{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C1047E040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C1047E040","canonicalUrl":"https://aoctrl.com/schneider/C1047E040","factsUrl":"https://aoctrl.com/api/mcp/products/C1047E040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX series, MicroLogic 7.2 E electronic trip unit, 40 A at 40 °C, 4 poles, LSIR protection with integrated earth leakage, EN/IEC 60947-2.","salesMarkdown":"## Trip unit for ComPacT NSX — MicroLogic 7.2 E The Schneider Electric C1047E040 is a MicroLogic 7.2 E electronic trip unit for the ComPacT NSX100...250 range. It's rated 40 A at 40 °C (Ir adjustable 18–40 A) and carries LSIR protection — long-time, short-time, instantaneous, and residual earth-leakage — all integrated into one 4-pole unit. The LCD display gives you local readout of metered values, event logs, and protection settings without needing a connected gateway. Built to EN/IEC 60947-2, this trip unit is designed for distribution boards where you need coordinated protection and energy metering in one package. The 20-minute thermal memory before and after tripping means the unit remembers the thermal state of the conductors even after a short interruption — useful when re-energizing a circuit that just tripped on overload. L (long-time) protects against sustained overloads — Ir adjustable 18–40 A with tr delay from 15 s to 400 s at 1.5×Ir. S (short-time) handles bolted faults up to the Isd setting, with delay adjustable 0–0.4 s (I²t on or off). I (instantaneous) catches high-magnitude faults with no intentional delay. R (residual) is the integrated earth-leakage protection, Class A, switchable via the IΔn rotary. That means one trip unit covers overcurrent, short-circuit, and ground-fault protection without an external module. The 4P configuration supports multiple neutral protection modes: 3D + N/2 (half-rated neutral), 4D (full-rated), 3D + OSN (oversized neutral), or no neutral protection. Neutral position is left, fixed-mount only. ## Integration notes The trip unit snaps into the ComPacT NSX100–250 fixed-mount breaker. The LCD display and local signalling LEDs (green ready, red overload at 105% Ir, orange pre-alarm at 90% Ir) give you status at a glance without opening the door.","metaTitle":"Schneider Electric C1047E040 MicroLogic 7.2 E Trip Unit, 40","metaDescription":"Schneider Electric C1047E040 MicroLogic 7.2 E electronic trip unit for ComPacT NSX. 40 A at 40 °C, 4P, LSIR protection, integrated earth leakage. EN/IEC 60947-2. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"440 V AC 50/60 Hz","IP Rating":"IP40","Application":"Distribution","Display Type":"LCD display","Product Status":"Active","Trip Unit Type":"Electronic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,241.34 – $1,377.05","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/36b28234bf60c6a757267d8c0f0c9de5.pdf","sourceUrl":"https://www.se.com/hk/en/product/C1047E040/trip-unit-micrologic-7-2-e-for-compact-nsx-100-160-250-circuit-breakers-electronic-rating-40a-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C1047E040/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C1047E040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C1047E040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}