{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C1044B100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C1044B100","canonicalUrl":"https://aoctrl.com/schneider/C1044B100","factsUrl":"https://aoctrl.com/api/mcp/products/C1044B100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100...250, MicroLogic 4.2 AB trip unit, 100 A at 40 °C, 4P, LSoIR + earth-leakage, EN/IEC 60947-2.","salesMarkdown":"## Trip unit for ComPacT NSX breakers The Schneider Electric C1044B100 is a MicroLogic 4.2 AB electronic trip unit for the ComPacT NSX100...250 range, rated 100 A at 40 °C in a 4-pole configuration. It provides LSoIR protection — long-time overload (L), short-time short-circuit with fixed delay (So), instantaneous short-circuit (I), and integrated earth-leakage (R) — all in one unit. The trip unit is EN/IEC 60947-2 certified, so it meets the standard for low-voltage switchgear and controlgear in industrial panels. ## Protection settings and adjustability The long-time pickup Ir is adjustable from 40 to 100 A, letting you match the trip threshold to the actual load current. Short-time pickup Isd is adjustable from 1.5 to 10 times Ir, while instantaneous pickup Ii is fixed at 1500 A. Earth-leakage sensitivity IΔn and time delay Δt are both adjustable, and the unit includes a rotary switch to disable earth-leakage protection when needed. The trip unit mounts fixed in a ComPacT NSX100...250 circuit breaker.","metaTitle":"Schneider Electric C1044B100 ComPacT NSX MicroLogic 4.2 AB T","metaDescription":"Schneider Electric C1044B100 ComPacT NSX100...250 trip unit, MicroLogic 4.2 AB, 100 A at 40 °C, 4P, LSoIR protection with integrated earth-leakage. EN/IEC 60947-2. Current lifecycl","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Special application","Product Status":"Active","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/61e930529943df18b7ffae1600e5654c.pdf","sourceUrl":"https://www.se.com/za/en/product/C1044B100/trip-unit-micrologic-vigi-4-2ab-compact-nsx100250-4p-basic-and-earth-leakage-protections-special-application-100a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C1044B100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C1044B100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C1044B100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}