{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"C104TM016C","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"C104TM016C","canonicalUrl":"https://aoctrl.com/schneider/C104TM016C","factsUrl":"https://aoctrl.com/api/mcp/products/C104TM016C","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric ComPacT NSX100...250, TM-D trip unit, thermal-magnetic, 16 A at 50 °C, 4 poles 4D, EN/IEC 60947-2.","salesMarkdown":"The Schneider Electric C104TM016C is a TM-D thermal-magnetic trip unit for the ComPacT NSX100...250 range, rated 16 A at 50 °C, 4 poles (4D), and built to EN/IEC 60947-2. It provides LI protection — thermal overload (L) and magnetic short-circuit (I) — with a fixed instantaneous pickup of 190 A and an adjustable long-time pickup from 0.7 to 1 x In. The 16 A rating at 50 °C sets the continuous current the trip unit can carry without nuisance tripping in a warm panel — if your ambient is higher, you must derate. The 190 A fixed instantaneous pickup means magnetic trips occur at roughly 12 x In, which is typical for distribution-level short-circuit protection per EN/IEC 60947-2. The 4D protected poles (all four poles with neutral protection set to 1 x Ir) suit a 4-wire distribution system where the neutral is not fully rated. ## Integration Notes This trip unit snaps into a ComPacT NSX100...250 fixed-mount circuit breaker. The IP40 front-of-panel protection (IEC 60529) is sufficient for enclosed distribution boards but not for washdown environments.","metaTitle":"Schneider Electric C104TM016C ComPacT NSX TM16D Trip Unit, 1","metaDescription":"Schneider Electric C104TM016C ComPacT NSX TM-D trip unit, 16A at 50°C, 4P, thermal-magnetic, EN/IEC 60947-2. Obsolete — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Voltage":"690 V AC 50/60 Hz 750 V DC","IP Rating":"IP40","Application":"Distribution","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-50...85 °C","Main Product Or Component Type":"Trip unit","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bf94ea419779db9110fe46497e290006.pdf","sourceUrl":"https://www.se.com/ae/en/product/C104TM016C/trip-unit-tm16d-for-compact-nsx100-circuit-breakers-thermal-magnetic-rating-16a-50-degrees-c-4-poles-4d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/C104TM016C/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/C104TM016C","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/C104TM016C when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}