://aoctrl.com/schneider/C1044A100","factsUrl":"https://aoctrl.com/api/mcp/products/C1044A100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, MicroLogic 4.2 AL electronic trip unit, 100 A at 40 °C, 4 poles, EN/IEC 60947-2.","salesMarkdown":"## Trip unit for ComPacT NSX — MicroLogic 4.2 AL The C1044A100 is a MicroLogic 4.2 AL electronic trip unit from the Schneider Electric ComPacT NSX100...250 range. The protection package is LSoI — long-time, short-time with fixed delay, and instantaneous — with a fixed instantaneous pickup of 1500 A. ## What the protection settings mean for your panel Long-time pickup (Ir) is adjustable from 40 to 100 A in the field, with a fixed time delay. The delay curve gives you 400 s at 1.5 x Ir, 16 s at 6 x Ir, and 11 s at 7.2 x Ir — that's a slow blow for feeder protection, not a motor-start curve. Short-time pickup (Isd) is adjustable 1.5 to 10 x Ir, with a fixed delay. Instantaneous (Ii) is fixed at 1500 A. That means for a 100 A setting, anything above 1500 A trips instantly — no adjustment. Earth-leakage sensitivity (IΔn) and time delay (Δt) are both adjustable via the rotary switch on the front. The neutral protection settings let you choose 0.5 x Ir (3D + N/2), 1 x Ir (4D), or no protection (3D) — match it to your system grounding. IP40 front-of-panel protection handles the usual dry indoor panel.","metaTitle":"Schneider Electric C1044A100 MicroLogic 4.2 AL Trip Unit, 10","metaDescription":"Schneider Electric C1044A100 MicroLogic 4.2 AL electronic trip unit for ComPacT NSX100-250. Rated 100 A at 40 °C, 4P, EN/IEC 60947-2. Integrated earth-leakage protection. Active pr","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Product Status":"Active","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$11.01","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3c25df0f3211a495abbcc1bf3ccbecdd.pdf","sourceUrl":"https://www.se.com/vn/en/product/C1044A100/trip-unit-micrologic-vigi-4-2al-compact-nsx100250-4-poles-electronic-basic-protections-earth-leakage-alarm-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C1044A100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C1044A100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C1044A100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}